5 Function & Options list:
Note: The functions described in the table may not be applicable to the model and may subject to change without
further notice.
Function
Options Remark
No Name
Zone 1
1
Remote control number selection
A, B, C, D
2
Solar radiation sensitivity level adjustment
1, 2, 3, 4, 5
3
[iAUTO-X/iAUTO/iCOMF, Cool & Dry] mode set temperature [Low2]
selection
16°C ~ [High2]
4
[iAUTO-X/iAUTO/iCOMF, Cool & Dry] mode set temperature [High2]
selection
[Low2] ~ 30°C
5
Heat mode set temperature Low1 selection
16°C ~ [High1]
6
Heat mode set temperature High1 selection
[Low1] ~ 30°C
7
Filter cleaning disable/enable selection
00 / 01
8
nanoe-G default ON disable/enable selection
00 / 01
9
Dust sensor monitoring & LED disable/enable selection
00 / 01
10
Auto restart disable/enable selection
00 / 01
11
Dust sensor sensitivity level adjustment
1, 2, 3
12 ~ 49 Reserve
Zone 2
50
ECO demo ON
None (No display)
51
Light sensor check
None (No display)
52
nanoe-G / ECO sensor check
None (No display)
53
DOA check
None (No display)
54
Odor cut control selection [Enable (01) / Disable (00)]
00 / 01
55
Frequency tolerance selection [±3Hz (03) / ±7Hz (07)]
03 / 07
56
Fixed fan speed selection during heat mode compressor OFF
[Enable (01) / Disable (00)]
00/01
57
nanoe check
None (No display)
58
Heat mode thermo shift adjustment
-3°C ~ 3°C
59
Others (Cool & Dry) mode thermo shift adjustment
-3°C ~ 3°C
60
Deice start determination judgment temperature switching
[Yes (01) / No (00)]
00/01
61
Cool mode disable selection [Yes (01) / No (00)]
00/01
62
Heat mode disable selection [Yes (01) / No (00)]
00/01
63
Base pan heater selection [Base pan A (A) / Base pan B (b)]
A / b
64
Disable fan speed reduction during cool mode thermo-Off
[Yes (01) / No (00)]
00/01
65
LED smart OFF selection
00 – Disable /
01 – Enable
66
nanoe-G ON/OFF duration selection
01 – Pattern 1 /
02 – Pattern 2 /
03 – Pattern 3 /
04 – Pattern 4
67
Operation OFF deice function selection
00 – Disable /
01 – Enable
68
Compressor frequency change speed selection
01 – Pattern 1 /
02 – Pattern 2 /
03 – Pattern 3
69
Up/Down air swing upper limit restriction
00 – Disable
01 – Enable
70
Failure diagnosis mode disable
None (No display)
71
Compressor Fhmax setting selection
01 – Offset 1 /
02 – Offset 2 /
03 – Offset 3
72 ~ 99 Reserve