9
• Response message from the slave in exception (error) status (When a value out of the setting range is set)
The function code MSB is set to 1 for the response message in exception (error) status (86H).
If an exception code (03H: Value out of the setting range) is returned, the error can be determined by
reading this code.
(Fig. 6.4-10)
7. Communication command table
Modbus
function code
Data item
Data
03H/06H
1110H: Step 1 SV
Set value, Decimal point ignored
03H/06H
1111H: Step 1 time
Set value, Decimal point ignored
03H/06H
1120H: Step 2 SV
Set value, Decimal point ignored
03H/06H
1121H: Step 2 time
Set value, Decimal point ignored
03H/06H
1130H: Step 3 SV
Set value, Decimal point ignored
03H/06H
1131H: Step 3 time
Set value, Decimal point ignored
03H/06H
1140H: Step 4 SV
Set value, Decimal point ignored
03H/06H
1141H: Step 4 time
Set value, Decimal point ignored
03H/06H
1150H: Step 5 SV
Set value, Decimal point ignored
03H/06H
1151H: Step 5 time
Set value, Decimal point ignored
03H/06H
1160H: Step 6 SV
Set value, Decimal point ignored
03H/06H
1161H: Step 6 time
Set value, Decimal point ignored
03H/06H
1170H: Step 7 SV
Set value, Decimal point ignored
03H/06H
1171H: Step 7 time
Set value, Decimal point ignored
03H/06H
1180H: Step 8 SV
Set value, Decimal point ignored
03H/06H
1181H: Step 8 time
Set value, Decimal point ignored
03H/06H
1190H: Step 9 SV
Set value, Decimal point ignored
03H/06H
1191H: Step 9 time
Set value, Decimal point ignored
03H/06H
0001H: SV1
Set value, Decimal point ignored
0002H: Not used
03H/06H
0003H: AT
0000H: Cancel
0001H: Perform
03H/06H
0004H: OUT1 (Heating) proportional band
Set value, Decimal point ignored
03H/06H
0005H: OUT2 (Cooling) proportional band
Set value, Decimal point ignored
03H/06H
0006H: OUT1 (Heating) integral time
Set value
03H/06H
0007H: OUT1 (Heating) derivative time
Set value
03H/06H
0008H: OUT1 (Heating) proportional cycle
Set value
03H/06H
0009H: OUT2 (Cooling) proportional cycle
Set value
03H/06H
000AH: Manual reset
Set value, Decimal point ignored
03H/06H
000BH: A1 value
Set value, Decimal point ignored
03H/06H
000CH: A2 value
Set value, Decimal point ignored
000DH: Not used
0011H: Not used
03H/06H
0012H: Set value lock
(*1)
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
0013H: Not used
0014H: Not used
03H/06H
0015H: Sensor correction
Set value, Decimal point ignored
03H/06H
0016H:
Overlap band/Dead band
Set value
0017H: Not used
03H/06H
0018H: Scaling high limit
Set value, Decimal point ignored
03H/06H
0019H: Scaling low limit
Set value, Decimal point ignored
03H/06H
001AH: Decimal point place
0
000H: No decimal point
0001H: 1 digit after decimal point
0002H: 2 digits after decimal point
0003H: 3 digits after decimal point
(*1) If Lock 3 is selected, the set data is not saved in the memory. After the power is turned off, the
set value reverts to the value set before Lock 3 was selected.
3.5 idle
characters
Slave
address
Function
code
Exception
code
Error check
CRC
3.5 idle
characters
(01H)
(86H)
(03H)
(0261H)
1
1
1
2
Number of
characters