![Panasonic FP2 Series Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/panasonic/fp2-series/fp2-series_user-manual_262311034.webp)
FP2 Serial Data Unit
Confirming the Unit Settings and Design Contents
3
−
6
3.2
Setting the Transmission Speed and Transmission Format
3.2.1
Transmission Format Settings Set Using Switches
The transmission speed and data length parameters of the COM.1 and COM.2 ports
can be changed using the transmission format setting switches. Values specified using
these switches become effective when the power supply is turned on.
Transmission speed: on
−
on
−
off: 19200bps
on
−
off
−
on: 9600bps
on
−
on
−
on: 4800bps
Data length: on: 8 bits
off: 7bits
For COM.1 port
For COM.2 port
The transmission format setting switches are located on the rear of the unit.
3.2.2
Transmission Format Settings Using the Shared Memory
Transmission format values which are set automatically in advance when the power
supply is turned on can be changed by changing the contents specified in the shared
memory, and turning the software reset (Y1D) on and then off again.
Procedure:
FP2
CPU
unit
FP2 serial
data unit
Shared
memory
1003, 1004
1003, 1004
1003, 1004
1003, 1004
Y1D: on
X1E: on
Y1D: on
Transmission
format is
written to
shared memory
using
F151
(WRT)
instruction.
1. Transmission format
is written.
2. Software reset (Y1D)
is turned on.
3. When software reset is
completed, “Software
Reset Completed flag”
(X1E) goes on.
4. After software reset
is completed, soft-
ware reset (Y1D)
which went on earli-
er goes off.
Shared
memory
Shared
memory
Shared
memory
The transmission format setting area consists of addresses 1003 (COM.1) and 1004
(COM.2) of the shared memory.
Содержание FP2 Series
Страница 1: ......
Страница 6: ...FP2 Serial Data Unit Table of Contents iv ...
Страница 18: ...FP2 Serial Data Unit Functions of Serial Data Unit 1 2 ...
Страница 22: ...FP2 Serial Data Unit Functions of Serial Data Unit 1 6 1 3 Restrictions on Units Combination ...
Страница 24: ...FP2 Serial Data Unit Parts and Functions 2 2 ...
Страница 30: ...FP2 Serial Data Unit Confirming the Unit Settings and Design Contents 3 2 ...
Страница 44: ...FP2 Serial Data Unit Communication with External Devices 4 2 ...
Страница 66: ...FP2 Serial Data Unit Precautions Regarding Serial Data Unit Operation and Programs 5 2 ...
Страница 72: ...FP2 Serial Data Unit Operation If an Error Occurs 6 2 ...
Страница 78: ...FP2 Serial Data Unit Specifications 7 2 ...
Страница 86: ...FP2 Serial Data Unit Specifications 7 10 7 4 Transmission Format ...
Страница 88: ...FP2 Serial Data Unit Sample Programs 8 2 ...
Страница 98: ...FP2 Serial Data Unit Sample Programs 8 12 8 2 Table of ASCII Codes ...
Страница 100: ...Record of changes FP2 Serial Data Unit R 2 ...
Страница 101: ......
Страница 102: ......