9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of diff erent 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept upright. 

 

- Ensure that the refrigeration system is 

earthed prior to charging the system with 
refrigerant. 

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over fi ll 

the refrigeration system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant.To avoid fi re 
or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
reclaimed refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 

that: 

• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d) Pump down refrigerant system, if possible.

e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate 

in accordance with manufacturer’s 
instructions.

h) Do not over fi ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been fi lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off .

k) Recovered refrigerant shall not be charged 

into another refrigeration system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.To avoid fi re or 
explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains fl ammable 
refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off  valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

 Safety precautions

ACXF55-17630_YZ0218-0.indb   28

ACXF55-17630_YZ0218-0.indb   28

1/9/2018   2:24:54 PM

1/9/2018   2:24:54 PM

Содержание CS-XU9UKH-8

Страница 1: ...s ng b i ng i l p t tr c khi l p t i u khi n t xa c ng g i c ng v i d n l nh v c g b b i ng i l p t tr c khi l p t Operating Instructions Air Conditioner 20 37 Before operating the unit please read t...

Страница 2: ...ng 5 gi y hi n th th i gian theo 12 gi am pm ho c 24 gi 2 X c nh n SET S d ng i u khi n trong kho ng 8 m t t nh t i u khi n n thi t b 2 t i u khi n n thi t b AIR CONDITIONER ON OFF SET TIMER CANCEL O...

Страница 3: ...t mong mu n L n Xu ng TEMP D i nhi t l a ch n 16 0 C 30 0 C 60 F 86 F Nh n v gi n t trong kho ng 10 gi y chuy n n v nhi t t C ho c F C m n b n l a ch n M y i u h a kh ng kh Panasonic Ti ng Vi t N i du...

Страница 4: ...t v x l kh ng ng c th g y r ga i n gi t ch y n Vui l ng ki m tra l i v i i l y quy n ho c chuy n gia v lo i ch t l nh s d ng Vi c s d ng c c lo i ch t l m l nh kh c c th l m h ng s n ph m ch y n ho c...

Страница 5: ...ng Kh ng t c c thi t b d ch y tr c ng gi th i ra tr nh ch y n Kh ng gi l nh th i tr c ti p v o c y c nh hay v t nu i tr nh g y th ng t ch ho c h h i Kh ng ch m v o c nh s c c a l nh m c nh s c c th g...

Страница 6: ...g T ng t khi b o qu n ng ng c n b c k n u h b ng k p d y bu c b o qu n R32 gi ng nh b o qu n R410A Vi c v n h nh b o d ng s a ch a v ph c h i m i ch t l m l nh ph i c ti n h nh b i c c nh n vi n c o t...

Страница 7: ...n ngh c a nh s n xu t 2 2 Ti n h nh c ng vi c Tr c khi ti n h nh l m vi c tr n c c h th ng ch a m i ch t l m l nh d ch y c n tri n khai c ng t c ki m tra an to n m b o r ng m i r i ro ch y m c th p n...

Страница 8: ...i ch t l m l nh tr khi c c b ph n n y c ch t o t v t li u v n c kh n ng ch ng n m n ho c c b o v c bi t ch ng l i t c nh n n m n 2 8 Ki m tra c c thi t b i n Vi c s a ch a v b o tr c c thi t b i n ph...

Страница 9: ...n x c nh n t l kh ga ph h p t i a l 25 Ch t l ng ph t hi n r r ph i ph h p v i h u h t c c m i ch t l m l nh c d ng nh ng n n tr nh s d ng c c ch t t y r a c ch a Clo b i nguy n t n y c th ph n ng v i...

Страница 10: ...ng 24 24 thi t b v xi lanh d ng thu m i ch t ph i p ng m i ti u chu n theo quy nh d N u c th b m v i h th ng ch t l m l nh e N u kh ng th t o ra kho ng ch n kh ng c n l p i l p l i c c ho t ng tr n c...

Страница 11: ...o ki n t v n c a nh s n xu t M i ch t c thu h i s c g i l i cho nh cung c p sau khi c ng trong c c xi lanh ph h p v d n nh n Ch V n chuy n R c th i li n quan Kh ng l n c c m i ch t trong c c thi t b...

Страница 12: ...h p n y t c c a c nh o gi v qu t s ho t ng theo c i t c a i u khi n t xa N u m t i n khi m y ang ch y ch s c ph c h i ngay khi c i n tr l i ch AUTO T NG t c qu t s c t ng i u ch nh theo ch ho t ng N...

Страница 13: ...h c nhau M y ki m so t nhi t d a theo nhi t ph ng t ng t c l m m t ph ng Sau t i a 4 gi nhi t s c t theo l n thi t l p cu i c ng T c qu t c c nh AUTO nghi m c m l a ch n t c qu t Trong khi m y t t nh...

