![Panasonic : S-26PU1U6 Скачать руководство пользователя страница 163](http://html.mh-extra.com/html/panasonic/s-26pu1u6/s-26pu1u6_technical-data-and-service-manual_18365163.webp)
1-155
1-154
1. Specifications
6-40. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the
wiring diagram.
WARNING
(2) This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device
(RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the wiring regulations. The
Earth Leakage Circuit Breaker (ELCB) must be an approved 15 A, having a contact separation in all poles.
(3) To prevent possible hazards from insulation failure, the unit must be grounded.
(4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or
misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before
beginning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on single side.
(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer, because special-
purpose tools are required.
6-41. Important Note for Wiring 4-Way Cassette 36” × 36”
(1) The power supply inlet is located at the lower area of the
refrigerant tubing side of the unit. The electrical component box
is located at the air intake of the bottom of the unit.
(2) Before installing the ceiling panel, be sure to carry out the
wiring connection.
(3) Remove the lid located on the bottom of the indoor unit
attaching the electrical component box by unscrewing the
Phillips head tapping screws (×2).
(4) Lead the wires from the power supply inlet to the unit. Be sure
to lead the wires through the power supply inlet. Make sure that
no wire is caught between the indoor unit and ceiling panel.
Otherwise, the unit may cause a fire.
(5) Connect the wires into the terminals through the power supply
inlet for the electrical component box.
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its original
position with paying attention not to have the wires caught in
the lid.
Power supply inlet
Tapping screw position
00_271724_Eng.indb 12
2015-8-26 14:43:55
6-42. How to Install the Ceiling Panel
(1) Removing the air-intake grille
1) Remove the 2 screws on the latch of the air-intake grille.
(Fig. 1-131) (Reattach the air-intake grille after installation
of the ceiling panel.)
2) Slide the air-intake grille catches in the direction shown by
the arrows
1
to open the grille. (Fig. 1-131)
1
1
Fig. 1-131
3) With the air-intake grille opened, remove the grille hinge
from the ceiling panel by sliding it in the direction shown
by the arrow
2
. (Fig. 1-132) (Reattach the air-intake grille
after installation of the ceiling panel.)
2
Fig. 1-132
(2) Removing the corner cover
Slide the corner cover in the direction of the arrow
1
and
remove it.
2
1
Fig. 1-133
Corner cover
Corner cover
Push to
disengage
Ceiling panel
Slide
Strap
(3) Installing the ceiling panel
The power must be turned ON in order to change the flap angle. (Do
not attempt to move the flap by hand. Doing so may damage the flap.)
1) Hang the temporary latches on the inside of the ceiling panel to
the receptacle on the unit to temporarily attach the ceiling panel
in place. (Fig. 1-134)
The ceiling panel must be installed in the correct direction
relative to the unit. Align the REF. PIPE and DRAIN marks on the
ceiling panel corner with the correct positions on the unit.
When removing the ceiling panel, push the temporary latches
outward while holding the ceiling panel.
(Fig. 1-134)
Fig. 1-134
2) Align the panel installation holes and the unit screw holes.
3) Tighten the supplied washer head screws at the 4 panel
installation locations so that the panel is attached tightly to the
unit. (Fig. 1-135)
Fig. 1-135
4) Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps between
the unit and the ceiling panel, or between the ceiling panel
and the ceiling surface. (Fig. 1-136)
Fig. 1-136
If there is a gap between the panel and the ceiling, leave the ceiling
panel attached and make fine adjustments to the installation height
of the unit to eliminate the gap with the ceiling. (Fig. 1-137)
Receptacle on the
main unit
Push to disengage
Temporary latch
Temporary latch
Do not allow gaps.
Ceiling panel
Main unit
Ceiling surface
Drain tube corner
Refrigerant tube
corner
DRAIN mark
REF. mark
Washer head screws
Ceiling panel
Air-intake grille
Air-intake
grille hinge
Ceiling panel
Screw
Latch
Make fine adjustments by a wrench or
other tool to the installation height of the
unit to eliminate the gap with the ceiling
through the hole of the corner cover.
Fig. 1-137
00_271724_Eng.indb 20
2015-8-26 14:44:02
1
SM830203-04.indb 155
15/10/16 10:45:07
Содержание : S-26PU1U6
Страница 8: ...vii MEMO ...
Страница 76: ...1 68 1 Specifications 1 4 Dimensional Data Outdoor Unit U 26PE1U6 U 26PS1U6 U 36PE1U6 U 36PS1U6 1 ...
Страница 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1 ...
Страница 218: ...2 12 MEMO ...
Страница 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3 ...
Страница 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3 ...
Страница 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3 ...
Страница 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3 ...
Страница 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3 ...
Страница 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3 ...
Страница 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3 ...
Страница 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3 ...
Страница 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3 ...
Страница 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3 ...
Страница 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3 ...
Страница 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3 ...
Страница 233: ...3 15 3 Electrical data U 26PE1U6 3 ...
Страница 234: ...3 16 3 Electrical data U 26PS1U6 3 ...
Страница 235: ...3 17 3 Electrical data U 26PS1U6 3 ...
Страница 236: ...3 18 3 Electrical data U 36PE1U6 3 ...
Страница 237: ...3 19 3 Electrical data U 36PE1U6 3 ...
Страница 238: ...3 20 3 Electrical data U 36PS1U6 3 ...
Страница 239: ...3 21 3 Electrical data U 36PS1U6 3 ...
Страница 240: ...3 22 3 Electrical data U 42PE1U6 3 ...
Страница 241: ...3 23 3 Electrical data U 42PE1U6 3 ...
Страница 242: ...3 24 3 Electrical data U 42PS1U6 3 ...
Страница 243: ...3 25 3 Electrical data U 42PS1U6 3 ...
Страница 244: ... MEMO 3 26 ...
Страница 284: ...5 24 MEMO ...
Страница 297: ...201510 ...