Panasonic SF4D-*-01 Series Скачать руководство пользователя страница 6

<Using NPN output>

 

I/O circuit diagrams

Main circuit

Main circuit

Emitter

Receiver

6.8kΩ

6.8kΩ

0.1µF

0.1µF

6.8kΩ

6.8kΩ

6.8kΩ

0.1µF

6.8kΩ

470Ω

470Ω

470Ω

(Brown) +V

(Brown) +V

(Pink) Test / Reset input

(Orange) Synchroni

(Orange) Synchroni

(Red) Auxiliary output

(Pale purple) Interlock setting input

(Orange / Black) Synchronization -

(Orange / Black) Synchronization -

(Pale blue) Output polarity setting / Lockout release input

(Pale blue) Output polarity setting / Lockout release input

(Blue) 0V

(Blue) 0V

Users’ circuit

Users’ circuit

Internal circuit

Internal circuit

*S1

*S1

24V DC 

+20 -30

%

+

K2

Load

K1

(Black) Control output 1 (OSSD 1)

(Pale purple) External device monitor input

(White) Control output 2 (OSSD 2)

K1 K2

<Reference>

K1, K2: External device (forcible guide relay or magnetic contactor)

 

Basic wiring

(Orange) Synchroni

(Orange) Synchroni

(Red) Auxiliary output

(Pale purple) Interlock setting input

(Orange / Black) Synchronization -

(Orange / Black) Synchronization -

(Pale purple) External device monitor input

(Brown) +V

(Brown) +V

(Pink) Test / Reset input

(Pale blue) Output polarity setting / Lockout release input

(Pale blue) Output polarity setting / Lockout release input

(Blue) 0V

(Blue) 0V

24V DC 

+20 -30

%

+

K1
K2

(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)

Emitter

Receiver

Gray cable

Gray cable 

(with black line)

Interlock function

Invalid (auto reset)

External device monitor function

Invalid

Auxiliary output

Cannot be used

<Reference>

K1, K2: Safety relay unit, etc.

*S1

Switch S1

• Test / Reset input

Manual reset …0 to +2.5V (source current 5mA or less): Emission halt, Open: Emission

Auto reset …0 to +2.5V (source current 5mA or less): Emission, Open: Emission halt

• Interlock setting input, External device monitor input

0 to +2.5V (source current 5mA or less): Valid, Open: Invalid

Using line synchronization setting and 12-core cable

 

Refer to the manual on “

our web site: 

https://panasonic.net/id/pidsx/global

 

”.

9

INDICATOR OPERATION

Lower application indicator

Upper application indicator

Upper application indicator

Emitter: Light emission intensity control indicator

Receiver: Function setting indicator

Stable light 

reception indicator

Emitter: Test indicator

Receiver: Interlock indicator

Digital indicator

Emitter: Operation indicator

Receiver: OSSD indicator

Frequency indicator

Lower application indicator

<Conditions: Line synchronization, Test input function invalid, Interlock function invalid>

 

Emitter indicator operation

Light blocked state

Light received state (all beam channels)

Top end beam channel

Unstable light 

reception state

Stable light reception state

Light blocked Light received Light blocked Light received

Bottom end beam channel

Received light intensity

Light blocked Light blocked Light received Light received

Other beam channels

Level 1

Level 1

Level 2

Level 3

Light received 

/ Light blocked

Light received 

/ Light blocked

Light received 

/ Light blocked Light blocked

Control output

(OSSD 1 / 2)

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Upper application 

indicator

Turns OFF Lights red Turns OFF Lights red Lights blue Lights blue Lights blue Lights blue

Lower application 

indicator

Turns OFF Turns OFF Lights red

Lights red Lights blue Lights blue Lights blue Lights blue

Stable light 

reception indicator Turns OFF Turns OFF Turns OFF Turns OFF Lights orange Lights green Lights green Lights green
Digital indicator Turns OFF Turns OFF Turns OFF Turns OFF Green 1 lights Green 1 lights Green 2 lights Green 3 lights
Frequency indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Light emission intensity 

control indicator

When short mode is selected by DIP switch: Lights orange

Test indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Operation indicator Lights red

Lights red

Lights red

Lights red Lights green Lights green Lights green Lights green

 

Receiver indicator operation

Light blocked state

Light received state (all beam channels)

Top end beam channel

Unstable light 

reception state

Stable light reception state

Light blocked Light received Light blocked Light received

Bottom end beam channel

Received light intensity

Light blocked Light blocked Light received Light received

Other beam channels

Level 1

Level 1

Level 2

Level 3

Light received 

/ Light blocked

Light received 

/ Light blocked

Light received 

/ Light blocked Light blocked

Control output

(OSSD 1 / 2)

