17

Signal inputs

Optional 
Thermostat

L N =AC230V, Heat, Cool=Thermostat heat, Cool terminal

External 
control

Dry contact  Open=not operate, Short=operate (System setup necessary) 
Able to turn ON/OFF the operation by external switch

Remote 
controller

Connected (Please use 2 cores wire for relocation and extension. Total 
cable length shall be 50m or less.)

Outputs

3-way valve

AC230V  N=Neutral  Open, Close=direction (For 
circuit switching when connected to DHW tank)

AC230V, 12 VA

2-way valve

AC230V  N=Neutral  Open, Close (Prevent water 
circuit pass through during cooling mode)

AC230V, 12 VA

Extra pump

AC230V (Used when Tank Unit pump capacity is 
insuffi cient)

AC 230V, 

0.6 A max

Boiler contact / 
Defrost signal

Dry contact (System setup necessary)

Thermistor inputs

Zone 1 room 
sensor

PAW-A2W-TSRT

Outdoor air sensor PAW-A2W-TSOD (Total cable length shall be 30m or less)

Connection of Optional PCB (CZ-NS5P)

Ext. 
comp. 
SW

Heat/
Cool 
SW

SG 
signal

Bit1

Bit2

Vcc

Solar 
sensor

Mixing 
valve 2

Mixing 
valve 1

Optional 
Thermostat 2

Demand 

signal

Zone 1 

water 

sensor

Zone 2 

water 

sensor

Pool 

water 

sensor

Zone 2 

room 

sensor

Zone 1 
Pump

Error 
signal

Pool 
Pump

Solar 
Pump

Zone 2 
Pump

L

N Cool Heat

N

O

C

N

O

C

Signal inputs

Optional Thermostat

L N =AC230V, Heat, Cool=Thermostat heat, Cool terminal

SG signal

Dry contact  Vcc-Bit1, Vcc-Bit2  open/short (System 
setup necessary)
Switching SW (Please connect to the 2 contacts controller)

Heat/Cool SW

Dry contact  Open=Heat, Short=Cool (System setup 
necessary)

External comp.SW

Dry contact  Open=Comp.OFF, Short=Comp.ON 
(System setup necessary)

Demand signal

DC 0~10V (System setup necessary)
Please connect to the DC 0~10V controller.

Outputs

Mixing valve

AC230V N=Neutral Open, 

Close=mixture 

direction

Operating time: 30s~120s

AC230V, 6VA

Pool pump

AC230V

AC 230V, 0.6 A max

Solar pump

AC230V

AC 230V, 0.6 A max

Zone pump

AC230V

AC 230V, 0.6 A max

Thermistor inputs

Zone room sensor

PAW-A2W-TSRT

Buffer tank sensor

PAW-A2W-TSBU

Pool water sensor

PAW-A2W-TSHC

Zone water sensor PAW-A2W-TSHC
Solar sensor

PAW-A2W-TSSO

Recommended External Device Specifi cation

 

This section explains about the external devices (optional) 
recommended by Panasonic. Please always ensure to use the 
correct external device during system installation. 

 

For optional sensor.

1.  Buffer tank sensor: PAW-A2W-TSBU

Use for measurement of the buffer tank temperature.
Insert the sensor into the sensor pocket and paste it on the 
buffer tank surface.

40

black

brown

blue

Dimensions (mm)

Ø6

2.  Zone water sensor: PAW-A2W- TSHC

Use to detect the water temperature of the control zone.
Mount it on the water piping by using the stainless steel metal 
strap and contact paste (both are included).

93

70

35

Dimensions (mm)

3.  Outdoor sensor: PAW-A2W-TSOD

If the installation location of the outdoor unit is exposed to direct 
sunlight, the outdoor air temperature sensor will be unable to 
measure the actual outdoor ambient temperature correctly.
In this case, optional outdoor temperature sensor can be fi xed at a 
suitable location to more accurately measure ambient temperature.

70

93

46

Dimensions (mm)

4.  Room sensor: PAW-A2W- TSRT

Install the room temperature sensor to the room which requires 
room temperature control.

Dimensions (mm)

86

86

60

30

5.  Solar sensor: PAW-A2W-TSSO

Use for measurement of the solar panel temperature.
Insert the sensor into the sensor pocket and paste it on the solar 
panel surface.

40

black

brown

blue

Dimensions (mm)

Ø6

6.  Please refer to the table below for sensor characteristic of the 

sensors mentioned above.

Temperature 

(°C)

Resistance 

(k

Ω

)

Temperature 

(°C)

Resistance 

(k

Ω

)

30

5.326

150

0.147

25

6.523

140

0.186

20

8.044

130

0.236

15

9.980

120

0.302

10

12.443

110

0.390

5

15.604

100

0.511

0

19.70

90

0.686

-5

25.05

80

0.932

-10

32.10

70

1.279

-15

41.45

65

1.504

-20

53.92

60

1.777

-25

70.53

55

2.106

-30

93.05

50

2.508

-35

124.24

45

3.003

-40

167.82

40

3.615

35

4.375

Содержание WH-ADC0509L3E5

Страница 1: ...cause these important contents are related to safety The meaning of each indication used is as below Incorrect installation due to ignorance or negligence of the instructions will cause harm or damage and the seriousness is classified by the following indications Please leave this installation manual with the unit after installation WARNING This indication shows the possibility of causing death or...

Страница 2: ...on approval applicable to respective country that may require to notify the local authority before installation The Tank Unit must be shipped and stored in upright condition and dry environment It may laid on its back when being moved into the building Work done to the Tank Unit after remove the front plate cover that secured by screws must be carried out under the supervision of authorized dealer...

Страница 3: ...ow Sensor g Water Pressure Sensor h Front Plate i Top Plate j Right Plate k Left Plate l Rear Plate m Tank Sensor Not Visible n Bushing 4 pieces o Safety Relief Valve p Network Adaptor Holder q Electric Anode Bar NotVisible Applicable only forWH ADC0509L3E5AN and WH ADC0509L6E5AN r Electric anode PCB NotVisible Applicable only forWH ADC0509L3E5AN and WH ADC0509L6E5AN Main Components Diagram Field ...

Страница 4: ...Tank Unit A place where air circulation in the room is good A place where drainage can be easily done e g Utility room A place where Tank Unit s operation noise will not cause discomfort to the user A place where Tank Unit is far from door way A place where accessible for maintenance Ensure to keep minimum distance of spaces as illustrated below from wall ceiling or other obstacles A place where f...

Страница 5: ...late the water circuit pipes to prevent reduction of heating capacity After installation check the water leakage condition in connection area during test run Failure to connect the tube appropriately might cause the Tank Unit malfunction Protection From Frost If the Tank Unit is being exposed to frost while power supply failure or pump operating failure drain the system When water is idle inside t...

Страница 6: ...of this pipework must be in such a way so that the outlet is visible and can not cause any damage Keep away from electrical components It is recommended to fit a tundish into this g pipework Tundish should be visible and positioned away from frost environment and electrical components WARNING This section is for authorized and licensed electrician only Work behind the Control Board Cover 5 secured...

Страница 7: ...ap g 2 Set all Tap Shower OPEN 3 Start filling water to the Domestic Hot Water Tank via Tube Connector i After 20 40min water should flow out from Tap Shower Else please contact your local authorized dealer 4 Check and make sure no water leaking at the tube connecting points 5 Set the Domestic Hot Water Tank Discharge Drain Tap g to OPEN for 10 seconds to release air from this pipeline Then set it...

Страница 8: ...ed in the Outdoor Unit 1 Confirm that the pressure relief valve is working properly Pull the lever horizontal direction 2 Release the lever when water comes out of the drain pipe of the pressure relief valve While the air continues to come out of the drain pipe keep raising the lever to completely discharge the air 3 Confirm that the water from the drain pipe stops 4 If water is leaking pull the l...

Страница 9: ...ove of the case 5 For embedded type Preparation Make 2 holes for screws using a driver Avoid the wire being caught Mount the top case Align the claws of the top case and then align the claws of the bottom case Screws field supply Bottom case Back side Top case Back side Remote controller terminal board Remove the coating Approx 6 mm Make sure the wiring connection is in the correct direction Mount...

Страница 10: ...t water piping connections Has the heat insulation been carried out at water piping connection Is the Pressure Relief Valve operation normal Is water pressure higher than 0 5 bar Is the water drainage work properly done Is the power supply voltage within the rated voltage range Is the cables being fixed to RCCB ELCB and terminal board firmly Is the cables being clamped firmly by holder clamper Is ...

Страница 11: ...roller Floor heating Indoor Connect floor heating or radiator directly to the Tank Unit Remove remote controller from Tank Unit and install it in the room where floor heating is installed This is an application that uses remote controller as Room Thermostat 3 External Room Thermostat Outdoor Room Thermostat Field supply Floor heating Indoor Connect floor heating or radiator directly to Tank Unit R...

Страница 12: ...nk It requires connection setting of buffer tank and T temperature setting at heating operation separately This system requires Optional PCB CZ NS5P Note Buffer tank thermistor must be connected to main indoor PCB only Outdoor Radiator Thermistor 1 Thermistor 2 Buffer tank Pump 2 Pump 1 Mixing valve 1 Indoor Floor heating Connect floor heating or radiator to 2 circuits through buffer tank as shown...

Страница 13: ...lected not display on remote controller Indoor Outdoor Simple 2 zone Floor heating Radiator Thermistor 2 Thermistor 1 Pump 2 Mixing valve Indoor Outdoor Radiator This is an example of simple 2 zone control without using buffer tank Built in pump from Tank Unit served as a pump in zone 1 Install mixing valve pump and thermistor specified by Panasonic on zone 2 circuit Please be sure to assign high ...

Страница 14: ...it to compensate for insufficient capacity by operate boiler when outdoor temperature drops heat pump capacity is insufficient Boiler is connected parallel with heat pump against heating circuit Besides that an application that connects to the DHW tank s circuit to heat up tank s hot water is also possible Boiler output can be control by either SG ready input from optional PCB or Auto control by 3...

Страница 15: ...wer Supply 1 cord Power Supply 2 cord Indoor Unit Outdoor Unit Connecting cable For connection to Optional PCB 7 1 By connecting Optional PCB 2 Zone temperature control can be achieved Please connect mixing valves water pumps and thermistors in zone 1 and zone 2 to each terminals in Optional PCB Temperature of each zone can be controlled independently by remote controller 2 Pump zone 1 and zone 2 ...

Страница 16: ... cable Mixing valve zone 1 cable Mixing valve zone 2 cable 2 way valve cable Extra pump cable Boiler contact cable D 1 and D 2 Bushings are for External control cable Outdoor air sensor cable Remote controller cable Room sensor zone 1 cable Room sensor zone 2 cable Buffer tank sensor cable Pool sensor cable Water sensor zone 1 cable Water sensor zone 2 cable Demand signal cable Solar sensor cable ...

Страница 17: ... Zone pump AC230V AC 230V 0 6 A max Thermistor inputs Zone room sensor PAW A2W TSRT Buffer tank sensor PAW A2W TSBU Pool water sensor PAW A2W TSHC Zone water sensor PAW A2W TSHC Solar sensor PAW A2W TSSO Recommended External Device Specification This section explains about the external devices optional recommended by Panasonic Please always ensure to use the correct external device during system i...

Страница 18: ...cuit board Pull the cable out of the Tank Unit so that there is no pinching If an Optional PCB has been installed in the Tank Unit connect to the CN CNT connector of the Optional PCB 2 Insert a flat head screwdriver into the slot on the top of the adaptor and remove the cover Connect the other end of the CN CNT cable connector to the connector inside the adaptor Slot Connector 3 Pull the CN CNT ca...

Страница 19: ...t direct water temp Set pool temp 4 Display Heat temp Display current heating temperature it is set temperature when enclosed by line 5 Display tank temp Display current tank temperature it is set temperature when enclosed by line 6 Outdoor temp Display outdoor temp 3 1 Remote Controller Outline The LCD display as shown in this manual are for instructional purpose only and may differ from the actu...

Страница 20: ...ll be recognised as main remote controller Set language confirm Clock format 12 00am Mon 24h am pm Select Confirm When language is set setting screen of time display appears 24h am pm Set time display confirm Date time 12 00am Mon Year Month Day Hour Min 2015 01 01 12 00 Select Confirm YY MM DD Time setup screen appears Set YY MM DD Time confirm Front grille 12 00am Mon Is O D front grille fixed N...

Страница 21: ...ction Yes No Tank setup Solar setup 12 Only when the selection for Optional PCB is Yes External Error signal Yes No 13 Only when the selection for Optional PCB is Yes Demand control Yes No 14 Only when the selection for Optional PCB is Yes SG ready Yes No Capacity setup 15 Only when the selection for Optional PCB is Yes External Compressor SW Yes No 16 Circulation liquid Water glycol 17 Only when ...

