background image

8

 Safety Precautions

2-3. Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 
during work, to ensure the technician is aware 
of potentially 

fl

 ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with 

fl

 ammable 

refrigerants, i.e. non sparking, adequately 
sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 
and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/
spill, isolate immediate hazard area and keep 
unauthorised personnel out.

2-4. Presence of 

fi

 re extinguisher

• If any hot work is to be conducted on the 

refrigerating equipment or any associated 
parts, appropriate 

fi

re extinguishing 

equipment shall be available at hand.

• Have a dry powder or CO

2

 

fi

 re extinguisher 

adjacent to the charging area.

2-5. No ignition sources

• No person carrying out work in relation to a 

refrigerating system which involves exposing 
any pipe work that contains or has contained 

fl

ammable refrigerant shall use any sources 

of ignition in such a manner that it may lead to 
the risk of 

fi

re or explosion. He/She must not 

be smoking when carrying out such work.

• All possible ignition sources, including 

cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, 
repairing, removing and disposal, during 
which 

fl

 ammable refrigerant can possibly be 

released to the surrounding space.

• Prior to work taking place, the area around 

the equipment is to be surveyed to make 
sure that there are no 

fl

 ammable hazards or 

ignition risks.

• “No Smoking” signs shall be displayed.

2-6. Ventilated area

• Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the 
system or conducting any hot work.

• A degree of ventilation shall continue during 

the period that the work is carried out.

• The ventilation should safely disperse any 

released refrigerant and preferably expel it 
externally into the atmosphere.

2-7. Checks to the refrigerating equipment

• Where electrical components are being 

changed, they shall be 

fi

 t for the purpose and 

to the correct speci

fi

 cation.

• At all times the manufacturer’s maintenance 

and service guidelines shall be followed.

• If in doubt consult the manufacturer’s 

technical department for assistance.

• The following checks shall be applied to 

installations using 

fl

 ammable refrigerants.

 

- The actual refrigerant charge is in 

accordance with the room size within 
which the refrigerant containing parts are 
installed.

 

- The ventilation machinery and outlets 

are operating adequately and are not 
obstructed. 

 

- If an indirect refrigerating circuit is being 

used, the secondary circuit shall be 
checked for the presence of refrigerant.

 

- Marking to the equipment continues to be 

visible and legible. Markings and signs that 
are illegible shall be corrected.

 

- Refrigerating pipe or components are 

installed in a position where they are 
unlikely to be exposed to any substance 
which may corrode refrigerant containing 
components, unless the components 
are constructed of materials which are 
inherently resistant to being corroded or 
are properly protected against being so 
corroded.

2-8. Checks to electrical devices

• Repair and maintenance to electrical 

components shall include initial safety checks 
and component inspection procedures.

• Initial safety checks shall include but not limit 

to:-

 

- That capacitors are discharged: this 

shall be done in a safe manner to avoid 
possibility of sparking. 

 

- That there no live electrical components 

and wiring are exposed while charging, 
recovering or purging the system. 

 

- That there is continuity of earth bonding.

• At all times the manufacturer’s maintenance 

and service guidelines shall be followed.

• If in doubt consult the manufacturer’s 

technical department for assistance.

• If a fault exists that could compromise safety, 

then no electrical supply shall be connected to 
the circuit until it is satisfactorily dealt with.

• If the fault cannot be corrected immediately 

but it is necessary to continue operation, an 
adequate temporary solution shall be used.

• The owner of the equipment must be 

informed or reported so all parties are advised 
thereinafter.

Содержание CS-XU10XKH

Страница 1: ...oughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control...

Страница 2: ...the remote control receiver on the indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 P...

Страница 3: ...purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operation POW...

Страница 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Страница 5: ...not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other o...

Страница 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Страница 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Страница 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Страница 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Страница 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Страница 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Страница 12: ...manually This operation can be activated even when the unit is OFF Note that the flap and fan speed will operate according to the remote control setting If a power failure occurs during this operatio...

Страница 13: ...s to turn on the unit in iAUTO X mode How to Use To reach the desired temperature quickly For Wireless LAN Module operation setup please refer to Setup Instructions Manual To connect to a network This...

Страница 14: ...ive setting or then press The nearest timer setting is displayed and will activate in sequence The timer operation follows the clock setting on the remote control and will repeat daily when timer has...

Страница 15: ...ailure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the unit s...

Страница 16: ...cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage from the drain pipe Front panel Wash gently and dry How to remove front panel AUTO...

Страница 17: ...heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due to the air purification effec...

Страница 18: ...refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents C...

Страница 19: ...r abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mis...

Страница 20: ...1 2 3 1 2 AAA R03 3 8 m A B A 1 CLOCK 12 am pm 24 CLOCK 5 2 20...

Страница 21: ...B 2 DRY iAUTO X COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F C F 10 22 33 34 36 37 38 39 40 41 45 47 AAA R03 2 2 Panasonic Burmese 21...

Страница 22: ...22...

Страница 23: ...ELCB RCD ELCB Burmese 23...

Страница 24: ...Ni Cd nanoeTM G 24...

Страница 25: ...R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese 25...

Страница 26: ...AHU 5 1 04MPa 4 15MPa 0 25 26...

Страница 27: ...1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese 27...

Страница 28: ...2 3 2 4 CO2 2 5 2 6 2 7 28...

Страница 29: ...2 8 capacitors discharged 3 Burmese 29...

Страница 30: ...4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8 30...

Страница 31: ...8 OFN OFN OFN OFN 9 OFN 7 Burmese 31...

Страница 32: ...10 Recover Machine Recover Machine 80 11 32...

Страница 33: ...12 Burmese 33...

Страница 34: ...To adjust airflow direction LAN ON OFF FAN SPEED FAN AUTO iAUTO X AUTO iAUTO X QUIET FAN SPEED QUIET nanoeTM X nanoeTM G nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY OFF 34...

Страница 35: ...LAN 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h iAUTO X 2 C 4 F AUTO 4 iAUTO X iAUTO X 23 C 60 iAUTO X iAUTO X iAUTO X 2 C 4 F 4 Burmese 35...

Страница 36: ...2 3 1 2 1 TIMER ON TIMER OFF 22 00 OFF 2 3 36...

Страница 37: ...iAUTO X COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY iAUTO X COOL DRY iAUTO X TIMER nanoe X nanoeTM X nanoeTM X COOL DRY 2 5 nanoeTM TECHNOLOGY 2 Burmese 37...

Страница 38: ...C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT 38...

Страница 39: ...H 99 pH 7 40 C 104 F AUTO OFF ON 2 A B 1 B A AUTO OFF ON 2 1 3 4 AUTO OFF ON nanoeTM G Burmese 39...

Страница 40: ...nanoeTM G 2 2 40...

Страница 41: ...POWER TIMER ON 15 TIMER ON UV Burmese 41...

Страница 42: ...COOL nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY ON nanoeTM G nanoeTM TECHNOLOGY nanoeTM X nanoeTM TECHNOLOGY OFF LAN ON LAN 42...

Страница 43: ...AUTO OFF ON 1 2 iAUTO X AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F nanoeTM TECHNOLOGY 2 3 Burmese 43...

Страница 44: ...H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36 Gas Pipe H 37 Liquid P...

Страница 45: ...52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98 F 99 D...

Страница 46: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Страница 47: ...47 Pb...

Страница 48: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 29860 SZ0221 0...

Отзывы: