49
11.2 Indoor Fan Motor Operation
11.2.1 Basic Rotation Speed
Manual
Fan
Speed
o
Fan motor’s number of rotation is determined according to remote control setting.
Remote control
○
○
○
○
○
Tab Hi
Me+
Me
Me-
Lo
Auto Fan Speed
o
According to room temperature and setting temperature, indoor fan speed is determined automatically.
o
The indoor fan will operate according to pattern below.
Fan
Speed
a b c d e f g h a b
Higher
Medium
Lower
[1
pattern
:
10s]
Feedback
control
o
Immediately after the fan motor is started, feedback control is performed once every second.
o
During fan motor on, if fan motor feedback
≥
2550 rpm or <50 rpm continuously for 10 seconds, the fan
motor error counter increased; fan motor is then stopped and restarted. If the fan motor error counter
increased to 7, then H19 – fan motor error is detected. Operation stopped and could not be restarted.
11.3 Outdoor Fan Motor Operation
Outdoor fan motor is operated with one fan speed only. Outdoor fan turns on when compressor starts to operate. But
outdoor fan will turns off 30 seconds after compressor stops to operate.
ON
ON
Compressor
OFF
ON
Fan
Speed
ON
Outdoor Fan
30 sec
OFF
Содержание CS-YS12MKV-7
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 13: ...13 4 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 14: ...14 4 2 Outdoor Unit 4 2 1 CU YS9MKV 7 4 2 2 CU YS12MKV 7 CU YS18MKV 7 ...
Страница 15: ...15 4 2 3 CU YS22MKV 7 ...
Страница 16: ...16 5 Refrigeration Cycle Diagram 5 1 CS YS9MKV 7 CU YS9MKV 7 CS YS12MKV 7 CU YS12MKV 7 ...
Страница 17: ...17 5 2 CS YS18MKV 7 CU YS18MKV 7 CS YS22MKV 7 CU YS22MKV 7 ...
Страница 18: ...18 6 Block Diagram 6 1 CS YS9MKV 7 CU YS9MKV 7 ...
Страница 19: ...19 6 2 CS YS12MKV 7 CU YS12MKV 7 ...
Страница 20: ...20 6 3 CS YS18MKV 7 CU YS18MKV 7 ...
Страница 21: ...21 6 4 CS YS22MKV 7 CU YS22MKV 7 ...
Страница 22: ...22 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 23: ...23 7 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 28: ...28 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS YS9MKV 7 CS YS12MKV 7 ...
Страница 29: ...29 8 1 2 CS YS18MKV 7 CS YS22MKV 7 ...
Страница 30: ...30 8 2 Outdoor Unit 8 2 1 CU YS9MKV 7 ...
Страница 31: ...31 8 2 2 CU YS12MKV 7 ...
Страница 32: ...32 8 2 3 CU YS18MKV 7 ...
Страница 33: ...33 8 2 4 CU YS22MKV 7 ...
Страница 34: ...34 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 36: ...36 9 1 3 Indicator Printed Circuit Board ...
Страница 37: ...37 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU YS9MKV 7 ...
Страница 38: ...38 9 2 1 2 CU YS12MKV 7 ...
Страница 39: ...39 9 2 1 3 CU YS18 22MKV 7 ...
Страница 43: ...43 This can be used for left rear piping and bottom piping also ...
Страница 87: ...87 15 2 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 ...
Страница 89: ...89 Figure 20 Figure 21 Figure 22 ...