As to wire for use to link power supply cord with switch, please firmly connect wire with terminal with torque
force1.2N·m below and ensure the joint doesn't work loose and no solder is attached on the conductor of power
supply cord.
Please disconnect the connector for use to link red wire with blue wire and connect the connector for linking the
red wire and white wire. When shifting the air volume from H to SH. (as shown above)
There are two combinations for air volume: High /Low and SH (Special High)/Low.
The factory set is High /Low. Please shift it to SH (Special High)/Low if required.
Please perform the ground connection.
The total rated current should less than 50% current of switch When multiple products are linked together for use.
After completion, please ensure to fix the terminal box with screws.
Ground wire
1
0m
m
4
0m
m
4
0m
m
1
40
m
m
Power cord of R type
Power cord of L type
Interlock with air conditioner
Remove the cover of switch box.
Remove the three screws fixed on the cover of switch box.
After putting the power supply cord through cord bushing, according to the wiring diagram, respectively fix the
power cord and wire for linking with switch on the terminal and fix the ground wire to its terminal.
Do not put the pressure at the joint of wire, use the cord clip to fix the power supply cord and wire for linking with switch.
Wire connection
Peel off the sheath of power supply cord by 40mm, and
peel off the sheath of each core wire by 10mm.
Please pay attention to the length of ground wire for
left type and right type.
Use this function
Not use this function
Botton
Botton
Botton
Botton
Botton
Botton
Off
On
WIRING DIAGRAM
The screws
fixed in the
switch box
R type
L type
FY-E
**
PM1
FY-E
**
PM1L