13.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Electric current during operation
Insufficient refrigerant (gas
leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
•
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.1.2. Diagnosis methods of a malfunction of a compressor
Nature of fault
Symptom
•
Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
•
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
•
The difference between high pressure and low pressure becomes almost zero.
•
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
•
The compressor has a humming sound.
61
CS-V7CKP CU-V7CKP5 / CS-V9CKP CU-V9CKP5 / CS-V12CKP CU-V12CKP5
Содержание CU-V7CKP5
Страница 12: ...4 Dimensions 12 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 13: ...13 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 14: ...5 Refrigeration Cycle Diagram 14 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 15: ...6 Block Diagram 15 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 63: ...63 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 64: ...64 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 72: ...72 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...
Страница 74: ...19 1 REMOTE CONTROL 74 CS V7CKP CU V7CKP5 CS V9CKP CU V9CKP5 CS V12CKP CU V12CKP5...