INSTRUCTION MANUAL
Separate type · digital sensor controller
DPC-L100
Sereis
For liquid / gas
MJE-DPCL100 No. 0081-79V
Thank you very much for purchasing Panasonic products.
Read this Instruction Manual carefully and thoroughly for the correct and optimum
use of this product.
Kindly keep this manual in a convenient place for quick reference.
WARNING
●
Never use this product as a device for personnel protection.
●
In case of using devices for personnel protection, use products which
meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel
protection applicable in each region or country.
●
The product for use inside Japan complies with Japanese Measurement
Laws. Avoid using the product model for outside of Japan within Japan.
1
PART DESCRIPTION
Notes: 1) Attach the unit switch plate corresponds to the set pressure unit.
2) The product for use inside Japan can be set only to “MPa” or “kPa.”
2
MOUNTING
●
The sensor mounting bracket
MS-DP1-6
is available as an option.
When mounting the sensor onto the
sensor mounting bracket, etc., the tight-
ening torque should be 0.5N·m or less.
●
T h e p a n e l m o u n t i n g b r a c k e t
MS-DP1-2
(optional), as well as the
front cover
MS-DP1-3
(optional) are
also available.
●
For mounting of the panel mounting
bracket, refer to the Instruction Manual
enclosed with
MS-DP1-2
.
3
CONNECTION OF PRESSURE SENSOR HEAD
●
In case of initial set up or reset, select pressure range.
●
incase changing pressure sensor head, check pressure range.
Connection method
1.
Insert the pressure sensor head cable into the
product’s connector area for the pressure sen-
sor head as shown in the right figure.
Disconnection method
1.
Pressing the release lever of the pressure sen-
sor head cable, pull out the connector.
Note: Do not pull by holding the cable without pressing the re-
lease lever, as this can cause cable break or connector
break.
<Terminal pin arrangement>
Terminal pin No.
Terminal name
1
Sensor head supply voltage
2
Analogue input
3
0V
4
Not used
4
WIRING
Connection method
1.
Insert cable with connector
CN-66A-C□
into
the product’s connector area for a power / I-O
cable as shown in the right figure.
Disconnection method
1.
Pressing the release lever of the cable with con-
nector, pull out the connector.
Note: Do not pull by holding the cable without pressing the release
lever, as this can cause cable break or connector break.
<Terminal pin arrangement>
Terminal pin
No.
Terminal name
Terminal pin
No.
Terminal name
1
+V
4
Comparative output 1
2
Analogue voltage
/ current output
5
Comparative output 2
3
0V
6
External input
Connector area for a
power supply / I-O cable
Connector area for a
pressure sensor head
Output 1 operation
indicator
Lights up when com-
parative output 1 is ON
Output 2 operation
indicator
Lights up when com-
parative output 2 is ON
Mode selection key
Set value UP key
Set value
DOWN key
Attach area for
unit switch plate
(Note 1, 2)
Main display
Sub display
Release lever
Pressure
sensor
head cable
<Connector area of the pressure sensor head cable>
e-con: 1473562-4
[Tyco Electronics AMP G.K.]
Release lever
Cable with
connector
CN-66A-C
□
<Connector area of the cable with connector>
Housing: PAP-06V-S
[JST Mfg. Co., Ltd.]
M3 (length 6mm)
screws with washers
Accessory with
MS-DP1-6
Sensor mounting bracket
MS-DP1-6
(Optional)
1 2 3 4 5 6
1 2 3 4
9
MENU SETTING MODE
●
The mode will change to RUN mode when the mode selection key is held
down during this setting process. In doing so, changed items before holding
down the mode selection key have been set.
Note: 1) In case connecting pressure range 1MPa type of pressure sensor head to Japanese model controller,
only “MPa” or “kPa” can be set. Also, in case connecting 3.5MPa or more type, setting item for unit
change is not displayed.
2) in case of connecting pressure range 3.5MPa type of sensor head to out side of japan type controller.
“
” is not displayed.
Setting Item
Factory setting
Description
Comparative
output 1 output
mode setting
Sets comparative output 1 output mode.
Comparative
output 2 output
mode setting
Sets comparative output 2 output mode.
