52
12. Protection
Control
12.1 Restart Control (Time Delay Safety Control)
The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
12.2 30 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
12.3 Total Running Current Control
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3
minutes.
Model YS9**
YS12**
YS18**
YS22**
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling / Soft Dry (A)
5.5
15.0
6.8
15.0
10.4
14.8
11.1
19.0
Cooling / Soft Dry (B)
5.0
15.0
6.3
15.0
9.3
14.8
10.6
19.0
The first 30 minutes of cooling operation, (A) will be applied.
12.4 IPM (Power Transistor) Prevention Control
Overheating Prevention Control
o
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
DC Peak Current Control
o
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
o
If the set value exceeds again more than 30 seconds after the compressor starts, the operation will restart
after 2 minutes.
o
If the set value exceeds again within 30 seconds after the compressor starts, the operation will restart after 1
minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off.
(B)
(A)
Outdoor air temperature
38.5°C
37.5°C
Содержание CS-YS12MKV-7
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 13: ...13 4 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 14: ...14 4 2 Outdoor Unit 4 2 1 CU YS9MKV 7 4 2 2 CU YS12MKV 7 CU YS18MKV 7 ...
Страница 15: ...15 4 2 3 CU YS22MKV 7 ...
Страница 16: ...16 5 Refrigeration Cycle Diagram 5 1 CS YS9MKV 7 CU YS9MKV 7 CS YS12MKV 7 CU YS12MKV 7 ...
Страница 17: ...17 5 2 CS YS18MKV 7 CU YS18MKV 7 CS YS22MKV 7 CU YS22MKV 7 ...
Страница 18: ...18 6 Block Diagram 6 1 CS YS9MKV 7 CU YS9MKV 7 ...
Страница 19: ...19 6 2 CS YS12MKV 7 CU YS12MKV 7 ...
Страница 20: ...20 6 3 CS YS18MKV 7 CU YS18MKV 7 ...
Страница 21: ...21 6 4 CS YS22MKV 7 CU YS22MKV 7 ...
Страница 22: ...22 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 23: ...23 7 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 28: ...28 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 29: ...29 8 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 30: ...30 8 2 Outdoor Unit 8 2 1 CU YS9MKV 7 ...
Страница 31: ...31 8 2 2 CU YS12MKV 7 ...
Страница 32: ...32 8 2 3 CU YS18MKV 7 ...
Страница 33: ...33 8 2 4 CU YS22MKV 7 ...
Страница 34: ...34 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 36: ...36 9 1 3 Indicator Printed Circuit Board ...
Страница 37: ...37 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU YS9MKV 7 ...
Страница 38: ...38 9 2 1 2 CU YS12MKV 7 ...
Страница 39: ...39 9 2 1 3 CU YS18 22MKV 7 ...
Страница 43: ...43 This can be used for left rear piping and bottom piping also ...
Страница 87: ...87 15 2 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 ...
Страница 89: ...89 Figure 20 Figure 21 Figure 22 ...