Technical/Programming Manual
FT1020G3 Rev 2.2.1
99
Text
= User definable interlocking text to be shown in menu H9/C1. Can be written
in this field or in the "Texts" dialog box, see chapter "Creating the alarm texts via
EBLWin
Buzzer
checked = activated interlocking input will turn on the FT1020G3 buzzer
(0.8 / 0.8 sec.)
114
. The buzzer can be silenced. It will be automatically turned on
again, if a new interlocking input is activated.
Latched output
checked = Output reset has to be performed via menu H9/C3.
(Automatically output reset will not take place when the control expression
becomes false.).
Fault
checked = Fault detection ON.
Fault Detection Time
: If the input is not activated within 5-255 seconds
after the output is activated
115
, a fault will be generated:
FAULT: Interlocking input AAA/PP
15.2
Interlocking indications
One or more activated Interlocking Combinations (interlocking output and/or input) are
listed in the CIE display
116
:
Disabled interlocking output is indicated by the LED "Disablements".
15.3
Interlocking outputs and inputs (H9)
Menu H9 has the following sub menus.
15.3.1
Activated interlocking outputs / inputs (H9/C1)
The following information will be shown in menu H9/C1:
Interlocking area AAA point PP output active
User definable text message..
dd-mm-yyyy hh:mm
or
Interlocking area AAA point PP input/output
active
User definable text message..
dd-mm-yyyy hh:mm
or
Interlocking area AAA point PP input active
User definable text message..
dd-mm-yyyy hh:mm
AAA
= Interlocking combination Area
114
Priority order: Fire alarm
– Pre-warning - Interlocking - Fault.
115
After the end of the delay time (if used).
116
This indication has the lowest priority and will only be shown if the display was empty.
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Technical Programming Manual FT1020G3 Rev 2 2 1 For Software V2 2 x FT1020G3 CIE M435 February 2016 ...
Страница 2: ...This page has deliberately been left blank ...
Страница 187: ...Technical Programming Manual FT1020G3 Rev 2 2 1 184 Figure 60 FT1020G3 General arrangement ...
Страница 188: ...Technical Programming Manual FT1020G3 Rev 2 2 1 185 Figure 61 FT1020G3 Block Wiring Overview ...
Страница 189: ...Technical Programming Manual FT1020G3 Rev 2 2 1 186 Figure 62 FT1020G3 Standard Block Wiring Diagram ...