2
- 19
Remote Control Functions
3. Timer Remote Controller
1
2
3
4
5
6
7
8
Use AWG#20 to AWG#16 wires.
Remote controller wiring can be extended to a maximum
of 1640 ft.
(1) Strip the insulation to approximately 35/64" from the ends
of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp connection
at the wire joint.
(3) If a special crimping tool is not used, or if the connection
is soldered, insulate the wires using insulation tape.
3-5. Group Control Using 2 Remote Controllers
It does not matter which of the 2 remote controllers you
set as the main controller. When using multiple remote
controllers (up to 2 can be used), one serves as the
main remote controller and the other as the sub-remote
controller.
CODE No.
(New) (Old)
Remote controller wiring
Power wire from remote
controller unit
Provided wire joint (white)
Wire joint
(sub)
2P terminal
base for remote
control wiring
Remote controller
(main)
1
Indoor unit
No. 1
: Ground (earth)
Indoor unit
No. 2
Indoor unit
No. 8
Indoor unit
No. 3
Connection wiring
for group control
1
1
1 2
2
2
2
1
2
1
2
RCU. Main/Sub
Main
Sub
CODE
ITEM
DATA
ITEM
Clock display
12 hours
(AM/PM)
24 hours
RCU. CK
Normal
RCU. CK
Room temperature sensor Main unit
RCU
CODE
ITEM
DATA
ITEM
Vent. button
Yes
No
Temperature unit
o
F
o
C
3-6. Remote Controller Setting Mode
To set the remote controller main/sub setting or change the sensor, follow the steps below.
Press both
and
buttons on the remote controller for more than
4 seconds together.
Select CODE No. with
buttons.
Change DATA with
(TIMER) buttons.
Press
. Finally, press
.
* DATA is memorized in the RCU. (DATA setting will not be changed even
when the power is turned off.)
* Make sure to set [Normal] for RCU. CK.
3-7. Indoor Unit Setting Mode
To select the ventilation setting or change the temperature unit, follow the steps below.
Press
+
+
buttons on the remote controller for more than 4 sec-
onds together.
Select CODE No. with
buttons.
Change DATA with
(TIMER) buttons.
Press
. Finally, press
.
* DATA is memorized in the indoor unit. (DATA setting will not be changed
even when the power is turned off.)
3-8. To Display the Sensor Temperature:
Press both
and
buttons on the remote controller for more than 4 seconds together.
Change the sensor address (CODE No.) with
buttons.
Select the UNIT No. which you want to call with the
button.
Press the
button to fi nish service mode.
3-9. To Display the Trouble History:
Press both
and
buttons on the remote controller for more than 4 seconds together.
Change the alarm message:
buttons
Press the
button to fi nish service mode.
Fig. 2-2
Fig. 2-3
SM830202-00̲3WAY VRF.indb 19
SM830202-00̲3WAY VRF.indb 19
2012/01/30 14:52:44
2012/01/30 14:52:44
Содержание U-72MF1U9
Страница 90: ...3 28 MEMO 1 2 3 4 5 6 7 ...
Страница 112: ...4 22 1 2 3 4 5 6 7 MEMO ...
Страница 127: ... MEMO 1 2 3 4 5 6 7 6 11 ...
Страница 128: ...201201 ...