11

(EN)

Switches

* The factory defaults are as follows.

OFF : SW1·2·3·4·8
ON : 

SW5·6·7

[SW1

2] Zone address setting

Select a zone from Zone 1 to 4 based on the group (Central address) to operate.

[SW3] ON/OFF controller Main/Sub setting 

(Main: OFF   Sub: ON)

 When installing one ON/OFF controller in one zone, set this to Main (OFF).

  When installing two ON/OFF controllers in one zone, set one to Main (OFF) and the other to Sub (ON).

 

Up to two ON/OFF controllers with Main and Sub combined can be connected for each zone.

Zone 1
Group 1 to 16

SW1

OFF

Ʒ

SW2

OFF

Zone 2
Group 17 to 32

SW1

ON

Ʒ

SW2

OFF

Zone 3
Group 33 to 48

SW1

OFF

Ʒ

SW2

ON

Zone 4
Group 49 to 64

SW1

ON

Ʒ

SW2

ON

Switches

SW1

ɿ

2

ɿ

3

ON/OFF controller Main/Sub

Main (SW3 OFF) Sub (SW3 ON)

OFF OFF OFF

OFF OFF ON

ON OFF OFF

ON OFF ON

OFF ON OFF

OFF ON ON

ON ON OFF

ON ON ON

[SW4] Central control Main/Sub setting 

(Main: OFF   Sub: ON)

  When using only one ON/OFF controller, set this to 

Main (OFF).

  When using this unit in combination with other central 

control devices such as an intelligent controller or a system 
controller, setting this unit to Sub (ON) is recommended.
Note that when using 

“[SW5•6•7] Prohibition setting”

set this to Main (OFF).

  When using more than one ON/OFF controllers in a 

condition other than 

, set one unit to Main (OFF) and 

the others to Sub (ON).

[SW5

6

7] Remote control prohibition setting

The remote control operations (operation/stop) are 
prohibited for groups for which the prohibition setting is 
made. This can be used when 

“[SW4] Switching Main/

Sub setting of the central control”

 is set to Main (OFF).

[SW8] ALL ON/ALL OFF target group setting

Sets the target to operate/stop when the “ALL ON” or “ALL 
OFF” button is pressed.
1  Set this to OFF when all the groups in the zone selected 

for “[SW1•2] Zone address setting” are targeted.

2  Set this to ON when only groups for which the prohibition 

setting is made are targeted.

Group 1 to 16 : Permitted

Group 1 to 16

Prohibited

Group 1 to 4

Permitted

Group 5 to 16

Prohibited

Group 1 to 8

Permitted

Group 9 to 16

Prohibited

Switches

SW5

ɿ

6

ɿ

7

Group 1 to 12

Permitted

Group 13 to 16

Prohibited

Prohibition setting disabled

ON OFF OFF

OFF OFF OFF

OFF ON OFF

ON ON OFF

OFF OFF ON

ON ON ON

ENGLISH

業務用リモコン̲CZ-ANC3据付書̲En.indd   11

業務用リモコン̲CZ-ANC3据付書̲En.indd   11

2017/05/17   14:36:55

2017/05/17   14:36:55

Содержание CZ-ANC3

Страница 1: ...et de installatie U moet in het bijzonder de Veiligheidsvoorschriften op pagina 62 lezen PORTUGUÊS 74 85 Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação Em particular é necessário ler as informações na secção Precauções de segurança na página 74 TÜRKÇE 86 97 Kuruluma başlamadan önce Kurulum Talimatlarını baştan sona okuyun Özellikle 86 sayfadaki Güvenlik Önleml...

Страница 2: ...iring Regulations After the installation is complete perform test operation to confirm that no abnormality is present Read the installation instructions of devices to be connected as well When relocating or repairing this controller provide the Installation Instructions to the servicing personnel WARNING ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTR...

Страница 3: ...intenance This product must not be modified or disassembled under any circumstances Modified or disassembled controller may cause fire electric shock or injury Do not clean inside the controller by users Engage authorized dealer or specialist for cleaning Do not operate with wet hands CAUTION Ground yourself to discharge static electricity before performing any wiring Do not use the controller at ...

Страница 4: ...er of connected indoor units Up to 16 groups 64 units Specifications Supplied accessories Operating Instructions 1 Installation Instructions 1 Switch name label 1 Switch box 1 Machine Screw M4 25 2 For Switch Box Wiring are not included field supplied item Safety Precautions 2 Specifications 4 Supplied accessories 4 Dimensions 5 Installation Precautions 5 Wiring 6 Mounting 10 Switches 11 Test Oper...

Страница 5: ... more on top and bottom General precautions on wiring Regulations on wire diameters differ from locality to locality For field wiring rules please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations Use the field supplied wiring with at least 1 mm in thickness of insulation part including the sheath Connect all wi...

Страница 6: ...nnectable units and devices Up to total of 100 units and devices can be connected Indoor unit Up to 64 units 1 Outdoor unit Up to 30 units Central control device Up to 10 units 1 The number of indoor units includes the interface adaptor External I O wiring Type of wiring Use a flexible wiring of 0 5 to 2 mm2 Total Wire Length 100 m or less Attention When using the controller at a location suscepti...

Страница 7: ...eld mesh Basic wiring diagram Connect the inter unit control wiring as shown in the figure When connecting interface adaptor read the installation instructions supplied with each product Outdoor unit Indoor unit L N FG N L T1 T2 U2 U1 U2 U1 U2 U1 U2 U1 Power Source 100 240V Inter unit control wiring No polarity ON OFF Controller Schedule Timer Ground Ground 1 1 1 2 Outdoor unit Indoor unit Indoor ...

Страница 8: ...ce cover The earth wiring for protection should be longer than the power line L N Power supply wiring L N 100 240V Power supply terminal board Signal terminal board U1 U2 Inter unit control wiring LINK Use this screw when connecting the shield for the inter unit control wiring to ground FG Functional Ground Note There is no polarity for the inter unit control wiring Attention Do not run the Inter ...

Страница 9: ...urrent Max 0 5 A Minimum application load DC5 V 1 mA Contact input output terminal Digital input All stop Voltage contact a Pulse When all stop input is ON the stop signal is sent periodically Pulse width 300 msec or more All operation Voltage contact a Pulse Pulse width 300 msec or more Contact allowable voltage DC24 V 10 Contact allowable current Max 10 mA All stop input Di 1 Input 1 Output DC24...

Страница 10: ...anel Connector Remove the connector Connect the connector 2 Mount to the switch box Insert the controller to the switch box supplied that has been embedded in the wall Mount the bottom case with the power supply part attached of the controller to the switch box with small screws supplied Do not allow the connection to be exposed to the external force of wiring Switch Box supplied Bottom case with ...

Страница 11: ...evices such as an intelligent controller or a system controller setting this unit to Sub ON is recommended Note that when using SW5 6 7 Prohibition setting set this to Main OFF When using more than one ON OFF controllers in a condition other than set one unit to Main OFF and the others to Sub ON SW5 6 7 Remote control prohibition setting The remote control operations operation stop are prohibited ...

Страница 12: ...the following 1 If all the buttons from 1 to 16 are blinking fast at 0 2 second intervals This unit is not recognising indoor units Check if the indoor units are turned on Check if the central address is correctly set Check if the inter unit control wiring is short circuited or disconnected at some location 2 If the buttons blink fast at 0 2 second intervals for 15 seconds after this unit is opera...

Страница 13: ...ess for each group Set the central address according to the following procedure Turn on this unit again after the setting is complete Setting from wired remote controllers CZ RTC4 Make the setting while stopped 1 Press and hold the 2 buttons for several simultaneously A 2 3 1 2 Select the Code no 03 3 Select the Set data The indicator illuminates after blinking Press Setting from wired remote cont...

Страница 14: ... Panasonic Corporation 2017 Printed in Japan Authorized representative in EU Panasonic Testing Centre Panasonic Marketing Europe GmbH Winsbergring 15 22525 Hamburg Germany ...

Отзывы: