Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
•
Displays outdoor unit alarms only.
•
Check the indoor unit alarm histories separately using the
indoor unit remote controllers or other control device.
<Operating procedure>
➀
Press and hold the
(CHECK) button and
button simultaneously for 4 seconds or longer to engage
outdoor unit alarm history mode.
During temperature monitoring,
illuminates.
The display and operations are the same as for the
alarm history monitor performed from the indoor unit
remote controller. However the “unit No.” display shows
the outdoor unit address.
➁
Press the temperature setting
and
buttons and select the item code for the alarm history.
The select outdoor unit address, the item code, and the
alarm history (alarm data) are displayed.
The outdoor unit address is displayed as R.C. XX-YY.
System XX = Outdoor unit system address
R.C. XX = Outdoor unit system address
YY = Outdoor unit sub-bus address
Item codes 01-08 are displayed. 01 indicates the most
recent alarm.
The alarm history displays the alarm code. (If no alarm
are present, then -- -- is displayed.)
➂
To clear the alarm history, press the
button. (The
outdoor unit alarm history will be cleared.)
➃
To exit, press the
(CHECK) button. The display
returns to the normal display.
1
3
4
2
5. Outdoor Unit Alarm History Monitor
SM830195-01̲Mini VRF SYS.indb 11
SM830195-01̲Mini VRF SYS.indb 11
2011/12/20 16:31:34
2011/12/20 16:31:34