1. ACCESSORIES SUPPLIED WITH OUTDOOR UNIT
The following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit.
Part name
Diagram
Quantity
Part name
Diagram
Quantity
Joint tubing A (ø19.05 ø25.4)
1
Protective bushing
(for protecting electrical wires)
2
Joint tubing B (ø19.05)
1
Banding strap
(for tying electrical wires together)
4
Operating Instructions
A4
1
Installation Instructions
A1
1
A2
1
Please install according to “WARNING” or “CAUTION” on page1-12-1-1-1 to 1-12-1-1-6.
2. SELECT THE OUTDOOR UNIT INSTALLATION LOCATION
WARNING
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back.
Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
1. Install the unit once you have checked that the installation location matches the following conditions.
A location with sufficient
ventilation.
Possibly a location that is sheltered from rain or direct sunlight and is well-ventilated so that hot and cool air does not build up.
A location where the area around the discharge is not exposed to animals or plants which could adversely affect the release of hot or cool air from the unit.
A location where the discharge and operation noise will not be a nuisance to the neighbours.
A location that can support the product’s weight or vibrations and secured for horizontal installation wherever possible.
A location that does not obstruct the air discharge or intake.
A location where there is no danger of flamma
ble or corrosive gas leaks.
A location that provides space for installation and service.
A location that allows the tube and cab
le length fixture
for internal and external connections.
It may need two or more people to carry out the installation work.
2. Refer to the diagram below for the installation location which is exposed to strong wind.
If a strong wind of more than 5 m/sec blows to the area directly in front of the discharge, the outdoor unit’
s air fl
o
w is reduced and the outfl
ow may re-enter
(short circuit) causing the following outcome:
“Reduced capacity”, “Increased frost formation during heating” or “Operation stopped due to increased pressure”.
Should an exceptionally strong wind blow to the area directly in front of the discharge of the outdoor unit; there is the risk of damage due to the fan’s
high-speed reverse rotation.
If the direction of the prevailing wind is known when operating the unit, place the unit at an appropriate angle to the wind’s direction so that the discharge
faces towards a building or a wall.
Air Intake
Wall / Standing outer wall
Intake side
Selecting the location for installation and service.
Strong wind
Air discharge
Strong wind
3. If installing at locations prone to snowfall, install the unit as high as possible with suitab
le roofing which shelters the unit from sn
ow.
4. Avoid installing the unit in locations where there are petroleum products (such as machine oil), saline content (such as coastal areas), sulphurous gas and where
high frequency noise is generated.
5. Place the indoor and outdoor unit, power cords and indoor/outdoor unit connection cables at a minimum distance of 1 meter or more away from televisions
and radios. This is to avoid interference to picture and/or sound.
(However, depending on the electromagnetic waves, noise interference may still occur even with the 1 meter separation.)
6. For restaurants and kitchens, avoid installing at locations which draws oil and steam.
Plastic parts can deteriorate from droplets of oil and steam or it can cause falling parts or water leakage.
7. Avoid installing at the location where cutting oil mist or iron powder is present.
8. If there is an immense v
oltage fluctuation due to the location
’s problem, ensure to split the power supply.
9. When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing between buildings, including the rooftop of a
building and a place where there is no building in surroundings
, fix the product with an
overturn prevention wire, etc.
10. Ensure to assign several people or use a mechanical lift, etc. to transport the unit.
SM830276-00_欧州向け R32シングル TD&SM.indb 8
2019/02/27 11:54:26
Содержание S-50PU2E5B
Страница 12: ... MEMO Xi SM830276 00_欧州向け R32シングル TD SM indb 12 19 02 26 15 26 22 ...
Страница 160: ...1 14 8 MEMO SM830276 00_欧州向け R32シングル TD SM indb 8 2019 02 27 11 55 39 ...
Страница 176: ... MEMO 2 16 SM830276 00_欧州向け R32シングル TD SM indb 16 19 02 28 13 23 00 ...
Страница 182: ... MEMO 3 6 SM830276 00_欧州向け R32シングル TD SM indb 6 19 02 26 10 39 17 ...
Страница 238: ... MEMO 5 38 SM830276 00_欧州向け R32シングル TD SM indb 38 19 02 28 13 29 52 ...
Страница 316: ...201903 SM830276 00_欧州向け R32シングル TD SM indb 1 19 02 15 8 52 12 ...