Страница 14: ...i nhi t khuy n c o ti t ki m i n COOL 26 0 C 28 0 C 79 F 82 F H ng gi ch COOL DRY L M L NH H T M N u l ch AUTO T NG c nh o gi s chuy n ng theo h ng tr i ph i v l n xu ng m t c ch t ng ch i AUTO X N u...

Страница 15: ...g 1 l n b i c c i l y quy n Kh i ngo i tr i D n s ch r c xung quanh m y L m s ch ng d n n c L i l c kh 2 tu n m t l n R a tr ng l i l c nh nh ng tr nh l m h b m t l i l c Ph i kh l i l c trong b ng r...

Страница 16: ...m u m t s linh ki n b ng nh a S b c m u t y thu c v o v t li u c s d ng trong c c linh ki n b ng nh a s b b c m u nhanh h n khi ti p x c v i nhi t nh s ng m t tr i tia c c t m ho c y u t m i tr ng B i...

Страница 17: ...gi v o v c a gi ra nh d i y c ngh a l m y ho t ng b nh th ng COOL 8 C 14 4 F M y s kh ng c s d ng trong m t th i gian d i K ch ho t ch c n ng nanoe TECHNOLOGY trong 2 3 gi nh m t c ch lo i tr m c n s...

Страница 18: ...trong nh ngo i tr i kh ng k t n i v i nhau H 34 C m bi n nhi t b l m m t kh i ngo i tr i c v n H 35 D ng i n ng c chi u c a kh i trong ngo i tr i c v n H 36 C m bi n nhi t ng d n gas kh i ngo i tr i c...

Страница 19: ...t h p v i m t k hi u h a h c Trong tr ng h p n y n tu n th c c quy nh c li n quan v h a ch t WARNING Bi u t ng n y cho bi t thi t b d ng m i ch t l m l nh d ch y N u m i ch t l m l nh b r r c ng l c...

Страница 20: ...roximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Con rm SET Use remote control within 8 m from the remote control receiver of the indoor unit 20 control receiver of the indoo...

Страница 21: ...Up Down TEMP Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for approximately 10 seconds to switch the temperature indication in C or F Thank you for purchasing Panasonic Air Conditioner The...

Страница 22: ...g will cause leakage electric shock or re Con rm with authorised dealer or specialist on usage of any speci ed refrigerant type Using refrigerant type other than the speci ed may cause product damage...

Страница 23: ...lity deterioration etc Do not use any combustible equipment in front of the air ow outlet to avoid re propagation Do not expose plants or pet directly to air ow to avoid injury etc Do not touch the sh...

Страница 24: ...ping securely seal the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certi ed personn...

Страница 25: ...on competent in the use of ammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior to beginning work on systems containing ammable refrigerants safety...

Страница 26: ...ly resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks...

Страница 27: ...ge of gas 25 maximum is con rmed Leak detection uids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refri...

Страница 28: ...standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is sit...

Страница 29: ...release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not...

Страница 30: ...ap and fan speed will operate based on remote control setting If power failure occurs during this operation this operation will be resumes immediately after power resumes For AUTO the indoor fan speed...

Страница 31: ...temperature according to room temperature to accelerate room cooling After max 4 hours the set temperature follows the last set temperature setting Fan speed is xed at AUTO fan speed selection is proh...

Страница 32: ...unit within the recommended temperature range may save energy COOL 26 0 C 28 0 C 79 F 82 F Air ow direction In COOL DRY mode If AUTO is set the ap swings left right and up down automatically In i AUTO...

Страница 33: ...Outdoor unit Clear debris that surround the unit Clear any blockage from drain pipe Air lters Once every 2 weeks Wash rinse the lters gently with water to avoid damage to the lter surface Dry the lte...

Страница 34: ...at higher speed to boost cooling performance during initial operation Discoloration of some plastic parts Discoloration is subject to material types used in plastic parts accelerated when exposed to h...

Страница 35: ...l to have the following temperature di erence between the air inlet and outlet vents COOL 8 C 14 4 F The units are not going to be used for a long period of time Activate nanoe TECHNOLOGY mode for 2 3...

Страница 36: ...ure sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor ou...

Страница 37: ...complies with the requirement set by the Directive for the chemical involved Troubleshooting Information WARNING This symbol shows that this equipment uses a ammable refrigerant If the refrigerant is...

Страница 38: ...Memo ACXF55 17630_YZ0218 0 indb 38 ACXF55 17630_YZ0218 0 indb 38 1 9 2018 2 24 58 PM 1 9 2018 2 24 58 PM...

Страница 39: ...Memo ACXF55 17630_YZ0218 0 indb 39 ACXF55 17630_YZ0218 0 indb 39 1 9 2018 2 24 58 PM 1 9 2018 2 24 58 PM...

Страница 40: ...Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2018 ACXF55 17630 YZ0218 0 ACXF55 17630_YZ0218 0 indb 40 ACXF55 17630_YZ0218 0 indb 40 1 9 2018 2...

Отзывы: