13.5 Cooling Overload Control (Cool)
This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooling
operation.
Comp stop
Comp freq
restricted
140°F
134.6°C
Comp freq
free
147.2°F
OD Pipe
temp
13.6 Heating Overload Control (Heat)
This control detect indoor pipe temperature and perform the compressor frequency restriction during heating
operation.
Comp stop
Comp freq
restricted
127.4°F
Comp freq
free
140°F
ID Pipe
temp
118.4°F
Comp freq
maintain
This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation.
RPM controlled
53.6°F
50°F
RPM free
OD temp
13.7 Extreme Low Temperature Compressor Low Pressure Protection
Control (Heat)
This control is to prevent low pressure drops too low during extremely low outdoor ambient temperature to
improve the compressor reliability.
During heating operation, when outdoor ambient temperature is in Zone 1, this control will be activated.
Compressor frequency restriction will be based on outdoor piping temperature.
Zone 0
23°F
26.6°F
Zone 1
OD temp
Comp freq
free
Comp freq
restricted
Comp freq
stop
-9.4°F
-5.8°F
-14.8°F
-11.2°F
OD pipe