6.6 Emergency back-up mode
The battery system is equipped with an emergency back-up power outlet. This outlet is limited to a maximum load of
1000 Watts and can be used to supply power to certain devices in case of a power cut.
CAUTION! Do not attempt to connect devices that, in total, require more power than 1000 W. If you exceed
1000 W the integrated battery protection device will trip and disconnect the internal battery packs. As a
consequence the system will not work. A qualified electrician will need to service the battery so it can be
turned on again.
As a precaution, only connect devices to the back-up power outlet that have significantly lower power consumption than
1000 W.
Suitable Devices
Unsuitable Devices
Cell phone chargers, laptop chargers
Vacuum cleaner
Router, modem
Microwave oven
LED TV
Any water pumps
LED lighting or halogen lighting
Kettle
Small HiFi system or radio
Hairdryer
6.6.1 How to activate and deactivate the emergency back-up power outlet
For safety reasons, the back-up power outlet will not be activated automatically when there is a power cut. It needs to be
switched on manually. If a power cut occurs, the GRID indicator light will be orange and the display will show PF (for
Power Failure) followed by 0.0. You might also see some error codes such as E020 for low grid voltage.