Settings
22
KW2M-A/X User's Manual
◆
Parameters for pulse input
○
: Available
-
: Not available
Item
Range
Initial value
Setting
Keys Web
Pulse input
30, 2000
30
-
○
Pre-scale
0.001 to 100.000
1.000
Unit for pulse
output
(OUT1,OUT2)
kWh
0.001, 0.01, 0.1, 1, 10, 100
(kWh/1pulse)
0.001
Alarm
Stand-by power, Active power,
Reactive power, Apparent power,
Over current, Under current,
Power interruption, Power factor,
Over voltage, Under voltage,
Over frequency, Under frequency,
Current THD, Voltage THD,
Current harmonics,
Voltage harmonics,
Current unbalancing,
Voltage unbalancing,
Power demand, Current demand
General-purpose Digitial output
Target phase for pulse output
(OUT1,OUT2)
Total, Phase1, Phase2, Phase3
total
Target phase
for alarm
output
(OUT1,OUT2)
Electric power
Total, All, Phase1, Phase2, Phase3
total
Current
All, Phase1, Phase2, Phase3,
Phase N
All
Power
interruption
Over voltage
Under voltage
All, Phase1, Phase2, Phase3,
Line 1-2, Line 2-3, Line 3-1
All
Integral direction (OUT1,OUT2)
P, -P
P
Output pulse width
1 to 100 [ms]
1
Stand-by alarm (threshold)
(OUT1,OUT2)
0.1 to 100.0 [%]
100.0
Stand-by alarm (start time)
(OUT1,OUT2)
0 to 9999 [sec.]
0
Stand-by alarm (phase)
(OUT1,OUT2)
Phase1, Phase2, Phase3, All
All
Power alarm
(active/reactive/apparent)
threshold (ON/OFF)
(OUT1,OUT2)
0.00 to 999999999.999
[kW/kvar/kVA]
999999999.999
PF alarm threshold (ON/OFF)
(OUT1,OUT2)
0.000 to 1.000
0.000
Over frequency alarm threshold
(ON/OFF)
(OUT1,OUT2)
0.00 to 100.00 [Hz]
100.00
Under frequency alarm threshold
(ON/OFF)
(OUT1,OUT2)
0.00