Страница 22: ...Tank is Yes except for AIO 33 Outdoor temp for Cool to Heat Cool Heat change temp setup 34 Tank Floor operation time max Max operation time for Heat Cool mode setup 35 Tank heat up time max Max operation time for Tank mode setup 36 Tank re heat temp Tank re heat temp setup 37 Sterilization Sterilization day and temp and time setup 38 Service setup Pump maximum speed Pump maximum speed setup Air pu...

Страница 23: ...ting Depend on model System setup 12 00am Mon Optional PCB connectivity Zone Sensor Heater capacity Anti freezing Select Confirm If there is built in Heater set the selectable heater capacity NOTE There are models which cannot select Heater capacity 4 Anti freezing Initial setting Yes System setup 12 00am Mon Optional PCB connectivity Zone Sensor Heater capacity Anti freezing Select Confirm Operat...

Страница 24: ...YES After that please begin setting according to remote controller instruction Boiler icon will be displayed on remote controller top screen After Bivalent connection Set YES there is two option of control pattern to be select SG Ready Auto 1 SG ready Only available to set when optional PCB set to YES SG Ready input from optional PCB terminal control ON OFF of boiler and heat pump as below conditi...

Страница 25: ...iler control characteristic in order to select the optimal setting for the system 3 Smart There are Energy price both electricity and boiler and Schedule to be set on remote controller Operation setting of Energy price and Schedule shall be responsible by installer Based on these settings system will calculate the final price for both electricity and boiler When final price of Electricity is lower...

Страница 26: ...8 6 85 1 4 1 6 15 5 2 55 50 8 7 90 85 1 7 20 15 5 3 8 8 1 8 5 4 5 6 55 8 9 9 1 90 1 9 2 1 20 5 7 60 55 9 2 95 90 2 2 25 20 5 8 9 3 2 3 5 9 6 1 60 9 4 9 6 95 2 4 2 6 25 6 2 65 60 9 7 100 95 2 7 30 25 6 3 9 8 2 8 6 4 6 6 65 9 9 100 2 9 3 1 30 6 7 70 65 A minimum operating current is applied on each model for protection purpose 0 2 voltage hysteresis is provided The value of voltage after 2nd decimal...

Страница 27: ...ter Initial setting Manual System setup 12 00am Mon External compressor SW Circulation liquid Heat Cool SW Force Heater Select Confirm Under manual mode user can turn on force heater through quick menu If selection is auto force heater mode will turn automatically if pop up error happen during operation Force heater will operate follow the latest mode selection mode selection is disable under forc...

Страница 28: ...t cool meter and Tank meter Both systems can provide all generation data of heating cooling and DHW directly from external meter If Heat cool meter is set to Yes it will read from external meter for heat pump s energy generation data during heating cooling and DHW operation 1 If Heat cool meter is set to No it will base on unit s calculation for heat pump s energy generation data during heating co...

Страница 29: ...tting range is 1 C 15 C 29 Heater ON OFF 0 C OFF ON a Outdoor temp for heater ON Initial setting 0 C Set outdoor temp when back up heater starts to operate Setting range is 20 C 15 C User shall set whether to use or not to use heater b Heater ON delay time Initial setting 30 minutes Set delay time from compressor ON for heater to turn ON if not achieve water set temperature Setting range is 10 min...

Страница 30: ...utdoor temp for Cool to Heat Initial setting 10 C 10 C Heat Cool Outdoor temp dropping Set outdoor temp that switches from Cooling to Heating by Auto setting Setting range is 5 C 14 C Timing of judgement is every 1 hour Tank 34 Floor operation time max Initial setting 8h Heat Tank 30min 10h Set max operating hours of heating When max operation time is shortened it can boil the tank more frequently...

Страница 31: ...ring room side operation 39 Dry concrete 30 C 1 2 3 4 5 6 35 C 35 C 40 C 40 C 45 C Stage Operate concrete curing operation Select Edit set temp for every stage 1 99 1 is for 1 day Setting range is 25 55 C When it is turned ON dry concrete starts When it is 2 zone it dries both zones 40 Service contact Contact 1 Bryan Adams ABC abc 0 9 Other A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a b c...

Страница 32: ...r NOTE It is different from to use not to use backup heater set by client When this setting is used heater power on due to protection against frost will be disabled Please use this setting when it is required by utility company By using this setting it cannot defrost due to low Heating s setting temp and operation may stop H75 Please set under the responsibility of installer When it stops frequent...

Отзывы: