Make sure the direction of the arrow
on the OA filter is correct.
2
Latch
Frame cover
Lock plate
MAINTENANCE
AIR FLOW
AIR FLO
W
AIR FLOW
AIR FLOW
1
Main
switch
Filter reset
button
I
O
10
20
30
40
50
60
50
60
70
80
90
100
50
60
70
80
90
100
Supply Air
Air fourni
(CFM)
(CFM)
min/h
min/h
Exhaust Air
Air
d'évacuation
Filter
Reset
Button
Bouton de
réinitialisation
du filtre
(pi
3
/min)
(pi
3
/min)
It is suggested to replace the OA filter
every 6 months. Please fill in beginning
time on new OA filter before replacing.
Please replace OA filter by Panasonic
Model FV-FL0810VE1 or FV-FL1310VE1.
OA filter
RA filter
BEGINNING TIME:
OA filter
RA filter
Energy recovery core
1
2
2
Clean the OA filter, RA filter and energy
recovery core.
5
Connect power, press filter reset button with sound of beep, then filter indicator and
buzzer sound will be off.
1
2
3
Reinstall the filters.
4
Reinstall and close frame cover by locking the latches, then reset the lock plate.