background image

14

(EN)

1

Press and hold the 3 buttons for 
4 seconds or more simultaneously.

 

2

Select [Test run].

 

 

 

3

Select [ON]. 

(The unit enters the test 

operation mode. Then, [TEST] turns on.)

 

 

 

Press 

.

4

Perform the test operation.

5

Finish the test operation.

Perform step 1 and 2, and then select [OFF] in step 3. ([TEST] display 
disappears.)

 

The test operation can be performed in Heat or Cool mode.

 

Temperature cannot be changed.

 

The test operation mode is automatically turned o

  in 60 minutes. (To prevent continuous 

test operation) 

 

Outdoor units do not operate for approx. 3 minutes after the power is turned on or 
operation is stopped.

Attention

 

Do not use this mode for purposes other than the test operation. (To prevent 
overload of the units)

 

Read the installation instructions supplied with the units.

Test Operation 

Содержание CZ-RTC5B

Страница 1: ...ns on page 3 WEB ACXF60 26852 EN H0318 20921 Panasonic Corporation http www panasonic com Contents Part Names 2 Supplied accessories 2 Safety Precautions 3 Specifications 4 Installation Precautions 5...

Страница 2: ...lluminates during operation Blinks during alarm 8 Start Stop button Starts Stops operation 3 Enter button Fixes the selected content 4 Energy saving button Switches Energy saving Normal operation Rig...

Страница 3: ...t breaker of the units before installation Ask your dealer or professionals for installation and electric work This controller shall be installed in accordance with National Wiring Regulations Connect...

Страница 4: ...ature Humidity range 0 C to 40 C 20 to 80 no condensation Indoor use only Power Source DC16 V supplied with indoor unit Clock precision 30 seconds month at normal temperature 25 C Adjust periodically...

Страница 5: ...e Remote control wiring Wiring diagram 1 2 R1 R2 Indoor unit Terminals for RC wiring RC RC wiring field supply No polarity Type of wiring Use cables of 0 5 to 1 25 mm2 Total wire length 500 m or less...

Страница 6: ...ntroller to Main and the other to Sub for Main sub for Setting P 11 When using the remote controllers in combination set this unit to Main CZ RTC2 CZ RTC4 CZ RE2C2 CZ RELC2 Using 1 indoor unit R1 R2 1...

Страница 7: ...oy the PCB 2 Mount to the wall Flat blade screwdriver Insert the driver and slightly turn Bottom case Mounting Exposed type 1 3 2 Mount the top case Align the claws of the top case and then align the...

Страница 8: ...en align the claws of the bottom case Avoid the wire being caught Claw 2 places Screw Supplied Hole for screw Claw 2 places Mount the bottom case to the wall Pass the wire through the hole in the cent...

Страница 9: ...Note To return to the previous screen Press 1 Press Controller name 2 Select Initial settings 3 Select the item to set Language 4 Set Default setting English Clock 4 Set Repeat 5 4 2018 Controller na...

Страница 10: ...s Up to 16 characters Space is included in the number of characters To change the character type Select the character type with and press To enter space Select Space with and press To delete 1 charact...

Страница 11: ...actory setting 0001 Not displayed 0002 Not displayed password Detailed settings 3 Set Select the indoor unit number Code no and Set data Repeat Indoor unit number Set data Code no 4 Press After Select...

Страница 12: ...address is set and 90 seconds or more have passed Set elec consumption 3 Set Select the power supply voltage of outdoor units 4 Select YES Note Set the power supply voltage of outdoor units to calcula...

Страница 13: ...f the remote controller indoor units and outdoor units 3 Select Select the unit number 4 Confirm the content Pressing will return to the Maintenance func screen Service check This displays the alarm h...

Страница 14: ...lay disappears The test operation can be performed in Heat or Cool mode Temperature cannot be changed The test operation mode is automatically turned o in 60 minutes To prevent continuous test operati...

Страница 15: ...Panasonic Corporation 2018 2021...

Отзывы: