PACD011001C2
Function
Function Urban Multi “MX1, ME1 Series” Using R-22
43
Discharge Super
Heating (DSH)
Control
(DSH = Td - high pressure condensation saturation temperature)
During both the inverter and standard compressors are running, when the injection valve for either one
goes OFF and discharge super heating (DSH) continues for 10 minutes at temperature difference of less
than 10°C, the istandard compressor are controlled at 76 Hz or less+OFF for 3 minutes.
Control According
to Outdoor
Temperature
If the outdoor temperature exceeds 27°C when heating, forced thermostat OFF is carried out in order to
prevent a safety device from being tripped or a sensor malfunction.
1.13.2 ME1 Series
High Pressure (Hp) Control
Low Pressure (Lp) Control
Discharge Pipe Temperature (Td) Control
Inverter Current Control
Hp
≥
21.3kg/cm²
(2.087MPa)
Hp
≥
23.0kg/cm²
(2.254MPa)
Hp>25.0kg/cm²
(2.450MPa)
Hp>27.5kg/cm²
(2.695MPa)
Heat exchanger
capacity control
76Hz+OFF
Forced thermostat OFF
Up to 2 times
in 30 minutes
E3 stop due
to malfunction
(VF001)
Lp>2.0kg/cm²
(0.196MPa)
DSH>15˚C
&
Lp<1.2kg/cm²
(0.118MPa)
LP<0.8
R1T>5ºC
LP<0.5
R1T
≤
5ºC
Lp<0.3kg/cm²
(0.029MPa)
Lp<0kg/cm²
(0MPa)
(Cooling)
30Hz+OFF
(Heating, simultaneous cool / heat operation)
Hot gas bypass
valve ON
106Hz+OFF
or
60Hz+ON
Injection valve ON
Lp<1.7kg/cm²
(0.167MPa)
Forced thermostat
OFF
Up to 2 times
in 30 minutes
E4 stop due
to malfunction
Hot gas bypass
valve ON
(VF002)
&
&
or
LP<0.8
R5T<Te + 10ºC
LP<0.5
R5T
≥
Te + 10ºC
&
&
or
Td
≥
130˚C
Td>105˚C
or
DSH>55˚C (DSH = Discharge Super Heating)
or
Td>90˚C&Lp<3kg/cm² (Control during cooling)
or (0.294MPa)
Td>90˚C&Lp<1.0kg/cm²
or (0.098MPa)
(Injection solenoid valve ON)
u
38Hz+OFF : Both high
u
106Hz+OFF(-): STD only high
u
38Hz+ON(-): INV only high
Td>135˚C
Forced thermostat OFF
Up to 2 times
in 100 minutes
Td
≥
135˚C
F3 stop due
to malfunction
(VF005)
( )
Control during heating
&
Simultaneous
cool / heat operation
INV
≥
15.0A(Y1)
FREQUENCY
1 STEP DOWN
L8 stop due
to malfunction
INV
≥
15.0A(Y1)
Forced thermostat OFF
UP to 4 times in 60 minutes
(VF004)
Содержание Urban Multi MX1R Series
Страница 13: ...PACD011001C2 xii Table of Contents ...
Страница 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Страница 35: ...Function PACD011001C2 14 Function Urban Multi MX1 ME1 Series Using R 22 1 1 3 CU 8 10ME1XPA Heat Recovery ...
Страница 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Страница 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Страница 171: ...Troubleshooting by Remote Controller PACD011001C2 150 Troubleshooting Urban Multi MX1 ME1 Series Using R 22 ...
Страница 237: ...Troubleshooting OP Unified ON OFF Controller PACD011001C2 216 Troubleshooting Urban Multi MX1 ME1 Series Using R 22 ...
Страница 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Страница 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Страница 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Страница 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Страница 359: ...Troubleshooting by Remote Controller PACD011001C2 338 Troubleshooting Urban Multi MX1R ME1R Series Using R 407C ...
Страница 425: ...Troubleshooting OP Unified ON OFF Controller PACD011001C2 404 Troubleshooting Urban Multi MX1R ME1R Series Using R 407C ...
Страница 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Страница 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Страница 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Страница 513: ...Troubleshooting by Remote Controller PACD011001C2 492 Troubleshooting UM Combination MA1R Series Using R 407C ...
Страница 585: ...Wiring Diagrams Outdoor Unit PACD011001C2 564 Appendix 1 2 ME1 Series Heat Recovery CU 8 10ME1XPA ...
Страница 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Страница 589: ...Wiring Diagrams Outdoor Unit PACD011001C2 568 Appendix 1 4 ME1R Series Heat Recovery CU 8 10ME1XPK ...
Страница 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Страница 591: ...Wiring Diagrams Outdoor Unit PACD011001C2 570 Appendix 1 5 MA1R Series Combination PA 16 18 20MA1XPK ...
Страница 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Страница 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Страница 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Страница 597: ...Wiring Diagrams Indoor Unit PACD011001C2 576 Appendix 2 4 Built In Type CS 20 25 32 40 50 63FMHPP ...
Страница 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Страница 599: ...Wiring Diagrams Indoor Unit PACD011001C2 578 Appendix 2 5 Ducted Type CS 40 50 63 80 100 125EMHPK ...
Страница 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Страница 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Страница 602: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 581 2 7 Wall Type CS 20 25 32 40 50 63KM1HPK ...
Страница 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...
Страница 643: ...SERIAL No EUUMSM01001 Printed in Japan ...