1. ATTACHMENT
Attached documents
• Procedures and Technical Points for System Installation(Chillers)
• Procedures and Technical Points for Electrical Wiring Work(Chillers)
• Instruction Manual
Concerning anchor bolts
• For anchor bolts, use M10.
• Anchor bolts shall be procured locally.
2. SELECTING THE INSTALLATION LOCATION
CAUTION
1. Secure the space stipulated for inspection and maintenance work (Fig. 2). Inadequate space for
such work
can create the threat of injuries due to falls from the installation site.
2. When installing the water heat exchanger unit on a roof or other elevated location, place permanent
ladders, railings or other aids in passageways to prevent worker falls, as well as fences, railing and
other aids around the unit itself.
3. Install the unit in a location facilitating easy water draining. Defective work in this category can result
in water leakage, water damage to household effects and other problems.
• Keep indoor drain pipe sections as short as possible.
• Insulate all indoor drain pipe sections.
• Adopt measures to ensure that drain water causes no problems for neighboring homes or other parties.
4. Always use a level to con
fi
rm the horizontal level.
If it is not
fl
at, water leakage may occur.
1. Avoid installations in locations where machines emitting high frequencies are present.
2. When hoisting up the water heat exchanger unit for installation site delivery:
• Attach ropes to the unit base hoisting
fi
xtures at 4 locations, and raise up the unit.
• When attaching ropes, use wooden splints or other aids to prevent scratching or deformation to
the facing or other damage.
• When hoisting by crane, keep the crane hook at least 1 meter from the unit.
CAUTION
• When carrying in the unit, do not allow it to tip over. Damage to the machinery can cause
subsequent breakdowns.
4
Fig.1 Anchor bolts
312mm
1014mm
Anchorbolts:M10
Over 50mm
Over 600 mm
Refrigerant
tubing side
Over 50mm
Over 50mm
Over 2m
Wooden splints
Over 1m
Ropes
Fig.2 Fig.3