background image

8

(EN)

Mounting

Remove the air inlet grille.

Installation position for 
receiver (Fig. A)

Indoor unit electric 
component box

Air Inlet grille

Ceiling panel

Remove the screw fi xing the corner cover.

Screw

Corner cover

Place a hand on both the right and left convex 
parts of the corner cover to remove it.

Convex part

Ceiling panel

Corner cover

Corner cover

Hang the string of the receiver on the pin of 
the ceiling panel.

Receiver

Pin

String

Ceiling panel

Pass the wiring from the receiver section into 
the slit.
For more wiring information, see the section 
“Wiring”.

Fix the wiring with the clamper (supplied) while 
leaving enough length of wiring to remove the 
receiver.

 

●When attaching the fi lter chamber, cut the 

clamper (a), and attach the receiver.

Slit

Fix with the clamper (supplied).

(a) Cut this clamper.

Fit the receiver to the ceiling panel so the 
5 claws are properly set, and fi x it with the 
removed screw.

 

●Make sure the wire is not caught.

 

●Refer to the installation instructions supplied 

with the panel.

The receiver can be installed only on the corner shown in Fig. A. Consider the direction where the 
panel is attached to the indoor unit.

Содержание CZ-RWRU3

Страница 1: ...ecifications 5 Installation Precautions 6 Wiring 7 Mounting 8 Setting 9 Address Setting 9 Test Operation 10 Self diagnostics table and detected contents 11 Contents English Read through the Installation Instructions before you proceed with the installation In particular you will need to read under the Safety Precautions on page 3 W1121 0 ...

Страница 2: ...ction Receives signals 2 Indication lamp Indicates operation status 3 Emergency operation button Starts Stops emergency operation Supplied accessories Number of pieces Installation Instructions 1 Installation Instructions Disc 1 Clamper 1 ...

Страница 3: ...UTION This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage WARNING Turn off the circuit breaker of the units before installation This receiver shall be installed in accordance with National Wiring Regulations Connect and fix the specified cables for wiring securely Do not allow the connection to be exposed to the external force of the cab...

Страница 4: ...ak Location with lots of water or oil droplets including machine oil Location where droplets of organic solvents spread Location where acidic or alkaline solutions or special sprays are frequently used Do not wash with water Do not operate with wet hands NOTICE The English text is the original instructions Other languages are translation of the original instructions ...

Страница 5: ...tions Model No CZ RWRU3 CZ RWRU3W Dimensions H 29 7 mm W 211 8 mm D 211 8 mm Weight 160 g Temperature Humidity range 0 C to 40 C 20 to 80 No condensation Indoor use only Power Source DC16 V supplied from indoor unit ...

Страница 6: ...splay or LCD televisions Direct sunlight or other sources of bright light Do not bundle together with the power source wiring or store in the same metal tube Operation error may occur Be careful not to connect cables to other terminals of indoor units e g power source wiring terminal Malfunction may occur Avoid the following locations for installation Location where condensation occurs Location wh...

Страница 7: ...ination set the wired remote controller to Main Installation example R1 R2 1 2 CN001 R1 R2 R1 R2 R1 R2 1 2 CN001 Indoor unit Indoor unit Indoor unit Indoor unit Terminals for RC wiring RC wiring No polarity Receiver Sub Wired RC Main Receiver Sub Wired RC Main Using 1 indoor unit Using more than 1 indoor unit Note The receiver can be connected to any indoor unit for operation Multiple infrared rem...

Страница 8: ...wiring from the receiver section into the slit For more wiring information see the section Wiring 6 Fix the wiring with the clamper supplied while leaving enough length of wiring to remove the receiver When attaching the filter chamber cut the clamper a and attach the receiver Slit Fix with the clamper supplied a Cut this clamper 7 Fit the receiver to the ceiling panel so the 5 claws are properly s...

Страница 9: ...nation set the wired remote controller to Main Address Setting When more than 1 receiver is installed in the same room setting addresses prevents interference For how to change addresses of infrared remote controllers see the operating instructions of infrared remote controllers Infrared remote controller address display Address Address Address Address Address Address Address ON OFF States ALL 1 2...

Страница 10: ...N TIMER STANDBY blink during test operation 3 To finish test operation press and hold the emergency operation button for 10 seconds Attention Do not use this mode for purposes other than the test operation To prevent overload of the units Read the installation instructions supplied with the units The test operation can be performed in Heat or Cool mode Temperature cannot be changed The test operati...

Страница 11: ...eration of outdoor protection device P02 P08 P15 P31 Alternately Error in the indoor thermistor F01 F03 F10 F11 Alternately Error in the outdoor thermistor F04 F09 F12 F28 Alternately Error in the indoor EEPROM F29 Simultaneously Error in the outdoor EEPROM F30 F31 Simultaneously Error related to the compressor H01 H31 Error in indoor settings L01 L03 L05 L09 Simultaneously Error in outdoor settin...

Страница 12: ...ral household waste For proper treatment recovery and recycling of old products please take them to applicable collection points in accordance with your national legislation By disposing of them correctly you will help to save valuable resources and prevent any potential negative effects on human health and the environment For more information about collection and recycling please contact your loca...

Отзывы: