manualshive.com logo in svg
background image

 

 
 
 

PANASONIC FIRE ALARM SOLUTIONS 

DAILY USER´S MANUAL 

EBL128 VERSION 2.2.X 

 
 
 

 

Содержание EBL128

Страница 1: ...PANASONIC FIRE ALARM SOLUTIONS DAILY USER S MANUAL EBL128 VERSION 2 2 X...

Страница 2: ...DOCUMENT INFORMATION DOCUMENT NAME DAILY USER S MANUAL EBL128 VERSION 2 2 X DOCUMENT NUMBER MEW01786 DATE OF ISSUE 2015 01 19 REVISION 1 DATE OF REVISION 2015 03 30...

Страница 3: ...1 HOW TO LOG ON 7 5 NAVIGATION GENERAL PROCEDURES 8 6 PERFORM MONTHLY TEST H1 9 7 DISABLE OR RE ENABLE H2 10 7 1 SUB MENU LIST B1 B11 10 8 SET CALENDER AND CLOCK H3 12 9 PRESENT SYSTEM STATUS H4 13 9...

Страница 4: ...ed for the daily duties like disablements re enablements zone tests and so on in the EBL128 system Due to continual development and improvement different S W versions can be found This document is val...

Страница 5: ...4 DAILY USER S MANUAL EBL128 VERSION 2 2 X DOCUMENT NUMBER MEW01786 REVISION 1 2 DESCRIPTION OF THE FRONT YYYY MM DD EBL128 hh mm i User programmable information text...

Страница 6: ...lt condition for fault tx routing equipment is activated 10 Sevice One or more sensors have reached the service level See menu H4 U4 11 Alarm devices Steady light Output s type Alarm device are disabl...

Страница 7: ...the menus 26 Alarms queued Used when LEDs Alarms queued are lit Scroll through the queued alarm points or zone addresses 27 Evacuate Test LED Used to activate all the sounders or test LED Option only...

Страница 8: ...t H10 Change password H8 Maintenance H9 Interlocking outputs and inputs Described in this document H10 Change password 4 LOG ON TO THE CONTROL UNIT C I E USER NAME Up to ten users 0 to 9 may be progra...

Страница 9: ...indicates that this is list in which you can scroll with Press A to select accept Press the digits on the numeric pad to choose a menu or enter data If an operation is completed successfully the disp...

Страница 10: ...Up to four zones can be set in test mode Use the keypad to type the zone numbers f Press A g Perform the test h To end the test press A If the routing equipment shall not be tested the monthly test is...

Страница 11: ...enablement shall be used Press 1 insert time hh mm Press A B3 Disable output Use the keypad to select type of output 0 Loop unit output 1 C i e output S0 or S1 2 C i e output R0 3 C i e expansion boar...

Страница 12: ...s type Extinguishing 3 Output type Interlocking Press A B9 Disable re enable alarm devices Select Alarm devices in normal condition or Alarm devices disabled Press A The status is changed B10 Disable...

Страница 13: ...SET CALENDER AND CLOCK H3 a Log on to the c i e b Navigate to menu H3 c Press A Depending on if it is the date time and or the day that shall be set press and to highlight it d Use the keypad to enter...

Страница 14: ...the keypad to specify the Start sensor The default zone address 00 00 can be used Press A This is a list in which you can scroll NOTE For most detectors additional information can be shown by using U...

Страница 15: ...edged and corrected No status info not corrected serviced and not acknowledged fault Acknowledged not corrected serviced but acknowledged fault Serviced corrected serviced but not acknowledged fault a...

Страница 16: ...mately 10 seconds a Log on to the c i e b Navigate to menu H7 c Press A The sub menu Set zone in test mode D1 opens d Press A Use the keypad to type a zone number 01 99 e Press A The zone is now in te...

Страница 17: ...status is changed NOTE For the following the output must be reset via this menu Interlocking output activated via its control expression and with latching output selected in EBLWin Interlocking output...

Страница 18: ...est standards ensuring high quality and reliable fire alarm solutions Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 E mail info p...