8
Item
Unit
Mono Bloc Unit
Starting Current
A
22.0
Running Current
A
Cooling: 22.0
Heating: 17.3
Cooling: -
Heating: 18.3
Maximum Current For Mono Bloc Unit
A
26.0
Power Factor
%
Cooling: 94
Heating: 94
Cooling: -
Heating: 94
Power factor means total figure of compressor and outdoor fan motor.
Power Cord
Number of core
-
Length
m (ft)
-
Thermostat
Electronic Control
Protection Device
Electronic Control
Item
Unit
Water System
Performance Test Condition
EN 14511
Operation Range
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 25 ~ 55
Internal Pressure Differential
kPa
Cooling: 42.2
Heating: 72.0
Water Pipe Diameter
Inlet
mm (inch)
30 (1-3/16)
Outlet
mm (inch)
30 (1-3/16)
Water Drain Hose Inner Diameter
mm (inch)
15.00 (19/32)
Pump
Motor Type
DC Motor
No. of Speed
7 (software selection)
Input Power
W
112
Hot Water Coil
Type
Brazed Plate
No. of Plates
36
Size (H × W × L)
mm
65 × 120 × 376
Water Flow Rate
l/min (m
3
/h)
Cooling: 35.0 (2.1)
Heating: 45.9 (2.8)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 265 and below
Flow Switch
Magnetic Lead Switch
Protection Device
A
Residual Current Circuit Breaker (30)
Expansion Vessel
Volume
I
10
MWP
bar
3
Capacity of Integrated Electric Heater
kW
6.00
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled water inlet temperature
of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled water inlet temperature of 30°C and water outlet temperature of 35°C.
Specification are subjected to change without prior notice for further improvement.