N.O. / N.C.
selection
Sets when Nomal Open (N.O.) or Normal Close (N.C.).
Initial state of excepting OFF of the comparative output 2 setting is “
.”
Analogue voltage
/ current output
selection
Selects Analogue voltage output or analogue current output.
Function setting
Sets Auto-reference function or remote zero-adjustment function and current
value hold function or peak / bottom 2 function.
Response time
setting
Sets response time.
The response time can be select from 5ms, 10ms, 25ms, 50ms, 100ms,
250ms, 500ms, 1,000ms or 5,000ms.
Display color
selection of the
main display
Selects display coler of main display.
Unit selection
Selects pressure unit.
RUN mode
EASY mode
Hysteresis
mode
Press for 2 sec.
Window com-
parator mode
<Comparative output 2 output mode setting>
EASY mode
Hysteresis
mode
Window
comparator
mode
OFF mode
<N.O. / N.C. selection> (When the comparative output 2 output mode setting is set to OFF)
N.C.
N.O.
<N.O. / N.C. selection> (When the comparative output 2 output mode setting is set to other than OFF)
Output 1: N.O.
Output 2: N.O.
Output 1: N.C.
Output 2: N.C.
Output 1: N.O.
Output 2: N.C.
Output 1: N.C.
Output 2: N.O.
<Analogue voltage / current output selection>
Analogue
voltage
output mode
Analogue
current out-
put mode
<Function setting>
OFF
Auto-reference
function mode
Remote zero-
adjustment
function mode
Current
value hold
function
Auto-peak /
bottom hold
2 function
<Response time setting>
10ms
5ms
5,000ms
<Display color selection of the main display>
Red when ON
Green when OFF
Green when ON
Red when OFF
Always red
Always green
<Unit selection> (Note 1)
kPa (Note 2)
MPa
bar
kgf/cm
2
psi
<RUN mode>
<Comparative output 1 output mode setting>
10
PRO MODE
●
The mode will change to RUN mode when the mode selection key is held
down during this setting process. However, changed items before holding
down the mode selection key have been set.
Setting item
Factory setting
Description
Sub display
selection
Changes the indication of the sub display in RUN mode.
“
” : Displays nothing.
“
” : Current pressure unit is displayed.
“
” : Desired No. can be shown.
“
” : Desired numbers, alphabets (some of them cannot be displayed)
and signs can be shown.
Display speed
selection
Changes the speed of the displayed pressure value on the main display.
Hysteresis fixed
value selection
Sets hysteresis of the EASY mode and the window comparator mode.
(8 steps)
Displayed color
relation selection
The setting contents set at the displayed color setting in Menu setting mode
can be related with either comparative output 1 or comparative output 2.
External input
relation selection
The setting contents set at auto reference function and remote zero-adjustment
function can be shifted to correspond to either comparative output 1, 2 or 1 / 2.
Eco mode
setting
Current consumption can be lowered.
“
” : Normal operation (ECO mode is OFF.)
“
” : If any key operation is not carried out for approx. 5 sec. in RUN
mode, the display becomes dark.
“
” : If any key operation is not carried out for approx. 5 sec. in RUN
mode, the display is turned OFF.
Press any key to temporarily show the normal indication.
Setting check
code
Current setting contents can be checked. For codes. refer to “Code table.”
Setting copy
mode
The setting of the master side sensor can be copied to the slave side sensors.
For details, refer to “
SETTING COPY FUNCTION
.”
“
” : The setting contents are copied.
“
” : The setting contents are copied, and the slave side sensor goes
into key-lock state.
Reset setting
Returns to default settings (factory settings).
By pressing dowun mode key when “ ” mode, becomes default settings
(factory settings).
RUN mode
<PRO mode>
Hold down
for 4 seconds
<Sub display selection>
Display OFF
Unit display
No. display
Standard
<Display speed selection>
500ms
250ms
<Hysteresis fixed value selection> (1 level: Approx. 1 digit) (When Pa unit is selected.)
RUN mode
<Sub display selection>
When “
” is set
When “
” is set
Change the displayed
details with
Set pressure
range is displayed
on sub display.
Custom display
1,000ms
Min.
Max.
<Displayed color relation selection>
When “No. display” or “Custom display” is set in “Sub display selection.”
<External input relation selection>
<Reset setting>
RUN mode
<Eco mode setting>
OFF
Standard
Max.
<Setting check code>
<Setting copy mode>
Copy sending
OFF
Copy sending
ON
Copy sending
ON-L
Copy ready
state
Relating with
comparative
output 1
Relating with
comparative
output 2
Corresponding
to comparative
output 1
Corresponding
to comparative
output 2
Corresponding
to comparative
output 1 / 2
Automatic
Code table
●
Main display (first digit form left)
Code
1st digit
2nd digit
3rd digit
4th digit
Comparative
output 1 output
mode
N.O. / N.C.
selection
Comparative
output 2 output
mode
N.O. / N.C.
selection
Analogue
output
Threshold
display
External
input
EASY
N.O.
OFF
-
Analogue
voltage
output
Threshold
value 1
OFF
N.C.
EASY
N.O.
Threshold
value 2
AREF
Hysteresis
N.O.
N.C.
Threshold
value 3
ZERO
N.C.
Hysteresis
N.O.
Threshold
value 4
HOLD
Window
comparator
N.O.
N.C.
Analogue
current
output
Threshold
value 1
P.b.-2
N.C.
Window
comparator
N.O.
Threshold
value 2
-
-
-
N.C.
Threshold
value 3
-
-
-
-
-
Threshold
value 4
-
AREF: Auto-reference function, ZERO: Remote zero-adjust function,
HOLD: Current value hold function P.b.-2: peak / bottom hold 2 function
●
Sub-display (5th digit from left)
Code
5th digit
6th digit
7th digit
8th digit
Displayed color of
the main display
Displayed color
relation
Response time
Unit selection
(Note)
Display speed
Eco mode
Red when ON
Comparative
output 1
-
MPa
250ms
OFF
Comparative
output 2
-
kPa
std
Green when
ON
Comparative
output 1
-
kgf/cm
2
Full
Comparative
output 2
5ms
bar
500ms
OFF
Always red
Comparative
output 1
10ms
psi
std
Comparative
output 2
25ms
-
Full
Always green
Comparative
output 1
50ms
-
1,000ms
OFF
Comparative
output 2
100ms
-
std
-
-
250ms
-
Full
-
-
500ms
-
-
-
-
-
1,000ms
-
-
-
-
-
5,000ms
-
-
-
11
SETTING COPY FUNCTION
●
This can copy the settings of the master side sensor to the slave side sensor.
●
Be sure to use the setting copy function between the identical models. This
function cannot be used between different models.
●
Only one sensor can be connected on slave side with a master side sensor
for the setting copy function.
●
Do not use the setting copy function other than the following wiring, as pulsed output gener-
ates when turning the power ON after setting the master side sensor to the copy ready state.
Setting procedure
1.
Set the setting copy function of the master side sensor to “Copy sending ON
” or “Copy sending ON-L” with the pressure sensor head connected, and then
press the mode selection key so that the sensor is in copy ready state. For de-
tails, refer to
<Setting copy mode>
in “
PRO MODE
.”
2.
Turn OFF the master side sensor.
3.
Remove the pressure sensor head and connect the master side sensor with
the slave side sensor as shown below.
4.
Turn ON the master side sensor and the slave side sensor at the same time. (Note)
5.
Set contents (16-bit coded) are shown in orange on the main display of the
master side sensor and the copying starts.
6.
The same code explained above is shown in green on the main display of the slave
side sensor, and “
” is shown on the sub display (When copying is complete.)
7.
Turn OFF the power of the master side sensor and the slave side sensor and
disconnect the wire.
* If copying the setting to another sensor repeatedly, follow steps
3
to
7
.
Note: Take care that if the power is not turned on at the same time, the setting contents may not be copied.
To cancel the setting copy mode of master side sensor
1.
While the slave side sensor is disconnected, turn on the power of the master side sensor.
2.
Press the mode selection key for approx. 2 seconds.
12
AUTO-REFERENCE FUNCTION
●
The auto-reference function
corrects the set value using
the detected pressure value
during auto-reference input
as the reference pressure.
●
Using the detected pressure
value at auto-reference input
P(a) as a reference, the set
value 1’ is automatically cor-
rected to “set value 1 + P(a).”
Settable range and set pressure range after correction
●
The setting pressure range is wider than the rating pressure range so that the
auto-reference function can be handled.
If the corrected set value exceeds the set pressure range when auto-reference
input is carried out, the set value will be automatically corrected to within the set
pressure range. Thus, take care not to exceed the set pressure range.
Before auto-
reference
After auto-
reference
ON
OFF
ON
OFF
Atmospheric pressure
P (a) Set value 1 Set value 1’
Detected pressure value
at auto-reference input
Pressure
Set value 1’ after auto-reference is:
1’ = 1 + P (a)
Master side sensor
Slave side sensor
(Pink) External input
(Black) Comparative output 1
(Blue) 0V
(Brown) +V
Power
supply
Color code of cable
with connector
(Pink) External input
(Black) Comparative output 1
(Blue) 0V
(Brown) +V
5
I/O CIRCUIT DIAGRAMS
NPN output type
PNP output type
Notes: 1) When the analogue current is output, the output load resistance should be 250Ω max.
2) Take care that when the analogue current is output, 5V or more voltage generates.
3) When using the analogue voltage output, be careful to the input impedance of the connected device.
Furthermore, note that if the cable is extended, the cable resistance will cause the voltage to drop.
6
OUTPUT MODE AND OUTPUT OPERATION
●
The EASY mode, hysteresis mode or window comparator mode can be se-
lected as the output mode for comparative output 1 and comparative output
2. Refer to <
Comparative output 1 / 2 output mode setting
> in “
MENU
SETTING MODE
” for details.
EASY mode
●
ON / OFF of the comparative output is controlled in this mode.
Notes: 1) Hysteresis can be fixed in 8 steps.
Refer to <
Hysteresis fixed value selection
> in “
PRO MODE
” for setting.
2) “ ” is displayed for comparative output 1 and “
” for comparative output 2 on the sub-display.
Hysteresis mode
●
The comparative output ON / OFF state can be controlled with randomly set
hysteresis in this mode.
Notes: 1) “
” or “
” is displayed for comparative output 1 and “
” or “
” is displayed for com-
parative output 2 on the sub display.
Window comparator mode
●
In this mode, the ON or OFF state of the comparative output is controlled with
a pressure in the set range.
Notes: 1) Hysteresis can be fixed in 8 steps.
Refer to <
Hysteresis fixed value selection
> in “
PRO MODE” for setting.”
2) “
” or “
” is displayed for comparative output 1 and “
” or “
” is displayed for com-
parative output 2 on the sub display.
3) Set the interval between the Lo side and Hi side to hysteresis fixed value or more.
*1
Non-voltage contact, NPN transistor or
DC 2-wire output
High (5 to 30V DC or Open): Invalid
Low (0.4V DC or less): valid
or
*2
Non-voltage contact, PNP transistor or
DC 2-wire output
High (5 to +V DC or Open): valid
Low (0.6V DC or less): Invalid
or
Pressure
P
0
ON
OFF
Comparative
output
H (Hysteresis)
H: Hysteresis fixed (Note 1)
Pressure
Hi
Lo
ON
OFF
H (Hysteresis)
H: 1 digit or more
When using psi unit model for out-
side of Japan, it is 2 digits or more.
However, the 50MPa pressure
range model is 20 digits or more.
Comparative
output
Hi
Lo
ON
OFF
H: Hysteresis fixed (Note 1)
Pressure
Comparative
output
H (Hysteresis)
H (Hysteresis)
(Gray) Analogue
voltage / current
output (Note 1, 2, 3)
(Brown) +V
(Black) Comparative output 1
(White) Comparative output 2
(Pink) External input
(Blue) 0V
12 to 24V DC
±10%
+
-
Load
Load
(*1)
Main circuit
(Brown) +V
(Pink) External input
(Black) Comparative output 1
(White) Comparative output 2
(Gray) Analogue
voltage / current
output (Note 1, 2, 3)
(Blue) 0V
Load
Load
(*2)
Main circuit
12 to 24V DC
±10%
+
-
7
SETTING WHEN TURNING ON THE POWER
●
After turning ON the power, set pressure range of pressure sensor head con-
nected to this product. The set pressure range is memorized and the range is
displayed every time after tuning on the power. Then, move to RUN mode.
●
In case replacing sensor head or resetting it, set the pressure range again.
8
RUN MODE
Setting the threshold value
●
Refer to
<Comparative output 1 / 2 output mode setting>
in “
MENU
SETTING MODE
” for setting conditions.
●
The Sub display conducts the threshold value. Main display does not changed.
Notes: 1) If the set pressure range is exceeded, “ ” (exceeds the upper limit) or “
” (exceeds the lower
limit) will appear on the sub display. “
” will also appear if the Hi side threshold value exceeds the
Lo side threshold value when setting the “hysteresis mode / window comparator mode” threshold value.
2) Auto-reference value and remote zero-adjustment value are displayed.
For details, refer to “
AUTO-REFERENCE FUNCTION
” and “
REMOTE ZERO-ADJUSTMENT
FUNCTION.
”
3) In the dash line box is not displayed when not setting “
” or “
” in external input switch. For the
setting method, refer to<Function setting> in “
MENU SETTING MODE.
”
Zero-adjustment function
●
The zero-adjustment function forcibly sets the pressure value to “zero” when
the pressure port is opened.
Note: Even if the zero-adjustment is conducted, the analogue voltage / current output is not influenced.
Key lock function
●
The key lock function prevents key operations so that the conditions set in
each setting mode are not inadvertently changed.
<Key lock set>
<Key lock released>
Peak / bottom hold function
●
The peak / bottom hold functions display the peak value and bottom value of
the fluctuating pressure.
For detail, refer to “
PEAK / BOTTOM HOLD FUNCTION
.”
●
The peak value is displayed on the main display and the bottom value is dis-
played on the sub display.
●
the higher vacuum side indicates the peak value, while the lower vacuum side
indicates the bottom value.
<Peak / bottom hold set>
<Peak / bottom hold released>
-0.1 to 1MPa
0 to 50MPa
0 to 10MPa
0 to 3.5MPa
0 to 1MPa
Pressure range
setting
Turning ON the power
Check the set
pressure range
Resetting the
pressure range
Confirm the set
pressure range
RUN mode
The set pressure range is displayed.
Hold down
Automatic
Hold down
Automatic
Hold down
Automatic
Blinks alternately
Hold down
Hold down
Display is changed by pressing down.
Automatic
(Note 2)
Blinks alternately
Press down: increase threshold value to high pressure side.
Press down: decrease threshold value to low pressure side.
Comparative
output 1
EASY mode
(Comparative output 2 is OFF)
Hysteresis mode / Window
comparator mode
· Lo side
Hysteresis mode / Window
comparator mode
· Hi side
EASY mode
Comparative
output 2
Comparative
output 1
Comparative
output 2
Comparative
output 1
Comparative
output 2
(Note 3)
Operation chart
Note: The set values shift in the same manner during the EASY mode or the window comparator mode.
●
The detected pressure value at auto-reference input becomes “zero” when the
setting of the analogue voltage / current output selection function is changed
or the power is turned ON again.
●
The auto-reference input value can be checked when setting the threshold value
in RUN mode. Refer to “
Threshold value setting
” in “
RUN MODE
” for details.
13
REMOTE ZERO-ADJUSTMENT FUNCTION
●
The remote zero-adjustment function forcibly sets the pressure value to “zero”
when the external signal is input.
The setting value is not corrected when remote zero-adjustment is input. Make
sure that the pressure and set value during remote zero-adjustment do not exceed
the set pressure range.
Operation chart
Notes: 1) The setting values shift in the same manner during the EASY mode or the window comparator mode.
2) The remote zero-adjustment function is applicable only to the comparative output set at the external
input relation selection. Unset comparative output operates based on the atmospheric pressure.
●
The remote zero-adjustment value is cleared when the setting of the analogue
voltage / current output selection is changed or the power is turned ON again,
and normal operation based on the atmospheric pressure is resumed.
● The remote zero-adjustment value can be confirmed when setting the threshold
value in RUN mode. Refer to the threshold value setting in “
RUN MODE
”
14
CURRENT VALUE HOLD FUNCTION
●
During turning ON the external input, it display continuously current pressure value.
●
Even if holding the display, it is possible to determine output and to change
threshold value.
●
In case display is held, actual value is not displayed. be sure that impressed
pressure not exceed the specified value
.
15
PEAK / BOTTOM HOLD FUNCTION
●
In case setting peak / bottom hold 1 setting, displays peak value and bottom
value in same time after setting.
●
In case of setting peak / bottom hold 2 setting, displays both peak value and
bottom value in same time in conjunction with output.
In case power is ON (OFF), hold the display until next output is ON (OFF). the
set value in conjunction with output.
However, in case of setting window comparator, it operate as peak / bottom hold 1 setting.
●
For setting method, refer to “
Peak / bottom hold function
” in “
RUN MODE
.”
16
CAUTIONS
●
This product has been developed / produced for industrial use only.
●
Make sure that the power supply is OFF while wiring.
●
Take care that if a voltage exceeding the rated range is applied, or if an AC
power supply is directly connected, the product may get burnt or damaged.
●
Take care that wrong wiring will damage the sensor.
●
Do not run the wires together with high-voltage lines or power lines or put them
in the same raceway. This can cause malfunction due to induction.
●
If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
●
In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicin-
ity of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
●
Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.
●
Extension up to total 100m (emitter and receiver each for thru-beam type), or less,
is possible with 0.3mm
2
, or more of conductor cross-section area cable. However, to
reduce noise, make the wiring as short as possible. If using this product as complaint
model with CE Marking / UKCA Marking, the power supply line must be 30m or less.
Brinks alternately
External input ON
During normal operation
(each comparative output set to N.O.)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60
Displayed value (kPa)
1
2
10 20
Set value (kPa)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60
Displayed value (kPa)
P(a)
1
’
10 20
Set value (kPa)
2
’
30
During auto-reference input
(each comparative output set to N.O.)
• Detected pressure at auto-reference input: 10kPa
• Output mode: Hysteresis mode
During remote zero-adjustment input
(each comparative output set to N.O.)
• Detected pressure at remote zero-adjustment input: 10kPa
• Output mode: Hysteresis mode
Output
ON
OFF
0
0
10
10
20
20
30
30
40
40
50
50
60
-10
1
’
10 20
2
’
During normal operation
(each comparative output set to N.O.)
Output
ON
OFF
0
0
10
10
20
20
30
30
40
40
50
50
60
60
1
2
10 20
Applied pressure (kPa)
Displayed value (kPa)
Set value (kPa)
Applied pressure (kPa)
Displayed value (kPa)
Set value (kPa)
<
Bottom hold 2
>
ON
Bottom
value
OFF
OFF
Start
Current
value
Set
value
ON
<Peak hold 2>
Set
value
Start
ON OFF ON
ON
OFF
Peak value
Current
value
OFF
●
Make sure that stress by forcible bend or pulling is not applied directly to the
sensor cable joint.
●
This sensor is suitable for indoor use only.
●
Avoid dust, dirt, and steam.
●
Take care that the product does not come in contact with water, oil, grease, or
organic solvents, such as, thinner, etc.
●
Do not operate the keys with pointed or sharp objects.
●
Do not use this sensor in places having excessive vapor, dust, etc., or where it
may come in contact with corrosive gas, etc.
●
Never disassemble or modify the sensor.
●
This product use EEPROM. The EEPROM has lifetime and cannot set more
then 1 million times of setting.
17
ERROR INDICATION
●
When error is occurred, use the countermeasure listed blow.
Error
message
Cause
Corrective action
• The controller and the pressure sensor
head are not correctly connected.
• The pressure sensor head is damaged.
• Connect the controller and the pressure sensor
head correctly.
• Replace the pressure sensor head.
The load is short-circuited causing an over-
current to flow.
Turn the power OFF and check the load.
Pressure is applied during zero-point adjust-
ment.
Applied pressure at the pressure port should be
brought to atmospheric pressure and zero-point
adjustment should be done again.
External input is carried out outside the rated
pressure range.
Applied pressure range should be brought within
the rated pressure range.
Communication error
(Disconnection, faulty connection, etc.)
Check the wiring when using the copy function.
Communication error
(Incorrect model.)
Make sure that the system is configured of the
same models when using the copy function.
The applied pressure exceeds the upper limit
of the display pressure range.
Applied pressure range should be brought within
the rated pressure range.
The output is kept.
The applied pressure exceeds the lower limit
of the display pressure range.
When other error massage is displayed, contact us.
18
SPECIFICATIONS
Type
NPN output type
PNP output type
For inside of Japan For outside of japan For inside of Japan For outside of japan
Model No.
DPC-L101Z
DPC-L101
DPC-L101Z-P
DPC-L101-P
Applicable pressure
sensor head
DPH-L113V
,
DPH-L113
,
DPH-L133
,
DPH-L114
,
DPH-L154
Rated pressure range
-0.1 to 1MPa / 0 to 1MPa / 0 to 3.5MPa / 0 to 10MPa / 0 to 50MPa
Set pressure range
-1.177 to 1.177MPa / -1.070 to 1.070MPa / -3.74 to 3.74MPa / -10.70 to 10.70MPa /
-53.5 to 53.5MPa
Supply voltage
12 to 24V DC ±10% Ripple P-P 10% or less
Power consumption
(Note 2)
Normal operation: 960mW or less (current consumption 40mA or less at 24V supply voltage)
ECO mode (STD): 720mW or less (current consumption 30mA or less at 24V supply voltage)
ECO mode (FULL): 600mW or less (current consumption 25mA or less at 24V supply voltage)
Sensor head supply voltage
Same as supply voltage
Input
Pressure sensor
head input
Input voltage range: 1 to 5V DC (within the rated pressure range)
External input
• ON voltage: 0.4V DC or less
• OFF voltage: 5 to 30V DC or open
•
Input impedance: Approx. 10kΩ
• Input time: 1ms or more
• ON voltage: 5V to +V DC
• OFF voltage: 0.6V DC or less or open
•
Input impedance: Approx. 10kΩ
• Input time: 1ms or more
Comparative output
(Comparative output 1/2)
NPN open-collector transistor
• Maximum sink current: 50mA
• Applied voltage: 30V DC or less
(between comparative output and 0V)
• Residual voltage: 1V or less
(at 50mA sink current)
PNP open-collector transistor
• Maximum source current: 50mA
• Applied voltage: 30V DC or less
(between comparative output and +V)
• Residual voltage: 1V or less
(at 50mA source current)
Output operation
Selectable either N.O. or N.C., with key operation
Hysteresis
Minimum 1 digit
Repeatability
Within ±0.2% F.S.
Response time
5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms or 5,000ms
selectable with key operations
Analogue output
<Analogue voltage output>
• Output voltage: 1 to 5V
•
Output impedance: Approx. 1kΩ
• Zero point: Within 1V ±0.5% F.S.
(
DPH-L113V
: Within 1.364V ±0.5% F.S.)
• Span: Within 4V ±0.5% F.S.
• Linearity: Within ±0.1% F.S.
<Analogue current output>
• Output current: 4 to 20mA
•
Load resistance: 250Ω (MAX.)
• Zero point: within 4mA ±1% F.S.
(
DPH-L113V
: within 5.455mA ±1% F.S.)
• Span: Within 16mA ±1.5%F.S.
• Linearity: Within ±0.1%F.S.
Ambient temperature
-10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60ºC
Ambient humidity
35 to 85% RH, Storage: 35 to 85% RH
Material
Enclosure: PBT (with glass fiber), LCD display: Acrylic
Mounting screw section: Brass (nickel-plated), Switch: Silicon rubber
Weight
(Main body only)
Approx. 25g
Accessories
CN-66A-C2
(Cable with a connector, 2m long) (Optional for J type): 1 pc.
Unit switching label: 1 pc.
Notes: 1) The cable with connector is not enclosed with models that have “-J” at the end of the model names.
2) Excluding the current consumption of analogue output current and applying pressure sensor head.
3) The specified value is only for controller. Refer to attached instruction manual of pressure sensor head
of used as combination for specified value .
Panasonic Industry Co., Ltd.
Panasonic Industrial Devices SUNX Co., Ltd.
https://panasonic.net/id/pidsx/global
Please visit our website for inquiries and about our sales network.
Panasonic Industrial Devices SUNX Co., Ltd. 2022
September, 2022
PRINTED IN JAPAN