17.4.17 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
To maintain DC voltage level supply to power transistor.
To detect high DC voltage level after rectification.
Malfunction Caused
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level.
When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF
relay RY-C.
Troubleshooting
When abnormality indication starts again.
Reset the error code and turn on the unit again.
Is AC power supply normal fluctuation?
Verify PFC abnormality by measuring DC voltage between
DCP(+) and DCN(-) at the capacitor PCB.
Is the DC voltage between DCP(+) and DCN(-) normal?
Check the reactor impedance.
Is the impedence of the reactor low?
Is the DC voltage between CN-FM1 and 4 of the outdoor fan
motor normal?
Are the compressor’s winding resistance (U-V, V-W, U-W)
uniform?
Confirm the DC voltage between CN-FM 1 and 4 when
compressor is running. Normal voltage range should be
between 265-325Vdc.
NO
YES
YES
YES
NO (391.2Vdc ~ 425Vdc)
●
AC power supply abnormal surge.
YES (~280Vdc)
●
Defect in PFC circuitry.
●
Replace the outdoor unit PCB.
NO
●
Defect in outdoor fan motor.
●
Replace outdoor fan motor.
NO
●
Defect in compressor.
●
Replace compressor.
●
Defect in reactor.
●
Replace reactor.
For safety reason and to prevent
component breakdown, always
switch off the power before remove
and connect the component.
Check the compressor winding resistance:
●
Turn off the power and disconnect the harnesses U, V,
and W.
●
Measure the winding resistance between U-V, V-W, and
W-U.