6.8 Setup mode
To enter the Setup mode, press
key while pressing
key for approximately 3 seconds in the PV/SV
display mode.
To set or select each setting item, use
or
key, then register the value with
key.
Setting item numbers such as [25], [26], etc. are the same as those on the “6.4 Operation flowchart” (p.12).
Character
Name, Function, Setting range
Default value
Input type selection
K
(-200
to
1370 )
• The input type can be selected from a choice of; thermocouple (10 types), RTD (2 types),
DC current (2 types) and DC voltage (4 types), and the unit
/
can be selected as well.
• When changing the input from DC voltage to other inputs, remove the sensor connected to
this controller first, then change input type.
•
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC differs from
that of 0 to 1V DC.
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
K
-200 to
1370
K
-320 to
2500
K
-200.0 to 400.0
K
-320.0 to
750.0
J
-200 to
1000
J
-320 to
1800
R
0 to
1760
R
0 to
3200
S
0 to
1760
S
0 to
3200
B
0 to
1820
B
0 to
3300
E
-200 to
800
E
-320 to
1500
T
-200.0 to 400.0
T
-320.0 to
750.0
N
-200 to
1300
N
-320 to
2300
PL-
0 to
1390
PL-
0 to
2500
C(W/Re5-26)
0 to
2315
C(W/Re5-26)
0 to
4200
Pt100
-200.0 to 850.0
Pt100
-320.0 to 1500.0
JPt100
-200.0 to 500.0
JPt100
-320.0 to
900.0
Pt100
-200 to
850
Pt100
-320 to
1500
JPt100
-200 to
500
JPt100
-320 to
900
4 to 20mA DC
-2000 to 10000
0 to 20mA DC
-2000 to 10000
0 to 1V DC
-2000 to 10000
0 to 5V DC
-2000 to 10000
1 to 5V DC
-2000 to 10000
[25]
0 to 10V DC
-2000 to 10000
Scaling high limit setting
1370
[26]
• Sets scaling high limit value.
•
Setting range: Scaling low limit value to input range high limit value
DC voltage, current input: -2000 to 10000 (The placement of the decimal
point follows the selection.)
Scaling low limit setting
-200
[27]
• Sets scaling low limit value.
•
Setting range: Input range low limit value to Scaling high limit value
DC voltage, current input: -2000 to 10000 (The placement of the decimal
point follows the selection.)
Decimal point place selection
No decimal point
[28]
• Selects decimal point place.
Available only for DC input.
•
: No decimal point
: 1 digit after the decimal point
: 2 digits after the decimal point
: 3 digits after the decimal point