37
CAUTION
11.3 Indoor
Unit
11.3.1 How to Fix Installation Plate
The mounting wall is strong and solid enough to prevent
it from vibration.
The centre of installation plate should be at more than
551 mm at right and left of the wall.
The distance from installation plate edge to ground
should more than 1550 mm.
Always mount the installation plate horizontally by
aligning the marking thread and using a level gauge.
Mount the installation plate on the wall with 6 sets of
plug, bolt and washer (all non-supply) with size M8.
11.3.2 To Drill a Hole in the Wall and Install
a Sleeve of Piping
1 Insert the piping sleeve to the hole.
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
from the wall.
When the wall is hollow, please be sure to use the
sleeve for tube assembly to prevent dangers caused
by mice biting the connecting cable.
4 Finish by sealing the sleeve with putty or
caulking compound at the final stage.
11.3.3 Indoor Unit Installation
11.3.3.1 Install the Indoor Unit
1 When connecting solar pump station cable
between indoor unit and solar pump station, the
distance between both apparatuses shall be 2 ~
8 meters and the length of the said cable must
be shorter than 10 meter. Fail to do so may lead
to abnormal operation to the system.
2 Engage the slots on the indoor unit to the hooks
of installation plate
1
. Ensure the hooks are
properly seated on the installation plate by
moving it left and right.
3 Fix the screws
5
to the holes on the hooks of
installation plate,
6
, as illustrated below.
11.3.3.2 Water Piping Installation
The minimum requirement of water in the system is
50 litres (for 12.0kW~16.0kW) and 30 litres (for
9.0kW). If these values could not be achieved,
please install additional buffer tank (field supply).
Water inlet and water outlet in indoor unit are used
for connection to water circuit. Please request a
licensed technician to install this water circuit.
This water circuit must comply with all relevant
European and national regulations, i.e. IEC/EN
61770.
Be careful not to deform the piping with excessive
force when doing piping connection job.
Do not install any valve between indoor unit and
water piping to avoid accidental closure of water
supply to the indoor unit.
Use Rp 1¼” nut for both water inlet and outlet
connection and clean all pipings with tap water
before install.
Cover the pipe end to prevent dirt and dust when
inserting it through a wall.
Choose proper sealer which can withstand the
pressures and temperatures of the system.
Содержание WH-SDC09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 4 1 2 Weekly Timer Setting ...
Страница 18: ...18 4 1 3 Setting Up the Special Functions ...
Страница 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Страница 21: ...21 5 2 Outdoor Unit ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Страница 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC09C3E8 ...
Страница 27: ...27 8 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Страница 28: ...28 8 2 Outdoor Unit ...
Страница 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC09C3E8 ...
Страница 30: ...30 9 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Страница 31: ...31 9 2 Outdoor Unit ...
Страница 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Страница 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Страница 50: ...50 Solar Priority is Set Solar Priority is Not Set ...
Страница 53: ...53 Heat Tank Heating No Priority Solar Priority Set ...
Страница 54: ...54 Heat Tank Heating No Priority Solar Priority Not Set ...
Страница 64: ...64 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 65: ...65 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 113: ...113 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 114: ...114 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 137: ...137 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Страница 138: ...138 ...