 WARNING 

18. 

This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective 
national wiring rules or country-specific safety measures in terms of residual current. 

 

19. 

The unit is only for use in a closed water system. Utilization in an open water system may lead to excessive corrosion of the water 
piping and risk of incubating bacteria colonies, particularly Legionella, in water. 

 

20.  If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and information. 

 

21.  Select a location where in case of water leakage, the leakage will not cause damage to other properties. 

 

22. 

When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no 
electrical contact between equipment and building is allowed. Insulator must be installed in between. 

 

23. 

This installation may be subjected to building regulation approval applicable to respective country that may require to notify the local 
authority before installation. 

 

24. 

Any work carried out on the Mono bloc unit after removing the front panel which is secured by screws, must be carried out under the 
supervision of authorized dealer and licensed installation contractor. 

 

25. 

This unit must be properly earthed, the electrical earth must not be connected to a gas pipe, water pipe, the earth of a lightening rod or 
a telephone. Otherwise there is a danger of electrical shock in the event of an insulation breakdown or electrical earth fault in the 
Mono bloc unit. 

 

 

 CAUTION 

1. 

Do not install the Mono bloc unit in areas where there is a risk of flammable gas leakage. There is a risk of fire if flammable gas 
accumulates near or around the Mono bloc unit. 

 

2. 

Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the 
liquid refrigerant, it may cause frostbite. 

 

3. 

Make sure the power supply cord does not contact with hot part (i.e. water piping). High temperature may cause insulator of power 
supply cord damage hence electrical shock or fire. 

 

4.  Do not touch the sharp aluminium fin, sharp parts may cause injury.  

 

 

5. 

Do not apply excessive force to water pipes that may damage the pipes. If water leakage occurs, it will cause flooding and damage to 
other properties. 

 

6. 

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water leakage may happen and may 
cause damage to properties of the user. 

 

7. 

The piping installation work must be flushed before the Mono bloc unit is connected to remove contaminants. Contaminants may 
damage the Mono bloc unit components. 

 

8.  Select an installation location where it is accessible for maintenance. 

 

9. 

Power supply connection to Mono bloc unit. 

 

Power supply point should be in easily accessible place for power disconnection in case of emergency. 

 

Must follow local national wiring standard, regulation and this installation instruction. 

 

Strongly recommended to make permanent connection to a circuit breaker. It must be a double pole switch with a minimum 
3.0 mm gap. 

Power supply 1: Use approved 30A circuit breaker. 

Power supply 2: Use approved 30A circuit breaker. 

 

10.  Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire. 

 

11. 

After installation, the installer is obliged to verify correct operation of the Mono bloc unit. Check the connection point for water leakage 
during test run. If leakage occurs, it will cause damage to other properties. 

 

12. 

Installation work. 
Four or more people are required to carry out the installation work. The weight of Mono bloc unit might cause injury if carried by less 
than four people. 

 

 
 
 
 
 
 
 
 
 
 

Содержание WH-MDC12G6E5

Страница 1: ...dvise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death PRECAUTION OF LOW TEMPERATURE In order to avoid frost...

Страница 2: ...ire 3 Do not tie up the power supply cord into a bundle by band Abnormal temperature rise on power supply cord may happen 4 Do not insert your fingers or other objects into the unit high speed rotating fan may cause injury 5 Do not sit or step on the unit you may fall down accidentally 6 Keep plastic bag packaging material away from small children it may cause suffocation 7 Do not use pipe wrench ...

Страница 3: ...bloc unit 2 Do not release refrigerant during piping work for installation re installation and during repairing a refrigeration parts Take care of the liquid refrigerant it may cause frostbite 3 Make sure the power supply cord does not contact with hot part i e water piping High temperature may cause insulator of power supply cord damage hence electrical shock or fire 4 Do not touch the sharp alum...

Страница 4: ...nput Power W Output Power W 60 Fan Speed rpm Cooling 600 Top Fan 640 Bottom Fan Heating 510 Top Fan 550 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 903 7 1295 4 38 1 Item Unit Mono Bloc Unit Dimension Height mm inch 1410 55 1 2 Width mm inch 1283 50 1 2 Depth mm inch 320 12 19 32 Net Weight kg lbs 147 324 Noise Level dB A Co...

Страница 5: ...ch 15 00 19 32 Pump Motor Type DC Motor No of Speed 7 software selection Input Power W 112 Hot Water Coil Type Brazed Plate No of Plates 36 Size H W L mm 65 120 376 Water Flow Rate l min m3 h Cooling 35 0 2 1 Heating 45 9 2 8 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Device A Residual Current Circuit Breaker 30 Expansion Vessel...

Страница 6: ...r protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Service Mode Button for servicing purpose Front maintenance design for Mono bloc unit Operation Condition Water outlet temperature C Ambient temperature C COOLING Maximum 20 43 Minimum 5 16 HEATING Maximum 55 35 Minimum 25 20 NOTICE When the outdoo...

