11

0016H: T

[–199.9 to 750.0 ]

0017H: N

[–320 to 2300 ]

0018H: PL-

[0 to 2500 ]

0019H: C (W/Re5-26)

[0 to 4200 ]

001AH: Pt100

[–199.9 to 999.9 ]

001BH: JPt100

[–199.9 to 900.0 ]

001CH: Pt100

[–300 to 1500 ]

001DH: JPt100

[–300 to 900 ]

001EH: 4 to 20mA DC [–1999 to 9999]
001FH: 0 to 20mA DC [–1999 to 9999]
0020H: 0 to 1V DC

[–1999 to 9999]

0021H: 0 to 5V DC

[–1999 to 9999]

0022H: 1 to 5V DC

[–1999 to 9999]

0023H: 0 to 10V DC

[–1999 to 9999]

03H/06H

0045H: Direct/Reverse action

0000H: Heating (Reverse action)
0001H: Cooling (Direct action)

0046H: Not used

03H/06H

0047H: AT bias

Set value, Decimal point ignored

03H/06H

0048H: ARW

Set value

03H/06H

006FH: Key lock

0000H: Key enabled 0001H: Key locked

06H

0070H: Key operation change flag clearing

0000H: No action

0001H: All clearing

03H

0080H: PV (input value) reading

Current PV, Decimal point ignored

03H

0081H: OUT1 (Heating) MV reading

OUT1 (Heating) MV (manipulated

variable), Decimal point ignored

03H

0082H: OUT2 (Cooling) MV reading

OUT2 (Cooling) MV,
Decimal point ignored

03H

0083H: Current SV reading

Current SV, Decimal point ignored

03H

0084H: Running step remaining time

reading

Remaining time
Decimal point ignored

03H

0085H: Status flag

0000

0000

0000

0000

2

15

to

2

0

2

0

digit: OUT1 (Heating) output

0: OFF

1: ON (For current

output, Not decided)

2

1

digit: OUT2 (Cooling) output

0: OFF

1: ON

2

2

digit: A1 output

0: OFF

1: ON

2

3

digit: A2 output

0: OFF

1: ON

2

4

to 2

7

digit: Not used (Always 0)

2

8

digit: Overscale

0: OFF

1: ON

2

9

digit: Underscale 0: OFF

1: RUN

2

10

digit: OUT (STOP)/OFF (RUN)

selection

0: OUT (STOP)
1: OFF (RUN)

2

11

digit: During AT

0: OFF

1: AT

2

12

digit: OUT/OFF key function

selection

0: Control output OUT/OFF

function (Fixed value control)

1: Program control function

2

13

digit: Controller/Converter mode

selection

0: Controller

1: Converter

2

14

digit: Not used (Always 0)

2

15

digit: Change in key operation

0: No

1: Yes

03H

0086H: Running step

Running step

0087H: Not used
0088H: Not used
00A0H: Not used

Содержание KT2

Страница 1: ...unication protocol selection Modbus ASCII mode Selects the communication protocol Unavailable Modbus ASCII mode Modbus RTU mode Instrument number setting 0 Sets the instrument number individually to e...

Страница 2: ...in Connection RS 232C RS 485 Communication speed 2400 4800 9600 19200bps Fig 4 1 RS 485 PLC KT2 No 0 KT2 No 1 KT2 No 2 KT2 No 30 RS 485 Host computer KT2 No 0 KT2 No 1 KT2 No 2 KT2 No 30 RS 485 RS 232...

Страница 3: ...speed of KT2 in accordance with that of the host computer For instrument number setting and communication speed selection refer to Chapter 1 Setup of the KT2 or the instruction manual for KT2 Memory c...

Страница 4: ...communication line within a 1 character transmission period after sending the response Master side Notice on programming Set the program so that the master can disconnect the transmitter from the com...

Страница 5: ...a value Value out of the setting range 17 11H Illegal setting Unsettable status 18 12H Illegal setting During setting mode by keypad etc 4 Data Data differs depending on the function code A request me...

Страница 6: ...range is set The function code MSB is set to 1 for the response message in exception error status 86H 38H 36H If an exception code 03H 30H 33H Value out of the setting range is returned the error can...

Страница 7: ...by setting the MSB to 1 because the former is an illegal function For negative acknowledgement exception code Table 6 4 2 below is set to the data of response message and returned to the master in or...

Страница 8: ...tatus 83H If an exception code 02H Non existent data address is returned the error can be determined by reading this code Fig 6 4 7 3 Setting Address 1 SV1 A request message from the master When setti...

Страница 9: ...1191H Step 9 time Set value Decimal point ignored 03H 06H 0001H SV1 Set value Decimal point ignored 0002H Not used 03H 06H 0003H AT 0000H Cancel 0001H Perform 03H 06H 0004H OUT1 Heating proportional...

Страница 10: ...ecimal point ignored 03H 06H 0026H A2 hysteresis Set value Decimal point ignored 0027H Not used 0028H Not used 03H 06H 0029H A1 action delayed timer Set value 03H 06H 002AH A2 action delayed timer Set...

Страница 11: ...g MV manipulated variable Decimal point ignored 03H 0082H OUT2 Cooling MV reading OUT2 Cooling MV Decimal point ignored 03H 0083H Current SV reading Current SV Decimal point ignored 03H 0084H Running...

Страница 12: ...failure Check the following The connection or wiring of the communication cable is not secure Burnout or imperfect contact on the communication cable and the connector Communication speed of the slav...