10. Installation
Instruction
IMPORTANT
This product has been designed and manufactured to meet ENERGY STAR
®
criteria for energy efficiency when
matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to
achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging
and air flow instructions.
Failure to confirm proper charge and airflow may reduce energy efficiency and
shorten equipment life.
10.1 Accessories Supplied with Outdoor Unit
The following parts are supplied as accessories with each outdoor unit.
Check that all accessory parts are present before installing the outdoor unit.
HEAT PUMP-TYPES ONLY
Part name
Qty.
Diagram
Application
Drain elbow
1
For connecting the drain pipe
10.2 Cutting and Flaring the Piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
Reamer
2. To remove burrs
Point down
Pipe
1. To cut
Bar
0 –
1
/
32
"
(0-0.5 mm)
Copper pipe
When properly fl ared, the internal surface
of the fl are will evenly shine and be of
even thickness. Since the flare part
comes into contact with the connections,
carefully check the fl are fi nish.
Improper fl aring
Inclined Surface
damaged
Cracked Uneven
thickness
3. To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle