15
DAILY USER´S MANUAL
•
EBL128 VERSION 2.2.X
•
DOCUMENT NUMBER: MEW01786
•
REVISION: 1
11.
PERFORM ZONE TEST (H7)
Up to 99 zones can be set in test mode, which is indicated by the LED "Test mode" on the front. After one
hour without any testing activity, the test mode will be automatically ended. Valid for each zone respectively.
No outputs will be activated except the fire door outputs. The test mode alarm will be automatically reset
after approximately 10 seconds.
a)
Log on to the c.i.e.
b)
Navigate to menu H7.
c)
Press "A". The sub menu "Set zone in test mode D1" opens.
d)
Press "A". Use the keypad to type a zone number (01-99).
e)
Press "A". The zone is now in test mode.
f)
If more zones shall be set in test mode, repeat procedure c) to e).
g)
Perform the testing. To end the test mode for one zone press
.
END TEST MODE
a)
Open the sub menu D1 as described above.
b)
Press
to open the sub menu "End zone in test mode D2".
c)
Press "A".
d)
L = this is a list in which you can scroll. Select the zone for which the test mode shall be ended.
e)
Press "A".
f)
The next zone in the list will be shown. End the test mode like above.