3
- 12
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
Setting mode 1
<Operating procedure>
Press and hold the
(CHECK) button and
(VENTILATION) button simultaneously for 4
seconds or longer.
Press the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown in the table below.
Press the timer time
and
buttons to
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “
” stops blinking and remains
lit.)
During this mode, “
” is displayed, blinking.
The outdoor unit address display section displays
“ALL,” the item code number (DN value in the
table), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig.
A
)
and the last 4 digits (Fig.
B
). When the first 4
digits are displayed, the bottom dot of the colon is
illuminated.)
To exit the setting mode, press the
(CHECK)
button.
1
2
3
5
5
3
1
2
A
and
B
are displayed alternately.
(Example shows display of 0000 0001.)
A
Display of first 4 digits
B
Display of last 4 digits
Description
Parameter
DN
Outdoor unit fan Quiet
mode
0 = Disabled
1 = Quiet mode
Energy saving mode
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. c Demand (Mode 1)
0 = None
1 = Indoor EEPROM code : Set 28 to 01
(When power failure is recovered, the system restores automatically.)
2 = Indoor EEPROM code : Set 28 to 00
(When power failure is recovered, the system does not restore automatically.)
(When EF changed, set to EE for setting at shipment : Set to 0)
Energy saving
operation plug
0 = Independent
1 = All indoor units linked
Demand 1 current
40 = 40%, 45 = 45%, … 95 = 95% 100 = 100%, -1 = (no limit)
40 = 40%, 45 = 45%, … 95 = 95% 100 = 100%, -1 = (no limit)
Demand 2 current
Indoor unit connecting
Nos.
0 = Setting at shipment
(Indoor unit connecting Nos. shows after installation's communication.)
Auto restart setting
SM830195-01̲Mini VRF SYS.indb 12
SM830195-01̲Mini VRF SYS.indb 12
2011/12/20 16:31:35
2011/12/20 16:31:35