Mounting Position

Secure space as shown below when mounting 2 or more 
of this controller or mounting other devices side by side.

Up, down, left and right direction: 
100 mm or more 

Front: 50 mm or more 

100 mm 

100 mm 

100 mm 

100 mm 

100 mm 

100 mm 

100 mm 

100 mm 

50 mm 

50 mm 

 

How to Mount (Control Box)

1. Attach the controller to the control box so that the 

wiring can be taken out from the left side. (See the 
illustration below.) (Screws (

fi

 eld supply): 4)

•  Tighten the screw securely.

2. Remove the upper cover. (Cover-

fi

 xing screws: 4)

 

After the connection and setting (pages 4 to back 
cover) are complete, attach the upper cover. 
(Cover-

fi

 xing screws: 4)

Screw (

fi

 eld supply)

Upper cover

Screw (

fi

 eld supply)

Control 

box

Cover-

fi

 xing screw

 

Power Supply Wiring

•  Be sure to use a dedicated line for power source.
•  Be sure to earth this controller.
•  Do not connect the earth wiring to those of gas pipe, water 

pipe, lighting rod, telephone, etc.

 

Type of wiring

• Use a 

fl

 exible wiring of 2 mm

(Recommended).

•  Use the standard power supply wiring for Europe (such as 

H05RN-F or H07RN-F which conform to CENELEC (HAR) 
rating speci

fi

 cations) or use the wiring based on IEC 

standard (60245 IEC57, 60245 IEC66). 

 

Total Wire Length 
30 m or less

 

Inter-Unit Control Wiring

 

Type of wiring

• Use a 

fl

 exible shield wiring of 0.5 to 2 mm

2

.

 

Total Wire Length
1000 m or less

 

Number of connectable units and devices
(Up to total of 100 units and devices can be 
connected.)

Indoor unit

Up to 64 units per link *

Outdoor unit

Up to 30 units per link

Central control 
device

Up to 10 units

*: The number of indoor units includes the Interface Adaptor. 

 

External I/O Wiring

 

Type of wiring

• Use a 

fl

 exible wiring of 0.5 to 2 mm

2

.

Attention

•  When using the controller at a location susceptible to 

noise, use a shield wiring.

 

Total Wire Length
20 m or less

 

LAN Cable

 

Type of wiring

•  Category 5 or above straight cable

 

Total Wire Length
100 m or less

 

Basic Wiring Diagram

U2

U1

N

L

U2

U1

U1 U2

1-1

1-2

U1 U2

U1 U2

1-1

1-2

U1 U2

U1 U2

U1 U2

L

N

Power source

100-240 V ~ 50/60 Hz

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

LAN

cable

LINK 1

Power 

suply 

wiring

Inter-unit 
control wiring

• 

No polarity

LINK 2

Mounting

Wiring

CZ-CFUSCC1̲工説̲E.indd   3

CZ-CFUSCC1̲工説̲E.indd   3

2016/02/17   15:50:20

2016/02/17   15:50:20

Содержание CZ-CFUSCC1

Страница 1: ...or death This controller is strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown Earth Leakage Circuit Breaker ELCB must be incorporated in the fixed wiring in accordance with the wiring regulations The Earth Leakage Circuit Breaker ELCB mus...

Страница 2: ...od consult the network administrator Installation Precautions Installation Location Avoid the following locations for installation Under direct sunlight Location near heat source Location where the controller will be splashed with water or affected by dampness or humidity Uneven surface Location that is subject to excessive vibration or physical impacts Fixing screws may come off and the controlle...

Страница 3: ...H05RN F or H07RN F which conform to CENELEC HAR rating specifications or use the wiring based on IEC standard 60245 IEC57 60245 IEC66 Total Wire Length 30 m or less Inter Unit Control Wiring Type of wiring Use a flexible shield wiring of 0 5 to 2 mm2 Total Wire Length 1000 m or less Number of connectable units and devices Up to total of 100 units and devices can be connected Indoor unit Up to 64 u...

Страница 4: ...oltage DC5 V 10 Contact allowable current Max 10 mA Pulse input 1 Pi1 8 Pulse input 2 Pi2 9 Pulse input 3 Pi3 10 Common COM 7 COM Pulse width 30 msec or more 100 msec or more Pulse interval 1 sec or more Connecting Wiring When connecting external equipment refer to the Connecting to external equipment section below U1 U2 0 1 2 3 4 5 6 20 U1 U2 TB1 TB2 Power supply wiring Power supply terminal boar...

Страница 5: ...tion section back cover page 5 Start up the PC and set if the network settings as follows IP address 192 168 1 100 Subnet mask 255 255 255 0 Default gateway 192 168 1 254 6 Enter the following URL in the Web browser and access the cloud adaptor https 192 168 1 1 Recommended Web browser specifications Internet Explorer IE 11 The login screen appears If the login screen does not appear Check if the ...

Страница 6: ... and the number of detected units correspond with each other If some of the indoor units are not displayed unexpected indoor units are displayed Check if wiring is properly done or the address setting for air conditioners is correct After correction redo from step 2 4 Enter the central address To assign manually Select the central address text box of the indoor unit on the A C Unit List screen and...

Страница 7: ...ctions 1 2 When DHCP is used in the network environment Add a check mark for DHCP Enabled When other than the above Remove the check mark for DHCP Enabled and enter IP address Subnet mask and Default gateway of the cloud adaptor 2 3 When the DNS server information can be automatically obtained in the current environment Add a check mark for Obtain DNS server address automatically When other than t...

Страница 8: ...Orange Red Green Lighting Blinking slow once per about 2 seconds Blinking fast once per about 1 second Off LED Status and Solution The cloud adaptor is in the maintenance mode page 7 After maintenance change it to the operation mode Communication failure Both Link 1 and 2 Check if the inter unit control wiring between the air conditioners and the cloud adaptor is correct Both Link 1 and 2 Communic...

Отзывы: