background image

 
 

 

Figure 3.1 

Module Ground Position 

Junction Box 

Label 

Backside 

The ground holes 
are  on  the  backside  of 
the module frame. 

Ground Location  
(holes for bolt and nut) 

Array Wiring  

 

The  term  “array”  is  used  to  describe 
the  assembly  of  several  modules  on 
a  support  structure  with  associated 
wiring.  

 

Use  copper  wire  which  insulation  is 
sunlight  resistant  and  can  withstand 
the  maximum  possible  system  open 
circuit voltage. 

 

Interconnection of modules must be 
performed in a professional fashion. 
Wires  should  be  secured  and  only 
reasonable slack should be allowed. 

 

Check local codes for requirements. 

 
Earth Ground Wiring 

 

A  module  with  exposed  conductive 
parts 

is 

considered 

to 

be 

in 

compliance with UL 1703 only when 
it 

is 

electrically 

grounded 

in 

accordance  with  the  instructions 
presented 

below 

and 

the 

requirements 

of 

the 

National 

Electrical Code. 

 

All modules should be grounded. All 
structures  or metallic components in 
direct  contact  with  the  modules  or 
electric  wires  should  be  properly 
grounded too. To avoid the hazards 
of  electric  shock  or  fire,  modules 
should  be  grounded  by  the  frame 
only  at  the  locations  marked  in  this 
manual  (see  grounding  methods 
below). 

 

The array frame shall be grounded in 
accordance  with  NEC  Article  250 
(USA) or the CEC in Canada. 

 

Bonding shall be by a positive means, 
such as clamping, riveting, bolted or 
screwed  connectors,  or  welding, 
soldering  or  brazing.  If  the  bonding 
means  depends  upon  screw  threads 
two  or  more  screws  or  two  full 
threads  of  a  single  screw  must 
engage the metal. 

 

Great  care  should  be  exercised  to 
ensure  that  corrosion  caused  by  the 
grounding means be avoided. 

 

Corrosion can increase the resistance 
of  the  grounding  connection  on  the 
module,  or  can  even  cause  the 
grounding connection to fail entirely. 
Corrosion  can  be  caused  by  the 
effects  of  weather,  humidity,  dirt 
and  so  on.  It  can  also  be  caused 
when  two  dissimilar  metals  are  in 
contact (galvanic reaction).  

 

The 

module 

frame 

material 

is 

aluminum/magnesium alloy. 

 

All  fasteners  (nuts,  bolts,  washers, 

 

screws,  etc.)  must  be  stainless  steel 
unless otherwise specified. 

 

Length  of  bolt  should  not  be  more 
than  0.78’’  (20  mm)  in  order  to 
avoid  contacting  the  back-sheet  of 
the module. 

 

Acceptable 

grounding 

wire 

is 

following. 
Ilsco  Corp.  GBL-4DBT  10-14AWG-
Solid, 

4-6, 

8, 

10-14AWG-Strand 

Burndy L L C CL501TN 14AWG-Solid, 
14-4AWG-Strand 
Tyco  Electronics  Corp.  1954381-
1/1954381-2 10-12AWG Solid 

 

Each ledge on the module frame has 
two  holes  for  bolts  (0.205’‘diameter 
(5.2  mm)).  These  ground  holes  are 
marked with a “G” or "ground mark"  
adjacent  to  their  location  on  the 
frame rail (see Figure 3.1). 

 

Ground  wires  must  be  connected  to 
the  module’s  metal  frame  at  one  of 
these locations. 

 

Lay-in lugs or grounding clips can be 
used 

to 

ground 

Panasonic 

PV 

modules. 

Both 

methods 

are 

explained below, please choose one. 

 
 
 
Grounding  Locations  (or  grounding 
holes) 

Using bolt and nut  
(see Figures 3.3 and 3.5) 

 

If  using  this  method,  use  one  of  the 
holes  with  diameter  of  0.205’‘  (5.2 
mm)  

 

The bolt and nut size should be 

No.8  (0.164’‘diameter  (4.16 
mm)), 

or 

No.10 

(0.190’‘diameter  (4.83  mm)) 
or  M5  (0.197’‘diameter  (5.0 
mm)). 

 

Star  washers  must  be  used  to 

make  contact  through  the 
anodization  of  the  module 
frame.  

 

In  this  case,  the  screw  threads  are 
not  providing  the  electrical  ground 
contact. 

 

Recommended 

torque 

value 

in 

tightening  bolt  and  nut  is  2.3  N.m 
(20in-lb). 

 
Grounding Methods 

 

Where 

common 

grounding 

hardware  (nuts,  bolts,  star  washers, 
spilt-ring  lock  washers,  flat  washers 
and  the  like)  is  used  to  attach  a 
listed 

grounding/bonding 

device, 

the  attachment  must  be  made  in 
conformance  with  the  grounding 
device manufacturer's instructions. 

 

Common  hardware  items  such  as 
nuts, 

bolts, 

star 

washers, 

lock 

Содержание HIT VBHN325SA17

Страница 1: ...part of the Panasonic Group and is in charge of the manufacturing process for Panasonic HIT Model No VBHN325SA17 VBHN330SA17 Contents Please read before installation Safety Precautions General Information 3 Warning 3 Cautions 3 General Safety 3 UL Listing Information 3 Installation General 4 Notes on Installation 4 Operating Conditions 5 Special Conditions 5 Specifications Note on Specifications 6...

Страница 2: ...2 Edition Revision Date Revised Item Revised Content New Edition 2017 11 15 ...

Страница 3: ...and they do not subject the module to mechanical or electrical hazards Sparks may occur do not install modules where flammable gases or vapors are present Never rest or leave a module unsupported or unsecured Do not drop modules Do not use or install broken modules Do not artificially concentrate sunlight on a module Do not touch the junction box terminals Do not change the wiring of bypass diodes...

Страница 4: ...ntact an Authorized Representative with questions regarding mounting profiles for Panasonic HIT Notes on Installation Clearance between the roof surface and module frame is required to allow cooling air to circulate around the back of the module This also allows any condensation or moisture to dissipate The required clearance between the roof surface and the module is more than 4 inch Panasonic re...

Страница 5: ...l Conditions see below 2 The operating temperature must be within 40 C 40 F to 85 C 185 F 3 The wind pressure load of the installation site should be less than Load Resistance shown in Mount Locations and Load Resistance table in Figure 2 4 Some environmental conditions could apply Please refer to Panasonic s warranty exclusions Special Conditions 1 The operating temperature and installation place...

Страница 6: ...LING Do not hit the back sheet of a module by the connector when unpacking and handling To avoid the damage of the back sheet by connector fix the cables to the frame with tape after unpacking see below After fixing the cable to the frame do not stack modules to avoid the damage of the cable Do not handle modules by their cables or junction box Handle them by the frame with both hands in any situa...

Страница 7: ...ounding connection to fail entirely Corrosion can be caused by the effects of weather humidity dirt and so on It can also be caused when two dissimilar metals are in contact galvanic reaction The module frame material is aluminum magnesium alloy All fasteners nuts bolts washers screws etc must be stainless steel unless otherwise specified Length of bolt should not be more than 0 78 20 mm in order ...

Страница 8: ...trand 45 in lbs Recommended torque value in tightening bolt and nut is 2 3 N m 20in lb Using a Grounding Clip with bolt and nut Use Tyco Electronics 1954381 2 as grounding clip As shown in Figure 3 4 place the grounding clip onto the module frame Thread the hex nut onto the end of the screw then using a 3 8 in wrench tighten the nut Recommended torque value in tightening bolt and nut is between 1 ...

Страница 9: ...s manual Panasonic assumes no responsibility for any infringement of patents or other rights of third parties which may result from use of modules No license is granted by implication or under any patent or patent rights The information in this manual is believed to be reliable but does not constitute an expressed and or implied warranty The return of any modules will not be accepted by Panasonic ...

Страница 10: ...owed by additional suffixes may be followed by suffix numbers and letters PV PLS S PV PLS B may be followed by suffix numbers and letters may be followed by suffix numbers and letters Male PV connectors PV KST4 EVO2 2 5 6 or 10 followed by I II III or IV followed by UR Female PV connectors PV KBT4 EVO2 2 5 6 or 10 followed by I II III or IV followed by UR PV AZS4 male PV AZB4 female http ec staubl...

Страница 11: ...more than 0 78 20 mm If using a brass cup washer a flat washer must be inserted between the cup washer and module frame and the flat washer diameter must be greater than the cup washer diameter Cup washer Terminal cup Stainless steel or brass Star washer Stainless steel Flat washer Stainless steel Flat washer Stainless steel Spring washer Stainless steel Bolt Stainless steel 8 10 M5 Grounding hole...

Страница 12: ...e Longer side Grounding hole 0 205 diameter 5 2mm Grounding Clip 8 32 Screw Stainless steel Nut Stainless steel Copper wire Length not less than 0 63 16 mm not more than 0 78 20 mm Figure 1 2 Installation Solar Module Module Mounting Structure Rail 5 16 or M8 Bolt Stainless steel 5 16 or M8 Nut Stainless steel Flat washer Stainless steel Flat washer Stainless steel Spring washer Stainless steel ...

Страница 13: ...ge Voc 69 7 69 6 Short Circuit Current Isc 6 07 6 03 Cell Type Silicon hetero junction Silicon hetero junction Maximum System Voltage 600 600 Factory Installed Bypass Diodes 4 4 Maximum series fuse A 15 15 Silicon hetero junction Monocrysttaline silicon amorphous silicon hetero junction Mechanical Specifications Length mm inches Width mm inches Frame Depth mm inches Weight kg pounds 1590 62 60 105...

Страница 14: ...d Resistance L1 0 230 230 L2 450 380 345 S1 0 S2 250 50 psf 2400 Pa 112 psf 5400 Pa 112 psf 5400 Pa 50 psf 2400 Pa 50 psf 2400 Pa 91 psf 4400 Pa 112 psf 5400 Pa 50 psf 2400 Pa Load Resistance Positive Load Load Resistance Negative Load Mounting location range Note Load Resistance shown above is UL Test Load The UL Test Load is 1 5 times the design load value stated in specifications section Figure...

Отзывы: