Switches
* The factory defaults are as follows.
OFF : SW1·2·3·4·8
ON :
SW5·6·7
[SW1
•
2] Zone address setting
Select a zone from Zone 1 to 4 based on the group (Central address) to operate.
[SW3] ON/OFF controller Main/Sub setting
(Main: OFF Sub: ON)
When installing one ON/OFF controller in one zone, set this to Main (OFF).
When installing two ON/OFF controllers in one zone, set one to Main (OFF) and the other to Sub (ON).
Up to two ON/OFF controllers with Main and Sub combined can be connected for each zone.
Zone 1
Group 1 to 16
⾷
SW1
⿉
OFF
Ʒ
SW2
⿉
OFF
⾸
Zone 2
Group 17 to 32
⾷
SW1
⿉
ON
Ʒ
SW2
⿉
OFF
⾸
Zone 3
Group 33 to 48
⾷
SW1
⿉
OFF
Ʒ
SW2
⿉
ON
⾸
Zone 4
Group 49 to 64
⾷
SW1
⿉
ON
Ʒ
SW2
⿉
ON
⾸
Switches
⾷
SW1
ɿ
2
ɿ
3
⾸
ON/OFF controller Main/Sub
Main (SW3 OFF) Sub (SW3 ON)
OFF OFF OFF
OFF OFF ON
ON OFF OFF
ON OFF ON
OFF ON OFF
OFF ON ON
ON ON OFF
ON ON ON
[SW4] Central control Main/Sub setting
(Main: OFF Sub: ON)
When using only one ON/OFF controller, set this to
Main (OFF).
When using this unit in combination with other central
control devices such as an intelligent controller or a system
controller, setting this unit to Sub (ON) is recommended.
Note that when using
“[SW5•6•7] Prohibition setting”
,
set this to Main (OFF).
When using more than one ON/OFF controllers in a
condition other than
, set one unit to Main (OFF) and
the others to Sub (ON).
[SW5
•
6
•
7] Remote control prohibition setting
The remote control operations (operation/stop) are
prohibited for groups for which the prohibition setting is
made. This can be used when
“[SW4] Switching Main/
Sub setting of the central control”
is set to Main (OFF).
[SW8] ALL ON/ALL OFF target group setting
Sets the target to operate/stop when the “ALL ON” or “ALL
OFF” button is pressed.
1 Set this to OFF when all the groups in the zone selected
for “[SW1•2] Zone address setting” are targeted.
2 Set this to ON when only groups for which the prohibition
setting is made are targeted.
Group 1 to 16 : Permitted
Group 1 to 16
⿉
Prohibited
Group 1 to 4
⿉
Permitted
Group 5 to 16
⿉
Prohibited
Group 1 to 8
⿉
Permitted
Group 9 to 16
⿉
Prohibited
Switches
⾷
SW5
ɿ
6
ɿ
7
⾸
Group 1 to 12
⿉
Permitted
Group 13 to 16
⿉
Prohibited
Prohibition setting disabled
ON OFF OFF
OFF OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON ON ON
ENGLISH