1-128
1
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PE1
6. 4-Way Cassette 60×60 Type S-36PY2E5A×2 / U-71PE1E5A
INDOOR
MODEL
S-36PY2E5A ×2
PANEL
MODEL
(CZ-KPY3A / CZ-KPY3B) ×2
OUTDOOR
MODEL
U-71PE1E5A
Branch pipe
MODEL
CZ-P155BK1
PERFORMANCE TEST CONDITION
ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
7.1
7.1
7.1
2.5
8.0
BTU/h
24200
24200
24200
8500
27300
CURRENT
A
0.30 x 2
9.60
9.30
9.00
-
-
INPUT POWER
W
40 x 2
1.985k
1.985k
1.985k
-
-
TOTAL W
-
2.065k
2.065k
2.065k
450
2.650k
ANNUAL CONSUMPTION TOTAL kWh
*
4
-
-
-
-
1032.5
-
-
-
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.44
3.44/A
3.44
5.56
3.02
Erp
*
6
Pdsign
kW
-
-
-
-
7.1
-
SEER
(W/W)
-
-
-
-
6.2
-
Annual consumption
kWh
-
-
-
-
401
-
Class
-
-
-
-
A++
-
POWER FACTOR
%
-
-
-
94
93
92
NOISE INDOOR
(H/M/L)
dB-A
36/32/26(31)*7
Power Level dB
51/47/41(46)*7
NOISE OUTDOOR
(H/L)
dB-A
48/-
Power Level dB
65/-
H
E
A
T
I
N
G
CAPACITY
kW
8.0
8.0
8.0
2.0
9.0
BTU/h
27300
27300
27300
6800
30700
CURRENT
A
0.30 x 2
10.0
9.70
9.40
-
-
INPUT POWER
W
35 x 2
2.080k
2.080k
2.080k
-
-
TOTAL W
-
2.150k
2.150k
2.150k
400
2.900k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.72
3.72/A
3.72
5.00
3.10
Erp
*
6
Pdsign
kW
-
-
-
-
7.1
-
Tbivalen
°C
-
-
-
-
-7
-
SCOP
(W/W)
-
-
-
-
3.8
-
Annual consumption
kWh
-
-
-
-
2616
-
Class
-
-
-
-
A
-
POWER FACTOR
%
-
-
-
95
93
92
NOISE INDOOR
(H/M/L)
dB-A
36/32/26(31)*7
-
Power Level dB
51/47/41(46)*7
-
NOISE OUTDOOR
(H/L)
dB-A
-
50/-
Power Level dB
-
67/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
0.35/50 x 2
18.0/3.80k
18.0/3.93k
18.0/4.06k
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
10.0/2.0k
9.70/2.0k
9.40/2.0k
NETWORK IMPEDANCE (ΩMAX.)
-
-
FM OUTPUT (W)
40 x 2
90
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
4.2
(2.1×2)
(8.8)
-
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min) 9.7×2/8.0×2/6.0×2*7 (343)×2/(283)×2/(212)×2
HEAT
m
3
/min (ft
3
/min) 9.9×2/8.2×2/6.0×2*7 (350)×2/(290)×2/(212)×2
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
60
(2119)
HEAT
m
3
/min (ft
3
/min)
60
(2119)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A
2.35k
(82.9)
P
R
O
D
I
M
HEIGHT : H mm(inch)
260<265 + 23> (10-1/4)
996 (39-7/32)
WIDTH : W mm(inch)
575<583> (22-21/32)
940 (37-1/32)
DEPTH : D mm(inch)
575<583> (22-21/32)
340 (13-13/32)
Panel : H×W×D mm
3A:31 × 700 × 700, 3B:31 × 625 × 625
-
P
A
C
D
I
M
HEIGHT : H mm
345 (13-19/32)
1136
WIDTH : W mm
691 (27-7/32)
1055
DEPTH : D mm
691 (27-7/32)
485
MASS
(NET) k
g
(lb)
18 (40)
69 (152)
(GROSS) k
g
(lb)
23 (51)
77 (170)
Panel : (NET) k
g
(lb)
2.4 (5.3)
-
LAYERS LIMIT (actually)
11 (12)
2 (3)
Operation
Condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0 (16.4)
fl ared type, 5.0 (16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50 (16.4 ~ 164.0)
I/D&O/D HEIGHT DIFFERENCE m (ft)
15(OD located lower)/30(OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
*1: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2: If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7
°C
dry bulb and -8
°C
wet-bulb temperatures with rated voltage 230V
shall be used.
*3: Network Impedance shall be applicable for EUROPE and CHINA models.
*4: The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5: EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche
data indicates in an attached sheet.
*7: Noise and air flow rate of L are indicated by the values at FAN mode. ( ):Normal operation Cooling/Heating noise value. Normal operation Cooling/Heating air flow rate are
7.6 (m
3
/min).
SM830231-02̲Single̲欧州.indb 128
SM830231-02̲Single̲欧州.indb 128
2014/09/19 13:21:08
2014/09/19 13:21:08
Содержание S-36PU1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...