2.3 Setup on the Programmable Controller (GX Works3) Side
WUME-SCLGCT-3
2-4
2.3 Setup on the Programmable Controller (GX Works3) Side
This section explains how to set up parameters for IO-Link master
SC-LG2-CEF-P
.
The parameter setting method differs according to the master station unit.
The parameter setting method is explained below, using Mitsubishi Electric Corporation's
RJ71EN71 as an example.
Reference
For details, refer to the instruction manual of the master station unit that you use.
●
Example of RJ71EN71(CCIEF) unit parameter settings
Station type: Master station
Network No.: 1
<Network configuration settings>
Station number: 1
RX / RY settings (starting / ending): 1000 / 106F
RWw / RWr settings (starting / ending): 1000 / 1083
<Refresh settings>
Link side
CPU side
Device
name
Starting
address
Ending
address
Device
name
Starting
address
SB
00000
001FF
SB
00000
SW
00000
001FF
SW
00000
RX
01000
0106F
X
01000
RY
01000
0106F
Y
01000
RWr
01000
01083
W
01400
RWw
01000
01083
W
00400