background image

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00503 

2006-04-04 

4 / 2010-09-30 

 

Type numbers 

4550 

EBL128 c.i.e. (128 addresses).  Batteries are not included. 

4552 

RS485 transceiver component, for up to four display units, i.e. Ext. Fire Brigade 
Panels 1826 / 1828, Ext. Presentation Unit 1728 and/or Alert Annunciation Units 
1735 / 1736. 

4551 

Expansion board holder.  (For two 4580 and two 4581 expansion boards.) 

4580 

8 zones expansion board.   

4581 

8 relays expansion board.   

4513 

Cabinet for drawings.  (Similar to the EBL128 cabinet.)  

The  4580  board  can  be  used  to  connect 

conventional

  detectors  and  manual  call  points  to 

EBL128.  An end-of-line capacitor (470 nF) shall be connected in the last alarm point on each 
zone line. 

More information is available in the EBL128 Planning Instructions & Operating Instructions. 

Technical data 

Voltage 

  primary  (V AC) 
  secondary  (V DC) 
    normal 
    by battery backup 

 

230 
 
24 
21 - 30 

Current consumption (mA) 

Depending on connected units, etc. See EBL128 Planning Instructions. 

Ambient temperature (

C) 

  Operating 
  storage 

 

-5 to +40 
-40 to +75 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating (estimated) 

IP32 

Inputs 

1 COM loop for 128 addresses 

 

1 programmable input.  NO / NC (R>2K = open circuit).  Max. 2 mA.  
Alt. supervised, normally high resistance (3K3) or low (680R). 

Outputs 

1 programmable supervised voltage output (24 V DC, max. 500 mA) 

 

 

1 programmable supervised voltage output (24 V DC, max. 200 mA) 

 

 

1 programmable relay output. 

1

  Default set for routing equipment (Fire 

brigade tx).   

 

1 non-programmable relay output. 

1

  For routing equipment (Fault tx). 

 

Power supply (24 V DC, max. 200 mA) for routing equipment   

 

Power supply (24 V DC, max. 500 mA) for external equipment (Web-
server, up to 4 ext. FBPs, etc.)    Web-server requires approx. 65 mA.   

Interfaces 

RS232 ("D" connector) for a PC (Win128) 

 

RS232 for a Web-server 1598 

 

Socket for an optional RS485 transceiver, for ext. FBPs, EPUs and/or 
AAUs. 

Size H x W x D (mm) 

511 x 416 x 123 

Weight (kg) 

12.2   (Excl. Batteries) 

Colour (metal cabinet) 

Aluminium & light grey (NCS S1500-N, PMS Cool Grey 2)  

Approvals 

 EC certificate no. 

0786-CPD-20971

 

 

EN54-2:1997 / A1:2006,  EN54-4:1997 / A2:2006 

 

The Swedish front conforms to SS3654. 

Note!  

All voltages are nominal.  For more information see EBL128 Planning Instructions MEW00508. 

1

  Relay contacts:  max. 1 A @ 30 V DC.

 