Outline of Control
PACD011001C2
432
Function UM Combination “MA1R Series” Using R-407C
3.1.8
Startup Control
Fixes the frequency at a low level for a certain period of time during compressor startup to prevent liquid
return.
[Startup control in cooling operation]
[Startup control in heating mode]
Startup control ends
when
∗
1 is met
Opens outdoor
unit EV when
∗
2
is met
41Hz
∗
3
52Hz
20 sec delay
30 sec
1 min
2000
200 (in retry: 1200,
second time: 2000)
SH control
Normal full operation
Provides fan control to maintain
high pressure in cooling operation.
Equalization prior to startup
Startup control
Thermostat ON
Inverter charging
INV
SVP
Outdoor EV
Indoor EV
(Unit with
thermostat ON)
Outdoor fan
Indoor fan
∗
1
Startup control ending conditions
∗
2
Outdoor unit EV full-open conditions
∗
3
Operates at 52 Hz after operating at
41 Hz for 1 minute.
(until PI control is activated in
∗
1)
OR
OR
&
DSHi>30
Th6 – Te>10
Elapsed time of 15 minutes
LP<0.098MPa
Tc>Ta+10
Elapsed time of 10 minutes
Tcg>55deg
When condition
∗
1 is met
Maximum 15 minutes (including 5 minutes of restart standby in stop mode)
When HP - LP < 0.196MPa, compressor turns on.
(V0808)
Complete startup
control according to
∗
1
Startup controlling control
SH according to
∗
2
Cancellation of 0 pulse
instruction to indoor
EV according to
∗
5
41Hz
52Hz
20 sec delay
30 sec
1 min
SC control
Max .15min (including 5min for restart standby )
When HP-LP<0.196MPa compressor ON
Equalization prior to startup
Startup control
Thermostat ON
Inverter charging
INV
SVP
Outdoor
unit EV
Indoor EV
(Unit with
thermostat ON)
Outdoor
fan
Indoor fan
OR
OR
DSHi>30
Th6 – Te>10
LP<0.098MPa
PI control according to
∗
3
Hot start
Elapsed time of 1 minute
OR
Elapsed time of 15 minutes
(local setting of 10 minutes)
(30 minutes in power ON)
HP>1.47MPa
When condition
∗
1 is met
0pls
∗
1
Startup control ending conditions
∗
2
SH control by outdoor unit EV
PI control activated at SHS=10
(initial opening degree: 200 pls
In the case of an LP retry, the next PI
control is provided at SHS=5.
When condition
∗
1 is met, the next
startup condition is reset to SHS=10.)
∗
3
When returning to normal outdoor EV
control, the PI control is provided at
that opening degree.
∗
5
Indoor unit EV 0 pls instruction
cancellation conditions
∗
6
Defrost judgment is not conducted
during this control.
(V0809)
Содержание Urban Multi MX1R Series
Страница 13: ...PACD011001C2 xii Table of Contents ...
Страница 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Страница 35: ...Function PACD011001C2 14 Function Urban Multi MX1 ME1 Series Using R 22 1 1 3 CU 8 10ME1XPA Heat Recovery ...
Страница 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Страница 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Страница 171: ...Troubleshooting by Remote Controller PACD011001C2 150 Troubleshooting Urban Multi MX1 ME1 Series Using R 22 ...
Страница 237: ...Troubleshooting OP Unified ON OFF Controller PACD011001C2 216 Troubleshooting Urban Multi MX1 ME1 Series Using R 22 ...
Страница 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Страница 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Страница 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Страница 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Страница 359: ...Troubleshooting by Remote Controller PACD011001C2 338 Troubleshooting Urban Multi MX1R ME1R Series Using R 407C ...
Страница 425: ...Troubleshooting OP Unified ON OFF Controller PACD011001C2 404 Troubleshooting Urban Multi MX1R ME1R Series Using R 407C ...
Страница 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Страница 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Страница 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Страница 513: ...Troubleshooting by Remote Controller PACD011001C2 492 Troubleshooting UM Combination MA1R Series Using R 407C ...
Страница 585: ...Wiring Diagrams Outdoor Unit PACD011001C2 564 Appendix 1 2 ME1 Series Heat Recovery CU 8 10ME1XPA ...
Страница 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Страница 589: ...Wiring Diagrams Outdoor Unit PACD011001C2 568 Appendix 1 4 ME1R Series Heat Recovery CU 8 10ME1XPK ...
Страница 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Страница 591: ...Wiring Diagrams Outdoor Unit PACD011001C2 570 Appendix 1 5 MA1R Series Combination PA 16 18 20MA1XPK ...
Страница 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Страница 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Страница 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Страница 597: ...Wiring Diagrams Indoor Unit PACD011001C2 576 Appendix 2 4 Built In Type CS 20 25 32 40 50 63FMHPP ...
Страница 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Страница 599: ...Wiring Diagrams Indoor Unit PACD011001C2 578 Appendix 2 5 Ducted Type CS 40 50 63 80 100 125EMHPK ...
Страница 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Страница 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Страница 602: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 581 2 7 Wall Type CS 20 25 32 40 50 63KM1HPK ...
Страница 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...
Страница 643: ...SERIAL No EUUMSM01001 Printed in Japan ...