Safety precautions

1. Installation (Space)

• Product with fl ammable refrigerants, shall not 

be installed in an unventilated space, if that 
space is smaller than Amin (m²).

• In case of fi eld charge, the eff ect on 

refrigerant charge caused by the diff erent pipe 
length has to be quantifi ed, measured and 
labelled.

• Must ensure the installation of pipe-work shall 

be kept to a minimum. Avoid use dented pipe 
and do not allow acute bending.

• Must ensure that pipe-work shall be protected 

from physical damage.

• Must comply with national gas regulations, 

state municipal rules and legislation. Notify 
relevant authorities in accordance with all 
applicable regulations.

• Must ensure mechanical connections be 

accessible for maintenance purposes.

• In cases that require mechanical ventilation, 

ventilation openings shall be kept clear of 
obstruction.

• When disposal of the product, do follow to the 

precautions in #12 and comply with national 
regulations.
Always contact to local municipal offi  ces for 
proper handling.

2. Servicing
2-1. Service personnel

• The system is inspected, regularly supervised 

and maintained by a trained and certifi ed 
service personnel who is employed by the 
person user or party responsible.

• Ensure the actual refrigerant charge size is in 

accordance with the room size within which 
the refrigerant containing parts are installed.

• Ensure refrigerant charge not to leak.
• Any qualifi ed person who is involved with 

working on or breaking into a refrigerant 
circuit should hold a current valid certifi cate 
from an industry-accredited assessment 
authority, which authorizes their competence 
to handle refrigerants safely in accordance 
with an industry recognised assessment 
specifi cation.

• Servicing shall only be performed 

as recommended by the equipment 
manufacturer. Maintenance and repair 
requiring the assistance of other skilled 
personnel shall be carried out under the 
supervision of the person competent in the 
use of fl ammable refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

2-2. Work

• Prior to beginning work on systems containing 

fl ammable refrigerants, safety checks are 
necessary to ensure that the risk of ignition 
is minimised. For repair to the refrigerating 
system, the precautions in #2-2 to #2-8 must 
be followed before conducting work on the 
system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 
fl ammable gas or vapour being present while 
the work is being performed.

• All maintenance staff  and others working 

in the local area shall be instructed and 
supervised on the nature of work being 
carried out.

• Avoid working in confi ned spaces. Always 

ensure away from source, at least 2 meter of 
safety distance, or zoning of free space area 
of at least 2 meter in radius.

• Wear appropriate protective equipment, 

including respiratory protection, as conditions 
warrant.

• Ensure that the conditions within the area 

have been made safe by limit of use of any 
fl ammable material. Keep all sources of 
ignition and hot metal surfaces away.

2-3. Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 
during work, to ensure the technician is aware 
of potentially fl ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with fl ammable 
refrigerants, i.e. non sparking, adequately 
sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 
and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/
spill, isolate immediate hazard area and keep 
unauthorized personnel out.

2-4. Presence of fi re extinguisher

• If any hot work is to be conducted on the 

refrigeration equipment or any associated 
parts, appropriate fi re extinguishing 
equipment shall be available at hand.

• Have a dry powder or CO  fi re extinguisher 

adjacent to the charging area.

ACXF55-17630_YZ0218-0.indb   25

ACXF55-17630_YZ0218-0.indb   25

1/9/2018   2:24:53 PM

1/9/2018   2:24:53 PM

Содержание CS-XU9UKH-8

Страница 1: ...s ng b i ng i l p t tr c khi l p t i u khi n t xa c ng g i c ng v i d n l nh v c g b b i ng i l p t tr c khi l p t Operating Instructions Air Conditioner 20 37 Before operating the unit please read t...

Страница 2: ...ng 5 gi y hi n th th i gian theo 12 gi am pm ho c 24 gi 2 X c nh n SET S d ng i u khi n trong kho ng 8 m t t nh t i u khi n n thi t b 2 t i u khi n n thi t b AIR CONDITIONER ON OFF SET TIMER CANCEL O...

Страница 3: ...t mong mu n L n Xu ng TEMP D i nhi t l a ch n 16 0 C 30 0 C 60 F 86 F Nh n v gi n t trong kho ng 10 gi y chuy n n v nhi t t C ho c F C m n b n l a ch n M y i u h a kh ng kh Panasonic Ti ng Vi t N i du...

Страница 4: ...t v x l kh ng ng c th g y r ga i n gi t ch y n Vui l ng ki m tra l i v i i l y quy n ho c chuy n gia v lo i ch t l nh s d ng Vi c s d ng c c lo i ch t l m l nh kh c c th l m h ng s n ph m ch y n ho c...

Страница 5: ...ng Kh ng t c c thi t b d ch y tr c ng gi th i ra tr nh ch y n Kh ng gi l nh th i tr c ti p v o c y c nh hay v t nu i tr nh g y th ng t ch ho c h h i Kh ng ch m v o c nh s c c a l nh m c nh s c c th g...

Страница 6: ...g T ng t khi b o qu n ng ng c n b c k n u h b ng k p d y bu c b o qu n R32 gi ng nh b o qu n R410A Vi c v n h nh b o d ng s a ch a v ph c h i m i ch t l m l nh ph i c ti n h nh b i c c nh n vi n c o t...

Страница 7: ...n ngh c a nh s n xu t 2 2 Ti n h nh c ng vi c Tr c khi ti n h nh l m vi c tr n c c h th ng ch a m i ch t l m l nh d ch y c n tri n khai c ng t c ki m tra an to n m b o r ng m i r i ro ch y m c th p n...

Страница 8: ...i ch t l m l nh tr khi c c b ph n n y c ch t o t v t li u v n c kh n ng ch ng n m n ho c c b o v c bi t ch ng l i t c nh n n m n 2 8 Ki m tra c c thi t b i n Vi c s a ch a v b o tr c c thi t b i n ph...

Страница 9: ...n x c nh n t l kh ga ph h p t i a l 25 Ch t l ng ph t hi n r r ph i ph h p v i h u h t c c m i ch t l m l nh c d ng nh ng n n tr nh s d ng c c ch t t y r a c ch a Clo b i nguy n t n y c th ph n ng v i...

Страница 10: ...ng 24 24 thi t b v xi lanh d ng thu m i ch t ph i p ng m i ti u chu n theo quy nh d N u c th b m v i h th ng ch t l m l nh e N u kh ng th t o ra kho ng ch n kh ng c n l p i l p l i c c ho t ng tr n c...

Страница 11: ...o ki n t v n c a nh s n xu t M i ch t c thu h i s c g i l i cho nh cung c p sau khi c ng trong c c xi lanh ph h p v d n nh n Ch V n chuy n R c th i li n quan Kh ng l n c c m i ch t trong c c thi t b...

Страница 12: ...h p n y t c c a c nh o gi v qu t s ho t ng theo c i t c a i u khi n t xa N u m t i n khi m y ang ch y ch s c ph c h i ngay khi c i n tr l i ch AUTO T NG t c qu t s c t ng i u ch nh theo ch ho t ng N...

Страница 13: ...h c nhau M y ki m so t nhi t d a theo nhi t ph ng t ng t c l m m t ph ng Sau t i a 4 gi nhi t s c t theo l n thi t l p cu i c ng T c qu t c c nh AUTO nghi m c m l a ch n t c qu t Trong khi m y t t nh...

Страница 14: ...i nhi t khuy n c o ti t ki m i n COOL 26 0 C 28 0 C 79 F 82 F H ng gi ch COOL DRY L M L NH H T M N u l ch AUTO T NG c nh o gi s chuy n ng theo h ng tr i ph i v l n xu ng m t c ch t ng ch i AUTO X N u...

Страница 15: ...g 1 l n b i c c i l y quy n Kh i ngo i tr i D n s ch r c xung quanh m y L m s ch ng d n n c L i l c kh 2 tu n m t l n R a tr ng l i l c nh nh ng tr nh l m h b m t l i l c Ph i kh l i l c trong b ng r...

Страница 16: ...m u m t s linh ki n b ng nh a S b c m u t y thu c v o v t li u c s d ng trong c c linh ki n b ng nh a s b b c m u nhanh h n khi ti p x c v i nhi t nh s ng m t tr i tia c c t m ho c y u t m i tr ng B i...

Страница 17: ...gi v o v c a gi ra nh d i y c ngh a l m y ho t ng b nh th ng COOL 8 C 14 4 F M y s kh ng c s d ng trong m t th i gian d i K ch ho t ch c n ng nanoe TECHNOLOGY trong 2 3 gi nh m t c ch lo i tr m c n s...

Страница 18: ...trong nh ngo i tr i kh ng k t n i v i nhau H 34 C m bi n nhi t b l m m t kh i ngo i tr i c v n H 35 D ng i n ng c chi u c a kh i trong ngo i tr i c v n H 36 C m bi n nhi t ng d n gas kh i ngo i tr i c...

Страница 19: ...t h p v i m t k hi u h a h c Trong tr ng h p n y n tu n th c c quy nh c li n quan v h a ch t WARNING Bi u t ng n y cho bi t thi t b d ng m i ch t l m l nh d ch y N u m i ch t l m l nh b r r c ng l c...

Страница 20: ...roximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Con rm SET Use remote control within 8 m from the remote control receiver of the indoor unit 20 control receiver of the indoo...

Страница 21: ...Up Down TEMP Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for approximately 10 seconds to switch the temperature indication in C or F Thank you for purchasing Panasonic Air Conditioner The...

Страница 22: ...g will cause leakage electric shock or re Con rm with authorised dealer or specialist on usage of any speci ed refrigerant type Using refrigerant type other than the speci ed may cause product damage...

Страница 23: ...lity deterioration etc Do not use any combustible equipment in front of the air ow outlet to avoid re propagation Do not expose plants or pet directly to air ow to avoid injury etc Do not touch the sh...

Страница 24: ...ping securely seal the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certi ed personn...

Страница 25: ...on competent in the use of ammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior to beginning work on systems containing ammable refrigerants safety...

Страница 26: ...ly resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks...

Страница 27: ...ge of gas 25 maximum is con rmed Leak detection uids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refri...

Страница 28: ...standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is sit...

Страница 29: ...release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not...

Страница 30: ...ap and fan speed will operate based on remote control setting If power failure occurs during this operation this operation will be resumes immediately after power resumes For AUTO the indoor fan speed...

Страница 31: ...temperature according to room temperature to accelerate room cooling After max 4 hours the set temperature follows the last set temperature setting Fan speed is xed at AUTO fan speed selection is proh...

Страница 32: ...unit within the recommended temperature range may save energy COOL 26 0 C 28 0 C 79 F 82 F Air ow direction In COOL DRY mode If AUTO is set the ap swings left right and up down automatically In i AUTO...

Страница 33: ...Outdoor unit Clear debris that surround the unit Clear any blockage from drain pipe Air lters Once every 2 weeks Wash rinse the lters gently with water to avoid damage to the lter surface Dry the lte...

Страница 34: ...at higher speed to boost cooling performance during initial operation Discoloration of some plastic parts Discoloration is subject to material types used in plastic parts accelerated when exposed to h...

Страница 35: ...l to have the following temperature di erence between the air inlet and outlet vents COOL 8 C 14 4 F The units are not going to be used for a long period of time Activate nanoe TECHNOLOGY mode for 2 3...

Страница 36: ...ure sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor ou...

Страница 37: ...complies with the requirement set by the Directive for the chemical involved Troubleshooting Information WARNING This symbol shows that this equipment uses a ammable refrigerant If the refrigerant is...

Страница 38: ...Memo ACXF55 17630_YZ0218 0 indb 38 ACXF55 17630_YZ0218 0 indb 38 1 9 2018 2 24 58 PM 1 9 2018 2 24 58 PM...

Страница 39: ...Memo ACXF55 17630_YZ0218 0 indb 39 ACXF55 17630_YZ0218 0 indb 39 1 9 2018 2 24 58 PM 1 9 2018 2 24 58 PM...

Страница 40: ...Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2018 ACXF55 17630 YZ0218 0 ACXF55 17630_YZ0218 0 indb 40 ACXF55 17630_YZ0218 0 indb 40 1 9 2018 2...

Отзывы: