FP2 Analog Unit
Analog I/O Conversion Characteristics and Conversion Cycle Time
6 - 9
6.1
Analog Input Conversion Characteristics
If the input value exceeds the rated analog input range, the converted value becomes:
Range
Input value
Converted value
Thermocouple S
-40
_
C or less (*)
-400
+1500
_
C or more
+15000
Thermocouple J
-200
_
C or less
-2000
+750
_
C or more
+7500
Thermocouple K
-200
_
C or less
-2000
+1000
_
C or more
+10000
Thermocouple T
-200
_
C or less
-2000
+350
_
C or more
+3500
Thermocouple R
-50
_
C or less (*)
-500
+1500
_
C or more
+15000
Broken wire
+20000
(*) For the S and R ranges, conversion will be performed even if the input is outside of
the ranges 0 to -40
°
C and 0 to -50
°
C (respectively), but the precision cannot be
guaranteed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание FP2 -AD8
Страница 23: ...Chapter 3 Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 24: ...FP2 Analog Unit Wiring 3 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 37: ...Chapter 5 Initial Settings Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 99: ...Chapter 13 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 100: ...FP2 Analog Unit Troubleshooting 13 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 103: ...Chapter 14 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 104: ...FP2 Analog Unit Specifications 14 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...