Страница 7: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit Air inlet rear Air outlet Air inlet side Handle 2 pieces front and 2 pieces behind Cabinet Front Plate Top Plate ...

Страница 8: ... way Valve cable 3 min 0 5mm Booster Heater cord 3 min 1 5mm Room Themostat cable 4 or 3 min 0 5mm Tank OLP cable 2 min 0 5mm Tank Sensor cable 2 min 0 3mm External Controller cable 2 min 0 5mm Solar Three way Valve cable 3 min 0 5mm Solar Pump Station cable 2 min 0 5mm Type designation 60245 IEC 57 or heavier cord cable Remote Control Power Supply 1 Power Supply 2 7 It is advisable to avoid more ...

Страница 9: ...20 5 Dimensions 5 1 Mono Bloc Unit 579 400 356 154 1410 615 426 5 175 275 413 30 c c 70 277 320 152 1283 256 30 293 318 5 50 45 45 45 83 5 Unit mm Top View Front View Back View Side View Side View ...

Страница 10: ... Air Purge Valve Water Flow Switch Water Pump Water Inlet Connect to Sanitary Tank Water Outlet Connect to Sanitary Tank Drain Refrigerant Cycle Heating Water Cycle Heat Exchanger Heat Exchanger Strainer Strainer Receiver 4 Way Valve 2 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve Pressure Switch High Pressure Sensor Compressor Water Pressure Gauge Capillary Tube Expansion Valve Refrigera...

Страница 11: ...L2 YLW HT1 L2 ORG O Y W CN OLP1 WHT B B OLP 80 3 C 1 2 CN FLOW YLW CN TH1 WHT CN TH3 WHT CN TH2 WHT CN OLP2 WHT CN RCV2 WHT CN THERMO WHT FLOW SWITCH WATER OUTLET TEMP SENSOR THERMISTOR WATER INLET TEMP SENSOR THERMISTOR REFRIGERANT TEMP SENSOR THERMISTOR BL 2 1 1 6 3 3 BL 1 1 HEX WATER OUTLET TEMP SENSOR THERMISTOR 1 1 1 2 3 2 NOISE FILTER CIRCUIT G 1 4 5 6 7 BL RECTIFICATION CIRCUIT RECTIFICATIO...

Страница 12: ...WHT WHITE RED DC P CN EV 6 2 CN RY1 SWITCHING POWER SUPPLY CIRCUIT RECTIFICATION CIRCUIT PFC CIRCUIT DCN IN AC C BLUE DC N BLACK 2 DCN 2 BLACK FUSE 1 CN FM2 WHITE 1 4 7 7 4 2 CN FM1 CN PS W1 LOWER FAN MOTOR BLACK V U U RED P N V BLUE RED BLUE BLACK FG201 GREEN 3 2 WAY VA LVE MS R 1 DC P IN WHITE BL CAPACITOR ELECTRONIC CONTROLLER AC C BLACK B 1 CN ACL RY V1 AC BLK01 OPTIONAL 4 REA CTOR W GR W RELA...

Страница 13: ... the pump speed 4 Press OFF ON button to exit PUMP SPEED ADJUST MODE During PUMP SPEED ADJUST MODE we can select AIR PURGE function by pressing FORCE button In AIR PURGE function the pump will operate ON and OFF for 10 minutes to purge the air in the hydraulic system Press again the FORCE button to exit AIR PURGE function PUMP SPEED ADJUST MODE will stop operation 0 10 13 20 30 40 50 70 60 WATER F...

Страница 14: ... temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 1 000 2 000 3 000 4 000 5 000 6 000 1 10 000 11 500 13 000 14 500 16 000 17 500 15 11 7 3 1 5 9 13 17 21 25 15 11 7 3 1 5 9 13 17 21 25 ...

Страница 15: ...ure 35 C DBT C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 1 000 2 000 3 000 4 000 5 000 6 000 16 19 22 25 28 31 34 37 40 43 6 000 8 000 10 000 12 000 14 000 16 000 16 19 22 25 28 31 34 37 40 43 ...

Страница 16: ... 12000 2960 12000 3390 12000 4100 25 12000 1380 12000 1660 11800 1940 11700 2230 11400 2740 is rating based on T 8 18 2 2 WH MDC16G6E5 Water Out C 30 35 40 45 55 Outdoor Air C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 15 10600 4090 10300 4380 10000 4670 9700 4960 7900 4840 7 11900 4030 11400 4430 10800 4830 10300 52...

Страница 17: ...10000 1730 25 12080 2900 15700 3050 10000 1970 35 10000 3560 12000 3670 10000 2150 43 7800 3800 11100 3190 8000 2850 18 3 2 WH MDC16G6E5 Water Out C 7 14 18 OD Ambient C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 16 9200 1620 16400 2580 12200 2450 25 14400 3920 19200 3830 12200 2790 35 12200 4760 15000 4980 12200 2960 43 7750 3400 13800 5950 9700 4000 ...

Отзывы: