FP2 Positioning Unit
Home Return
10-19
Home return start flag (Y_2
)
1. Home return is initiated based on the parameters written to the positioning unit.
2. The flag is not initiated during the time that the pulse output busy flag (X_0) is ON.
(It has already been initiated).
3. The flag is reset when the power supply is turned OFF.
Near home input (X_7)
1. Deceleration begins when the near home switch input connected to the positioning unit becomes valid.
2. The leading edge of the signal is detected, so changes to flags following the input do not affect
operation.
-Confirmation of the input logic is necessary. <Refer to page 10-24.>
Home input (X_6)
1. The table stops when the home switch input becomes valid after the near home switch input
connected to the positioning unit became valid.
2. The leading edge of the signal is detected, so changes to flags following the input do not affect
operation.
-Confirmation of the input logic is necessary. <Refer to page 10-24.>
Deviation counter clear output
1. This goes ON for approximately 1 ms or 10ms after the home return has been completed.
- This is used in systems in which a servomotor is used.
Pulse output busy flag (X_0
)
1. This goes ON with the next scan after home return has been initiated, and goes OFF when the pulse
output is completed.
2. Operation cannot be shifted to any other operation while this signal is ON (except for a forced stop
and a deceleration and stop).
3. This is reset when the power supply is turned OFF.
-This flag is shared among E point control, P point control, JOG operation, JOG positioning operation
and home return. (except for the pulser input operation)
Home return done flag (X_8)
1. This goes ON when a home return is completed, and is maintained until E point control, P point
control, JOG operation, JOG positioning operation, a home return, or pulser input operation is started.
2. This flag is reset when the power supply is turned OFF.
Pulse output done flag (X_1)
1. The pulse output done flag does not go ON when a home return is completed.
2. Before a home return is started, this goes from ON to OFF when E point control, P point control, JOG
operation, JOG positioning operation or pulser input operation is completed.
3. If this is OFF before a home return is started, it remains OFF and does not change.
4. This flag is reset when the power supply is turned OFF.
-This flag is common to E point control, P point control, JOG operation, JOG positioning operation and
pulser input operation.
Содержание FPG Series
Страница 1: ......
Страница 12: ......
Страница 17: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Страница 18: ...Fanctions of FP Σ Positioning Unit FPΣPositioning Unit 1 2 ...
Страница 24: ...Fanctions of FP Σ Positioning Unit FPΣPositioning Unit 1 8 ...
Страница 25: ...Chapter 2 Parts and Specifications ...
Страница 26: ...Parts and Specifications FP Positioning Unit 2 2 ...
Страница 29: ...Chapter 3 Wiring ...
Страница 30: ...Wiring FP Positioning UNit 3 2 ...
Страница 44: ...Wiring FP Positioning UNit 3 16 ...
Страница 45: ...Chapter 4 Confirming the Unit Settings and Design Contents ...
Страница 46: ...Confirming the Unit Settings and Design Contents FP Positioning Unit 4 2 ...
Страница 61: ...Chapter 5 Power ON and OFF and Booting the System ...
Страница 62: ...Turning the Power ON and OFF and Booting the System FP2 positioning Unit 5 2 ...
Страница 70: ...Turning the Power ON and OFF and Booting the System FP2 positioning Unit 5 10 ...
Страница 71: ...Chapter 6 E Point Control Single Speed Acceleration Deceleration ...
Страница 83: ...Chapter 7 P Point Control Multi Stage Acceleration Deceleration ...
Страница 98: ...P Point Control Multi Stage Acceleration Deceleration FP Positioning Unit 7 16 ...
Страница 99: ...Chapter 8 JOG Operation ...
Страница 113: ...Chapter 9 JOG Positioning Operation ...
Страница 114: ...JOG Positioning Operation FP Positioning Unit 9 2 ...
Страница 129: ...Chapter 10 Home Return ...
Страница 130: ...Home Return FP2 Positioning Unit 10 2 ...
Страница 146: ...Home Return FP2 Positioning Unit 10 18 10 4 Action of the I O Flag Before and After a Home Return Operation ...
Страница 155: ...Chapter 11 Pulser Input Operation ...
Страница 167: ...Chapter 12 Deceleration Stop and Forced Stop ...
Страница 168: ...Deceleration Stop and Forced Stop FP2 Positioning Unit 12 2 ...
Страница 174: ...Deceleration Stop and Forced Stop FP2 Positioning Unit 12 8 ...
Страница 175: ...Chapter 13 Feedback Counter ...
Страница 176: ...Feedback Counter FP2 Positioning Unit 13 2 ...
Страница 185: ...Chapter 14 Precautions Concerning the operation and Programs ...
Страница 186: ...Precautions Concerning the Operation and Programs FP Positioning Unit 14 2 ...
Страница 192: ...Precautions Concerning the Operation and Programs FP Positioning Unit 14 8 ...
Страница 193: ...Chapter 15 Operation if an Error Occurs ...
Страница 194: ...Operation if an Error Occurs FP Positioning Unit 15 2 ...
Страница 207: ...Chapter 16 Specifications ...
Страница 208: ...Specifications FP Positioning Unit 16 2 ...
Страница 217: ...Chapter 17 Dimensions and Driver Wiring ...
Страница 218: ...Dimensions and Driver Wiring FP2 Positioning Unit 17 2 ...
Страница 219: ...Dimensions and Driver Wiring FP2 Positioning Unit 17 3 17 1 Dimensions ...
Страница 229: ...Chapter 18 Sample Program ...
Страница 230: ...Sample Program FP Positioning Unit 18 2 ...
Страница 233: ...FP Positioning Unit Sample Program 18 5 Program ...
Страница 238: ......
Страница 239: ......
Страница 240: ......