3WAY SYSTEM
Control Functions
1
- 38
1
10. Upper Current Limitation Mode (Demand control)
EEPROM setting in main outdoor unit
EEPROM setting in main outdoor unit
CODE: 1A
Setting No.
XX
0
0
40
40
45
45
CODE: 1E
Setting No.
0
No display
1
Information is displayed when input of demand control is set (factory preset mode).
2
Information is displayed only when the capacity is restricted by demand control.
100
Interval of “5”
100 (factory preset mode)
-1
No control
140
140
Control
Contact 1
Upper current limitation setting
Contact 2
No control (Operates to maximum capacity)
Operates to XX% of the upper limit for the rated current.
Operates to YY% of the upper limit for the rated current.
Always in stop condition
There are 2 types of control; demand control and infinity limit in the upper current limitation mode.
Either of them is controlled by the lower current limitation.
Serial-parallel I/O must be connected in order to perform demand control.
The below input is received by serial-parallel I/O, and demand control is performed.
The demand values can be set as needed with serial-parallel I/O.
It is able to display the present condition on the remote controller.
* The rated current indicates the current value that is listed in the catalog or similar material.
* XX and YY are able to set in EEPROM of main outdoor unit.
: Input present
: Input not present
10-1. Demand Control
CODE: 1B
Setting No.
YY
0
0
40
40
45
45
70
Interval of “5”
70 (factory preset mode)
-1
No control
140
140
8 hp
10 hp
12 hp
14 hp
16 hp
8.6 A
11.3 A
15.1 A
19.2 A
22.0 A
8.95 A
11.6 A
14.7 A
17.0 A
20.4 A
Cooling mode
Heating mode
Mixed mode (Cooling/Heating)
8.95 A
11.6 A
15.1 A
19.2 A
22.0 A
The standard value of the limit current is listed in the table below.
hp = horsepower
SM830226-00̲3WAY ECO-i SYSTEM.in38 38