Setting
1
Press and hold the 3 buttons for
4 seconds or more simultaneously.
,
,
►
2
Select the item to set.
▲
▼
→
RC. setting mode
3
Set.
(Select the Code no. and Set data.)
▲
▼
→
►
→
(Repeat)
Code no.
Set data
4
Press
After Selecting [YES], the unit restarts.
Code no
.
Set data
01
Main/sub
Set this when using 2 remote controllers.
• 0000: Sub
• 0001:
Main (factory
setting)
02
Clock type
Set the type of clock display.
• 0000: 24 hours
• 0001:
12 hours (AM/PM)
2F
Password
change
Set the administrator password.
• 0000 to 9999
• 0000 (factory setting)
36
Display of
operation lock
cancelling method
Set whether to display the operation lock cancelling method on the
lock screen while operation is locked. (For the lock screen, see the
“Part Names” section in the Operating Instructions.)
• 0000:
Displayed
(factory setting)
• 0001: Not displayed
• 0002:
Not displayed
(password)
Detailed settings
3
Set.
(Select the indoor unit number, Code no. and Set data.)
▲
▼
→
►
→
(Repeat)
Indoor unit
number
Set data
Code no.
4
Press
After Selecting [YES], the unit restarts.
Code no.
Set data
31
Vent output
setting
Set this when connecting a commercially sold fan, etc. to the ventilation
fan output “FAN DRIVE:2P (White)” on the indoor control board.
*Dedicated cables (optional) are required.
• 0000: Not connected
• 0001: Connected
32
Temp sensor
setting
Set this when measuring the room temperature with the room
temperature sensor of the remote controller.
• When using the main and sub controllers, the main one is enabled.
• When using with the remote sensor in combination, set the indoor
unit setting data.
*This setting is not available during group-controlling.
• 0000: Indoor unit
• 0001: Remote controller
33
Temp display
setting
Set the type of temperature display.
• 0000: °C
• 0001: °F
RC. setting mode
Detailed settings