12.13 Sterilization Mode
Purpose:
o
Boil tank temperature to customer set boiling temperature to operate sterilization.
Control start condition:
o
Tank connection set to YES by remote controller
o
Sterilization function selection is YES
o
Sterilization signal received from remote controller by timer.
Control
stop
condition:
o
After boiling timer completed. Boiling timer start counting once tank achieve boiling set temperature OR
o
After 4 hours of operation since sterilization function start OR
Control
content:
o
Once the sterilization function enable, set the target tank temperature to Boiling Set Temperature.
o
Booster heater will allow to ON during solar priority SET condition.
Booster heater OFF Temp. = Boiling Set Temperature 0°C
Booster heater ON Temp. = Boiling Set Temperature - 7°C
o
The sterilization set temperature may not achieve if tank booster heater function is deactivated.
o
Boiling timer which set by remote controller will start count after tank achieve boiling set temperature.
o
Sterilization
operation
will end after complete boiling timer or Max 4 hrs from function start.
o
Target tank temperature will set back to normal tank set temperature.
* Tank heater control is not affected by solar pump when solar priority set.
12.14 Quiet Operation
Purpose:
- To provide quiet operation compare to normal operation by reduces Mono bloc unit noise.
Starting
condition:
1 When quiet button is presses.
2 When quiet request ON time by weekly timer (Refer to remote control.)
When any of above mentioned condition is achieved, this control is activated.
New target FM speed = Present target FM speed - 80 rpm
Minimum target FM speed = 200 rpm
Cancellation
condition:
1 Cancel by press quiet button
2 Stop by OFF/ON button
3 When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
12.15 Anti Freeze Control
Anti freeze protection control can be select YES or NO from control panel. Default setting is YES.
In heatpump system, there are 2 types of anti freeze control:
1. Water pump circulation anti frost control
Water pump turns ON when
ALL
the below conditions are fulfilled:
o
Heatpump OFF (standby) OR water pump stop (Tank Mode) OR error occurs
o
Water flow switch is not abnormal
o
Outdoor ambient temp. < 3°C
o
Water inlet/outlet temp. < 6°C
o
After 5 minutes from previous water pump OFF
Water pump turns OFF when
ANY
of the below conditions is fulfilled:
o
Outdoor ambient temp.
≥
4°C
o
During -5°C < outdoor ambient temp. < 4°C
After water pump ON for 4 minutes, and water inlet/outlet temp.
≥
8°C
Else, shift to backup heater anti freeze control
o
During outdoor ambient temp. < -5°C
After water pump ON for 4 minutes, and water inlet/outlet temp.
≥
20°C
Else, shift to backup heater anti freeze control
However, if flow switch is abnormal (H62), then water pump circulation anti freeze control will not activate.
Содержание WH-MDC06E3E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Страница 11: ...11 4 1 1 Main Components ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 4 1 3 Weekly Timer Setting ...
Страница 16: ...16 4 1 4 Setting Up The Special Functions ...
Страница 17: ...17 5 Dimensions 5 1 Mono Bloc Unit ...
Страница 18: ...18 6 Refrigeration and Water Cycle Diagram ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram ...
Страница 21: ...21 8 Wiring Connection Diagram ...
Страница 22: ...22 ...
Страница 23: ...23 9 Electronic Circuit Diagram ...
Страница 24: ...24 ...
Страница 25: ...25 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 26: ...26 10 1 2 Solar Printed Circuit Board Optional ...
Страница 27: ...27 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 28: ...28 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 29: ...29 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 30: ...30 Main Components ...
Страница 39: ...39 Cool Mode Operation Time Chart 12 1 4 Cool Tank Mode Operation ...
Страница 41: ...41 ...
Страница 42: ...42 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 59: ...59 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 60: ...60 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 109: ...109 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge ...
Страница 110: ...110 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 117: ...117 18 4 Hydraulic Pump Performance ...
Страница 118: ...118 19 Exploded View and Replacement Parts List 19 1 WH MDC06E3E5 WH MDC09E3E5 Refrigerant System ...
Страница 119: ...119 ...
Страница 122: ...122 19 2 WH MDC06E3E5 WH MDC09E3E5 Water System ...