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Upper application 

indicator

Turns OFF Lights red Turns OFF Lights red Lights blue Lights blue Lights blue Lights blue

Lower application 

indicator

Turns OFF Turns OFF Lights red

Lights red Lights blue Lights blue Lights blue Lights blue

Stable light 

reception indicator Turns OFF Turns OFF Turns OFF Turns OFF Lights orange Lights green Lights green Lights green
Digital indicator Turns OFF Turns OFF Turns OFF Turns OFF Green 1 lights Green 1 lights Green 2 lights Green 3 lights
Frequency indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Function setting 

indicator

When the blanking function or parallel connection is used: Lights yellow (Applicable model: 

SF4D-□

)

When the communication module 

SF4D-TM1

 (option) is connected: Blinks orange

Interlock indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
OSSD indicator Lights red

Lights red

Lights red

Lights red Lights green Lights green Lights green Lights green

<Conditions: Optical synchronization (frequency 1), Test input function invalid, Interlock function invalid>

 

Emitter indicator operation

Light blocked state

Light received state (all beam channels)

Top end beam channel

Unstable light 

reception state

Stable light reception state

Light blocked Light received Light blocked Light received

Bottom end beam channel

Received light intensity

Light blocked Light blocked Light received Light received

Other beam channels

Level 1

Level 1

Level 2

Level 3

Light received 

/ Light blocked

Light received 

/ Light blocked

Light received 

/ Light blocked Light blocked

Control output

(OSSD 1 / 2)

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Upper application 

indicator

Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF

Lower application 

indicator

Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF

Stable light 

reception indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Digital indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Frequency indicator Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange
Light emission intensity 

control indicator

When short mode is selected by DIP switch: Lights orange

Test indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Operation indicator Lights green Lights green Lights green Lights green Lights green Lights green Lights green Lights green

 

Receiver indicator operation

Light blocked state

Light received state (all beam channels)

Top end beam channel

Unstable light 

reception state

Stable light reception state

Light blocked Light received Light blocked Light received

Bottom end beam channel

Received light intensity

Light blocked Light blocked Light received Light received

Other beam channels

Level 1

Level 1

Level 2

Level 3

Light received 

/ Light blocked

Light received 

/ Light blocked

Light received 

/ Light blocked Light blocked

Control output

(OSSD 1 / 2)

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Upper application 

indicator

Turns OFF Lights red Turns OFF Lights red Lights blue Lights blue Lights blue Lights blue

Lower application 

indicator

Turns OFF Turns OFF Lights red

Lights red Lights blue Lights blue Lights blue Lights blue

Stable light 

reception indicator Turns OFF Turns OFF Turns OFF Turns OFF Lights orange Lights green Lights green Lights green
Digital indicator Turns OFF Turns OFF Turns OFF Turns OFF Green 1 lights Green 1 lights Green 2 lights Green 3 lights
Frequency indicator Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange Lights orange
Function setting 

indicator

When the blanking function or parallel connection is used: Lights yellow (Applicable model: 

SF4D-□

)

When the communication module 

SF4D-TM1

 (option) is connected: Blinks orange

Interlock indicator Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
OSSD indicator Lights red

Lights red

Lights red

Lights red Lights green Lights green Lights green Lights green

Содержание SF4D-*-01 Series

Страница 1: ...nse interference extraneous light such as high fre quency fluorescent lamp inverter type rapid starter fluorescent lamp stro boscopic lights or direct sunlight 2 Areas with high humidity where condens...

Страница 2: ...cator lights orange When frequency 2 is set Two indicators light orange Emitter Name Function Line synchronization Optical synchronization Light emission intensity control indicator Orange Short mode...

Страница 3: ...er shearing machine in Japan always attach the protective tube SFPD A10 option to the cable The minimum bending radius of the cable with the protective tube SFPD A10 at tached is 55mm Take into consid...

Страница 4: ...regulator the frame ground F G terminal must be connected to ground 4 The power supply unit must have an output holding time of 20ms or more 5 If surges occur take countermeasures such as connecting a...

Страница 5: ...Reset input Manual reset Vs to Vs 2 5V sink current 5mA or less Emission halt Note Open Emission Auto reset Vs to Vs 2 5V sink current 5mA or less Emission Note Open Emission halt Interlock setting i...

Страница 6: ...ived Other beam channels Level 1 Level 1 Level 2 Level 3 Light received Light blocked Light received Light blocked Light received Light blocked Light blocked Control output OSSD 1 2 OFF OFF OFF OFF ON...

Страница 7: ...nisms Output from the device is correctly detected Wiring from the device is correct The response time of the overall system is equal to or less than the calculated value The current number of operati...

Отзывы: