11

10

Wiring

Maintenance/inspections/ How to reset a trip

Connector for control signals (I/O)

Connector on amplifier side: Parts No. S10B-PASK-2 (J.S.TMfg.,Co.,Ltd.) or equivalent.

Mating connector:(Example of optional I/O connector kit )

  Housing PAP-10 V-S, terminal SPHD-002 T-P0.5 (for AWG24-28) (J.S.TMfg.,Co.,Ltd.)

Terminal 

number 

Terminal 

Symbol

Terminal name

Terminal explanation 

1

I

1

*1

Signal input 1

Operation instruction input 

*1

Motor runs when "

I

1" and "GND" are shorted, and stops when 

they are opened.

2

I

2

*1

Signal input 2

Rotation  changeover input 

*1

CW operation when "

I

2" and "GND" are shorted, and CCW 

operation when they are opened. 

*2

3

I

3

*1

Signal input 3

Free-run stop input 

*1

Free-run stop when  "

I

3" and "GND" are shorted,

4

I

4

*1

Signal input 4

Trip reset input 

*1

cancels a trip state when  "

I

4" and "GND" are shorted,

5

I

5

*1

Signal input 5

Free-run stop input 

*1

Free-run stop when  "

I

5" and "GND" are shorted,

6

GND

*3

signal ground

common ground of  analog speed input and input/output signal 

*3

7

FIN

For speed setting 

Input

Speed can be set by applying voltage DC0 to 5 V.

Input impedance 100 kΩ. 

8

+5 V

The power supply 

for external  

speed setting

Power output dedicated when connecting an external variable 

resistor (5 kΩ, B characteristics) to FIN input (Cannot be used for 

any other purpose.) 

9

01

※1

Signal output 1 

Trip signal output. 

*1

  "L" in trip (Contact ON)

Open collector Vce max: DC30 V, Ic max: 50 mA 

10

02

※1

Signal output 2

Velocity pulse output. 

*1

  (24 pulses / 1 rotation)

Open collector Vce max;   DC 30 V, Ic max;   50 mA 

*1  Function of input/output can be changed by the Digital key pad or panaterm for BL. Default is shown.

  Please refer to an operation manual (Overall) for details. 

*2 Rotation direction is that on motor shaft. (CW: Rotation clockwise when see from the motor shaft, CCW: 

Rotation counterclockwise when see from the motor shaft)

*3 When resistor and control GND are disconnected in use of external variable resistor, 5 V is input to FIN 

irrespective of setting of variable resistor, and upper speed limit is directed; therefore use caution enough 

for connecting GND.

•The terminal number of the connector for control signals,pin No.1 is the grounding terminal side.

• When a control signal line is extended, please give as below 5 m. 

Connector for comunications (SER)

Modular jack: 85503-0001 (Japan Molex Inc.) or equivalent (RJ45)

Terminal 

number 

Terminal 

Symbol

Terminal explanation 

• Connection of digital key pad of 

an option is possible. digital key 

pad connecting cable of an option 

(DV0P383**) is required.

• The terminal number of 

a modular jack is the 

following figure

8

1

• Refer to operation manual  

(Overall) for the correspondence 

procedure of RS485. 

1

Do not connect anything.

2

5 V

DC5 V power supply for digital key pad

3

SOT

Interface for digital key pad or 

PANATERM for BL

4

SIN

5

RS485+ for connect RS485+

6

RS485− for connest RS485–

7

GND

power supply GNG for Digital key pad 

8

SCK

Interface for digital key pad

Maintenance/ inspections

Routine maintenance and inspection are essential for proper and satisfactory operation of 

the motor.

Maintenance/ Inspection item

Maintenance/

Check item

Inspection

procedure

Condition

Input voltage Voltmeter  Must be within ±10 % of rating.

Input current Ammeter  Must be within rated input current described on nameplate.

Insulation

resistance

Insulation 

resistance 

tester 

Measure the insulation resistance  with 500 V Megger. It must be 

above 1 MΩ.

Measuring position: Between power input line (L1, L2,L3) and 

grounding wire 

Noise 

Hearing

Noise level must not be different from the usual level. In addition, 

abnormal noise such as rumbling noise must not be heard. 

Vibration

By hand

Free from abnormal vibration. 

Installation 

bolt 

Torque 

wrench 

Check for loosening of bolt, and tighten additionally as necessary. 

Use 

environment

By sight

Check the ambient temperature and humidity, and make sure that 

dirt, dust, or foreign substance is not found. 

check the waste thread etc  don’t attached to the windhole of brushless 

amplifier. 

Caution

• Power-on/off operations should be done by the check operator themselves for ensuring 

safety in checking.

• Do not touch the motor while it is running or immediately after it stops because it gets hot 

and stays hot for a while after power has been turned off.

• The DC500 V megger testing should be performed only on the main circuit. Be sure to 

disconnect the power supply. Otherwise, failure will occur. The resistance should be 1 

MΩ between the ground with L1, L2 and L3 short-circuited.

When disassembly, troubleshooting, etc., is needed,

be sure to contact our service department or the sales agent of purchase.

How to clear trip

If the motor trips (alarm LED is lit), remove the cause and use one of the following clearing 

procedures.

•  Turn off power, and when the power LED goes off, turn on power again.

•  For clearing procedure using the panel B or an input terminal, refer to the Instruction 

Manual (Overall).

<CAUTION> 

Before clearing the trip, be sure to locate and remove the cause.

Содержание MINAS-BL KV Series

Страница 1: ... after reading and read as necessary Be sure to give this Instruction manual to an end user Label of safety precaution is affixed to the product If you are the first user of this product please be sure to read the instruction Manual Overall from our Web Site Web address of Panasonic Corporation http industrial panasonic com ww i_e 25000 motor_fa_e motor_fa_e html This product image is 200 W type o...

Страница 2: ...urrent protection earth leakage breaker over temperature protecter and emergency stop device must be installed The failure could result in electric shocks injuries or fire Transportation wiring and checking must be performed with power source turned off and after making sure that there is no risk of electric shock The failure could result in electric shocks or injuries Do not subject the product t...

Страница 3: ...ght this product Checking the model of Amplifier and Motor This amplifier is designed for use in combination with a motor to be specified by us Check a name of series rated output voltage specifications you wish to use You must not use any other combinations than those listed below Standard Voltage Out put Amplifier Type Applicable Motor Single phase AC100 to 120 V 50 W MBEK5A1BCV MBMS5AZBL 100 W ...

Страница 4: ...otor in corrosive atmosphere such as hydrogen sulfide sulfurous acid chlorine ammonia sulfur gas chloride gas sulfide acid alkali and salt in the atmosphere of combustible gas or in the vicinity of flammables 3 Place not exposed to grinding liquid oil mist iron powder and cutting particle 4 Well ventilated place with little moisture oil or inundation and place far from heat source such as a furnac...

Страница 5: ...supply outside of equipment from MCCB use an electric wire of 1 6 mm diameter 2 0 mm2 or more both for main circuit and grounding Apply grounding class D 100 Ω or below for grounding Do not tighten the ground wires together but connect them individually Fastening torque of earth screws to be 0 49 to 0 98 N m For details of parameters refer to the Instruction Manual Overall For the wiring of commun...

Страница 6: ...ation Connection of digital key pad of an option is possible digital key pad connecting cable of an option DV0P383 is required The terminal number of a modular jack is the following figure 8 1 Refer to operation manual Overall for the correspondence procedure of RS485 1 Do not connect anything 2 5 V DC5 V power supply for digital key pad 3 SOT Interface for digital key pad or PANATERM for BL 4 SIN...

Страница 7: ...fier Conformance to EC directive and UL standard Conformance to EC directive and UL standard Configuration of peripheral equipment Power supply 100 V system Single phase 100 V to 120 V 10 50 60 Hz 200 V system Single phase 3 phase 200 V to 240 V 10 50 60 Hz Use the equipment under the environment of overvoltage category II specified by IEC60664 1 In order to obtain overvoltage category III insert ...

Страница 8: ...void inputting a supply voltage which significantly exceeds the rated range to the power supply of this product Failure to heed this caution may result in damage to the internal parts causing smoking and or a fire and other trouble Item Specifications Model name Brushless amplifier MBEK 5A1BCV MBEK 5A5BCV MBEK 011BCV MBEK 015BCV MBEK 021BCV MBEK 025BCV MBEK 045BCV MBEK 083BCV Brushless motor MBMS5...

Страница 9: ... can be downloaded from the following web site http industrial panasonic com ww i_e 25000 motor_fa_e motor_fa_e html Pursuant to at the directive 2004 108 EC article 9 2 Panasonic Testing Centre Panasonic Marketing Europe GmbH Winsbergring 15 22525 Hamburg F R Germany 7 1 1 Morofuku Daito Osaka 574 0044 Japan Phone 81 72 871 1212 For your records The model number and serial number of this product ...

Отзывы: