ECONAVI function
This function is available by attaching an optional ECONAVI sensor.
The ECONAVI sensor detects human activity and conserves energy based on the
activity level.
WARNING
Do not use the ECONAVI function in a room with disabled persons or infants only. Due
to their limited motions, the ECONAVI sensor may judge no person is present, causing
the indoor unit to stop the operation.
Overview of the ECONAVI function
High activity
• Cooling: Target temperature is the same as the set temperature.
• Heating: Target temperature is 1 °C lower than the set temperature.
Low activity
• Cooling: Target temperature is 1 °C higher than the set
temperature.
• Heating: Target temperature is the same as the set temperature.
No one in the room
No one in the room for 20 minutes
• Cooling: Target temperature is 2 °C higher than the set
temperature.
• Heating: Target temperature is 2 °C lower than the set temperature.
No one in the room for 3 hours*
• When no one is in the room for approx. 3 hours* or more, the unit
operates in the specified Absence operation mode.
* This depends on the type of indoor unit.
• When the sensor
detects movements in
the room which has
been empty, it will
resume operation to
match with the activity
level.